Cut Sheet

www.panduit.com
technical information
Panduit
®
Opti-Core
®
Fiber Optic Indoor Interlocking Armored Cable is an integral part of the Panduit end-to-end fiber
optic solution, designed to support today's data needs while meeting tomorrow's ever-advancing network requirements.
Opti-Core
®
Fiber Optic Indoor Interlocking Armored Cable is used within buildings to provide high-density connectivity
and ease of installation. Interlocking aluminum armor eliminates the need for inner duct or conduit to provide a smaller
crush resistant pathway for improved design flexibility and lower installed cost. Applications include intra-building
backbones, building backbones, and horizontal installations for riser (OFCR), plenum (OFCP), and harsh environments.
Opti-Core
®
10Gig
Fiber Optic Indoor Interlocking Armored Cable features the highest quality OM3 and OM4 laser
optimized fiber to support 10 Gb/s applications while maintaining compatibility with existing 50μm multimode systems.
RoHS compliant singlemode and multimode cable is available in fiber counts from 6 to 144 fibers.
Panduit
®
Opti-Core
®
Fiber Optic Indoor Distribution
Interlocking Armored Cable
SPECIFICATION SHEET
UL-1666
NFPA 262
ROHS Compliant
ANSI/ICEA S-83-596
CSA 22.2
Telcordia GR-409
standards
Water blocking NA
Inner sheath PVC
Outer sheath PVC or PVDF
construction
Used in intrabuilding backbone, building backbone, and horizontal installations and harsh environments.
application
Mechanical Properties Riser Plenum
Tensile strength(<12 bers)
Installation: 150 lbs. (667 N)
Long term: 450 lbs. (200 N)
Installation: 100 lbs. (440 N)
Long term: 30 lbs. (132 N)
Tensile strength (>12 bers)
Installation: 300 lbs. (1335N)
Long term: 90 lbs. (400 N)
Installation: 150 lbs. (667 N)
Long term: 40 lbs. (200 N)
Compressive strength (crush) 250lb/inches
Impact 3 at 8.83 N*m
Temperature range
Storage: -40°F to +185°F ( -40°C to 85°C )
Operation:- 40°F to +167°F ( -40°C to 75°C)
Installation: -4°F to +140°F ( -20°C to +60°C)
-40°F to 185°F ( -40°C to 85°C )
-40°F to 167°F ( -40°C to 75°C )
32°F to 140°F (-0°C to 60°C )
mechanical properties
Fiber Count
Cable OD
Inches
Long Term Bend Radius
Inches
Installation Bend Radius
Inches
Cable Weight
Lbs./kft
2 0.52 5.2 10.4 121
4 0.55 5.5 11.0 128
6 0.56 5.6 11.2 132
8 0.58 5.8 11.6 135
12 0.59 5.9 11.8 146
24 0.63 6.3 12.6 161
36 0.97 9.8 19.5 398
48 0.96 9.6 19.2 381
60 1.01 10.1 15.2 345
72 1.12 11.2 22.4 495
96 1.25 12.5 25.0 632
144 1.28 12.8 25.6 703
physical properties – riser