Cable Fill Capacities for Cove Raceway
This information is to be used as a guide in selecting the proper size raceway. The maximum amounts may vary according to
the cable installation methods, straightness of cables, etc.
Cable fill #1: Open channel
without devices.
A = 5.4 in.
2
Cable fill #2: Open channel
with wire retainer.
A = 5.0 in.
2
Cable fill #3: Divided channel
(power and data) with
wire retainer and divider wall.
3A = 2.4 in.
2
SPEC = 40% cable fill The recommended design in cable capacity,
leaves room for future moves, adds, and changes.
MAX f
or Data = 60% cable fill The maximum cable quantity
based on cable interweaving and packing factors.
MAX f
or Power cable fill The maximum of electrical cables
based on UL temperature rise test.
3B = 2.4 in.
2
Cable fill #4: Divided channel
(power and data) with device box
and faceplate.
A = 1.6 in.
2
Cable fill #5: Divided channel
(power and data) with low profile
transition insert.
A = 1.8 in.
2
A = 1.4 in.
2
A = 2.4 in.
2
AWG dimensions represent typical outer cable diameter in inches.
CR-SR-Cove-Wirefill1
Raceway Type and
Configuration
Fill
Area
(In.²)
Electrical Cables Data Grade Cables Data Grade Cables Audio/Video
Fiber Optic
Cable
14 AWG 12 AWG 10 AWG 24 AWG/UTP CM 24 AWG/UTP CM
RG6 2 Strand
THHN/T90 Category 6 Category 6A
0.111 0.130 0.164 Dia. = 0.250 Dia. = 0.330 Dia. = 0.275 Dia. = 0.175
FILL FILL FILL FILL FILL
MAX MAX MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX
(UL Temp Rise Test) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%)
1. WCM35: No devices.
5.4 50 40 30 44 66 25 37 36 54 89 134
2.
WCM35: Using wire retainer
no devices.
5.0 50 40 30 40 61 23 35 33 50 83 124
3A.
WCM35: Power and data
using wire retainer and
divider wall.
2.41929111616243959
3B.
2.4302520————————
4A.
WCM35: Power and data
using device box and
faceplate adapter.
1.6 13 19 7 11 10 16 26 39
4B.
1.4252520————————
5A.
WCM35: Power and data
using low profile
transition insert.
1.8252520————————
5B.
2.42030111716254162