Information

For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
ELECTRICAL SOLUTIONS
D2.143
B2.
Cable
Accessories
C1.
Wiring
Duct
C3.
Abrasion
Protection
C4.
Cable
Management
D1.
Terminals
D2.
Power
Connectors
E1.
Labeling
Systems
E2.
Labels
E3.
Pre-Printed
& Write-On
Markers
F.
Index
B3.
Stainless
Steel Ties
C2.
Surface
Raceway
E5.
Lockout/
Tagout
& Safety
Solutions
B1.
Cable Ties
A.
System
Overview
D3.
Grounding
Connectors
E4.
Permanent
Identification
One-Hole, Vertical Two-Barrel Lug
Two-Hole, Two-Barrel Lug
Dual barrel provides termination of two conductors
Made from high strength, extruded aluminum alloy to provide
premium electrical and mechanical performance
Tin-plated to inhibit corrosion
Wide wire range-taking capability minimizes inventory requirements
Inspection window to visually assure full conductor insertion
Plated steel or aluminum set screw provides high strength, durable
electrical contact between conductor and connector
UL Listed and CSA Certified for use up to 600 V and UL
temperature rated 90°C
For Use with Stranded Aluminum or Copper Code Conductors
Type LAM2SA
L
W
T
P
H2
H1
Dual barrel provides termination of two conductors
Made from high strength, extruded aluminum alloy to provide
premium electrical and mechanical performance
Tin-plated to inhibit corrosion
Wide wire range-taking capability minimizes inventory requirements
Inspection window to visually assure full conductor insertion
Plated steel or aluminum set screw provides high strength, durable
electrical contact between conductor and connector
LAM2LB connector provided with dual set screws for premium
clamping of conductor to connector for heavy duty applications
UL Listed for use up to 600 V and temperature rated 90°C
Available with NEMA hole sizes and spacing
For Use with Stranded Aluminum or Copper Code Conductors
Type LAM2B
L
HOLE
SPACING
W
T
P
H
The use of Panduit oxide inhibiting joint compound (CMP-100) is recommended for pad to pad and conductor connections. See page D2.155.
HOLE
SPACING
L
W
P
H
T
Figure 1
Figure 2
The use of Panduit oxide inhibiting joint compound (CMP-100) is recommended for pad to pad and conductor connections. See page D2.155.
*UL Listed and CSA Certified.
NEMA hole sizes and spacing.
Part Number
Conductor
Size Range
Stud Hole
Size
(In.)
Hex Key
Size
(In.)
Figure Dimensions
(In.)
Std.
Pkg.
Qty.
L W H1 H2 T P
LAM2SA300-56-3
#6 AWG – 300 kcmil 5/16 5/16 3.00 1.00 2.00 1.25 0.50 1.00 3
Part Number
Figure
No.
Conductor
Size Range
Stud Hole
Size
(In.)
Stud Hole
Spacing
(In.)
Hex Key
Size
(In.)
Figure Dimensions
(In.)
Std.
Pkg.
Qty.
L W H T P
LAM2B350-12-3Y
1 #6 AWG – 350 kcmil 1/2 1.75 5/16 4.19 1.91 1.28 0.25 3.06 3
LAM2LB600-12-3*
2 #2 AWG – 600 kcmil 1/2 1.75 3/8 5.50 2.85 1.50 0.38 3.25 3
LAM2LB1000-12-3*
2 500 – 1000 kcmil 1/2 1.75 1/2 6.19 3.48 1.88 0.56 3.44 3