Technical Bulletin

Product Bulletin
Technical Information
www.panduit.com
Panduit
®
Opti-Core
®
Fiber Optic Indoor/Outdoor Interlocking Armored Cable
is an integral part of the Panduit end-to-end fiber optic solution, designed
to support today’s data needs while meeting tomorrow’s ever-advancing
network requirements. Opti-Core
®
Fiber Optic Indoor/Outdoor Interlocking
Armored Cable provides UV resistance, water-blocking, high density and
easy installation in transitional aerial and duct applications and entrance
facilities. Interlocking aluminum armor eliminates the need for inner duct or
conduit to provide a smaller crush resistant pathway for improved design
flexibility and lower installed cost. Opti-Core
®
Fiber Optic Indoor/Outdoor
Interlocking Armored Cable is tested in accordance with Telcordia GR-20,
Issue 2, GR-409 and EIA/TIA-455 series FOTPs for fiber optic cables.
Opti-Core
®
10Gig™ Fiber Optic Indoor/Outdoor Interlocking Armored Cable
features the highest quality OM3 and OM4 laser optimized fiber to support
10 Gb/s applications while maintaining compatibility with existing 50μm
multimode systems. RoHS compliant singlemode and multimode cable is
available in 6 and 12-fiber counts 6 in as a “central loose tube” design and in
24, 36, 48, 60, 72, 96 and 144-fiber counts in a “stranded loose tube” design.
For use indoors or outdoors.
Central loose tube constructions. Interlocking aluminum armor eliminates the need for inner duct or conduit.
Application
Construction
Mechanical Properties
Standards
TIA/EIA-568
ROHS Compliant
ANSI/ICEA S-83-596
ANSI/ICEA S-104-696
UL-1666
Telcordia GR-409
Telcordia GR-20
NFPA 262
CSA 22.2 No. 230
Product Bulletin
Water blocking
Yes – Dry
Inner sheath
PVC
Outer sheath PVC/ or PVDF
Tensile strength (<12 fibers)
Installation: 300 lbs. (1335 N)
Long term: 90 lbs. (400 N)
Installation: 300 lbs. (1335 N)
Long term: 90 lbs. (400 N)
Tensile strength (>12 fibers)
Installation: 600 lbs. (2670 N)
Long term: 180 lbs. (800 N)
Installation: 600 lbs. (2670 N)
Long term: 180 lbs. (800 N))
Compressive strength (crush)
250 lbs./inch
Impact
3 at 8.83 N*m
Torsion
10 cycles
Kink
IEC 60794-1-2 Method G7
Temperature range
Storage: -40º F to +185º F (-40º C to +85º C)
Operation: -40º F to +167º F (-40º C to +75º C)
Installation: -4º F to +140º F (-20º C to +60º C)
-40º F to +185º F (-40º C to +85º C)
-40º F to +167º F (-40º C to +75º C)
+32º F to +140º F (-0º C to +60º C)
Panduit
®
Opti-Core
®
Gel-Free Indoor/
Outdoor Interlocking Armored Cable

Summary of content (2 pages)