4.5 Wire and cable specifications
Wiring run Specifications Max. length
Lobby station
«
Switching hub
Cat-5e or higher, stranded,
twisted pair, straight
100 m
Power supply unit
«
Lobby station
0.65 mm (22 AWG) approx. 10 m
2 mm (12 AWG) approx. 20 m
Power supply unit
«
AC power source
1.2 mm (17 AWG)
No requirement
2 mm (12 AWG)
Lobby station
«
Electric lock
Access controller
Open door sensor
0.5 mm (24 AWG)
According to specification
of connected device.
1.2 mm (17 AWG)
Note the following when selecting wiring
R For all wiring (except network wiring), use 2-conductor (solid copper) wiring with a PE
(polyethylene)-insulated
PVC jacket.
Mid-capacitance, non-shielded wiring is recommended.
R A certified power supply wiring has to be used with this equipment. The relevant national installation and/or
equipment regulations shall be considered. A certified power supply wiring not lighter than ordinary polyvinyl
chloride flexible wiring according to IEC 60227 shall be used.