INSTALLATION INSTRUCTIONS System Controller Model No. CZ-64ESMC1U 85464369524010 CZ-64ESMC1U_eng.
Contents Page Product Information ............................................................................................... 2 Alert Symbols ........................................................................................................ 2 Installation Location ............................................................................................... 3 Electrical Requirements......................................................................................... 3 Safety Instructions ....
Installation Location • We recommend that this system controller be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the system controller. • • Do not install this system controller where there are fumes or flammable gases, or in an extremely humid space such as a greenhouse. Do not install the system controller where excessively high heatgenerating objects are placed. Electrical Requirements 1.
1. General This booklet briefly outlines where and how to install the system controller. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the controller before beginning. NOTE Give these instructions to the customer after finishing the installation. Part Name Figure Q’ty System Controller 1 Rubber bushing (7/8 in.) 4 Screws for fixture (1-3/16 in.
Installation procedure (1) Remove the flat-top screw on the bottom of the back case. When you open up the decorative cover, you will see two notches under the controller. Inset a coin or other flat object into these notches and pry off the back case. (Fig.1) (2) Connect the wires to terminal base of the system controller (see next page). (3) Attach the back case with the 2 screws (1-3/16 in.) provided.
Electrical Wiring SYSTEM CONTROLLER DC24V DC voltage pulse Photocoupler input Allowable contact voltage and current: 24 V, 10 mA Pulse width: 300 ms or more A1 A2 A3 COM No-voltage a-contact static output Allowable contact voltage and current: 30 V, 0.5 A A4 Digital Input A5 A6 Terminals for remote monitoring A1: Input for turning on air conditioners concurrently. A2: Input for turning off air conditioners concurrently.
Basic wiring diagram of control wiring A max.of 64 indoor units and 30 outdoor units can be connected in 1system. Up to 10 system controllers can be connected in 1 systems.
4. Address switch setting To avoid an electric shock hazard, DO NOT touch any terminal on the WA RNI NG Printed Circuit Board with a metal rod, a screwdriver edge nor a bare handwhen power is supplied. To Installers, After installation and adjustment, be sure to turn the BACK UP switch ON. All bits are set off when shipped from factory. PCB of the controller Dip switch How to reach the P.C. board Remove the flat-top screw on the bottom of the back case.
SW1 Main/sub selection switch OFF: System controller operates as main controller. ON: System controller operates as sub-controller. SW1 ON 1 2 3 4 5 6 7 8 OFF ALL/ZONE mode selection switch ALL mode: All indoor units can be controlled by system controller ZONE 1, 2, 3, 4 mode: Indoor units in one of zone 1, 2, 3, or 4 can be controlled by system controller. All indoor units cannot be set.
SW2 SW2 ON 1 2 3 4 5 6 7 8 OFF Auxilaly switch Must be set to OFF position. Beep tone switch OFF: Beep tone when each button is pushed. ON: No tone when each button is pushed. Indication switch Normally set to OFF position. When set to ON position, indication is not displayed on LCD of system controller. *All switches are OFF position at shipment. Fig. 6 10 CZ-64ESMC1U_eng.
5. Mode setting According to function of each system controller, set SW1 as Fig. 7. (1) Central control/Remote control mode Central control mode System controller is used as central control equipment. Individual setting by remote controller can be inhibitted by system controller. Remote control mode System controller is used as remote controller. Setting by system controller is inhibitted by other central control equipments. (2) ALL/ZONE mode ALL mode All indoor units can be controlled by system controller.
6. How to perform zone registration To operate the system controller properly, zone registration is required after finishing the test run (and after setting all indoor unit addresses) using one of the following methods.
ZONE registration table ZONE 1 2 GROUP Central address 1 Indoor unit address (UNIT No.
(a) Zone registration using the remote controller (Determination of central address) In this case, after confirming which indoor unit is connected to the remote controller and that the air conditioner in the OFF state, you set the central addresses one at a time. If the system has no remote controller, connect a remote controller to the system temporarily. Then follow this procedure. NOTE The indoor unit address must already have been set before performing zone registration.
(b) Zone registration using the system controller In this case, you set all Central addresses by system controller at once manually. and buttons at the same time (1) Press the for more than 4 seconds. and CODE No. C1 will flash. (2) After confirming that CODE No. C1 is displayed, button. Once in this mode, a change press the takes place as Fig. 10. (3) Select the zone and group No. which you want to set with and (GROUP) buttons. buttons. If already set, press the (4) Set the unit No.
(c) Automatic zone registration using the system controller and buttons at the same time for more than 4 (1) Press the seconds. and CODE No. C1 will flash. and ( ) button and (2) Select CODE. No. C2 by pressing press the button. C2 changes from flashing to ON state and automatic zone registration will start. (3) Registered GROUP No. will be disappeared all. (4) Central address will be assigned from small indoor unit address to large one in numerical order automatically.
7. How to check overlapping of central address no. (1) Press the and buttons at the same time for more than 4 seconds. and CODE No. C1 will flash. (2) Select CODE. No. C3 by pressing , ( ) button and press the button. C3 changes from flashing to ON state and will flash. Then auto. overlap checking will start. (3) If C3 changes from ON to flashing and stops flashing and disappears, there is no overlapping. Then finally, complete the auto overlap checking mode by pressing the button. (4) If some of GROUP No.
8. Memory back up switch ON OFF Check the back up switch is ON for back side of system controller PCB. Back up switch Back up battery 9. Test run (1) Power on for all indoor units. Next, power on for system controller. will flash, checking the indoor unit address automatically. (2) If group No. displayed on system controller is not same as indoor unit No.* which is connected, see Fig. 7 and setting again. *In case of group control, main unit No. only. 18 CZ-64ESMC1U_eng.