Service Manual

96
17.2 Sensible Capacity Chart
CU-XE9PKUA
208-230V Outdoor Temperature
Indoor
wet bulb
86 °F (30 °C) 95 °F (35 °C) 104 °F (40 °C) 114.8 °F (46 °C)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
62.6°F
(17.0 °C)
2.53 1.92 0.49 2.36 1.84 0.53 2.20 1.77 0.57 2.00 1.68 0.61
66.2°F
(19.0 °C)
2.55 0.54
67.1°F
(19.5 °C)
2.78 2.01 0.50 2.60 1.93 0.54 2.41 1.86 0.58 2.20 1.77 0.63
71.6°F
(22.0 °C)
3.03 2.08 0.51 2.83 2.00 0.55 2.63 1.93 0.59 2.39 1.84 0.64
CU-XE12PKUA
208-230V Outdoor Temperature
Indoor
wet bulb
86 °F (30 °C) 95 °F (35 °C) 104 °F (40 °C) 114.8 °F (46 °C)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
62.6°F
(17.0 °C)
3.33 2.53 0.73 3.11 2.42 0.79 2.90 2.33 0.84 2.63 2.21 0.91
66.2°F
(19.0 °C)
3.36 0.80
67.1°F
(19.5 °C)
3.66 2.65 0.75 3.42 2.54 0.80 3.18 2.45 0.86 2.89 2.33 0.93
71.6°F
(22.0 °C)
3.99 2.74 0.76 3.73 2.64 0.82 3.47 2.55 0.87 3.15 2.43 0.94
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
Indoor 80.6°F/66.2°F (27°C/19°C)
Outdoor 95.0°F/75.2°F (35°C/24°C)