Cut Sheet
www.panduit.com
specifications
LC and SC form factor Fusion-Splice Connectors shall be TIA/EIA-604 FOCIS-3
(for SC) and FOCIS-10 compatible (for LC), and include a pre-polished fiber which
eliminates the need for field polishing and adhesives. The connectors shall be
composed of a ferrule assembly with integral fiber, a front housing, and a rear
assembly, plus additional components as necessary by connector type (including
angled physical contact polish). The connectors shall exceed TIA/EIA-568-D.3
performance requirements for IL and RL, and have a functional temperature range
from -40°C to 75°C. These splice-on connectors shall be compatible with Sumitomo
brand splice units.
applications
Single Fiber Splice-On Connectors enable rapid deployment of high performance field terminations for today’s Enterprise
and Data Center applications. Field termination allows for deployment of custom fiber links without added time and planning
typically required for pre-terminated assemblies, while using the real-time splice loss calculations of typical fusion splice
machines to enable confidence in component performance. Splice-on connectors can be used for initial installation of fiber
links, MAC work, or repairs to existing links to minimize downtime. Fusion splice connectors also allow for higher
performance links through lower insertion loss and higher return loss characteristics. Splice-on connectors require less
space for management like splice sleeves and trays, as well as reducing the amount of fiber needing management typical
of pigtail splicing.
Fusion Splice-On Fiber Optic Connectors
SPECIFICATION SHEET
technical information
Standards Requirements:
TIA/EIA-604 FOCIS-3 (for SC) and TIA/EIA-604 FOCIS-10 (for LC); TIA/EIA-568-D.3
Fiber Compatibility:
9/125um Singlemode for OS1/OS2, 50/125 Multimode for OM2, OM3, and OM4
Fiber Size and Type:
250um coated ber or 900um tight buffered ber
Ferrule Type:
Factory polished zirconia ceramic
Insertion Loss:
Singlemode ber is 0.15dB IL average, 0.30dB IL maximum; multimode ber is 0.10dB IL
average, 0.25dB IL maximum
Return Loss:
Singlemode fiber is > 55dB (UPC) or > 65dB (APC); multimode fiber is > 30dB (PC)
key features and benefits
Quick Installation
The LC and SC splice-on connectors for 250um and 900um cable can be terminated in under
two minutes per connector.
Reliable Performance
Superior components mean better performing links with less down time.
Superior Function
Factory pre-polished end-faces and no index-matching gel enable installation almost anywhere.