Components

Agency
Mark Agency Requirement Classification/Performance
Wiring Duct
Types/Products
Underwriters
Laboratories, Inc.
File No. E147128
UL 1565
Material Flame Class V-0
Continuous-use temperature up to 50°C (122°F)
All wiring duct
types and covers
UL 1565
CSA C22.2
No. 18.5-13
Material Flame Class V-0
Continuous-use temperature up to 50°C (122°F)
Type H, HS, HN,
and DRD
Underwriters
Laboratories, Inc.
UL 508
section 15
An insulating barrier material shall comply with the minimum material
properties indicated in Table 15.1
PVC divider walls
UL 508
sections 34
and 181
Qualifies as a metal barrier with required thickness as indicated in
Table 6.1
SD*EMI metal
barrier
Canadian
Standards
Association
File No. 016446
CSA C22.2
No. 18.5-13
Material Flame Class V-0
Continuous-use temperature up to 50°C (122°F)
All wiring duct
types and covers
(except H, HS,
and HN)
European Union
Low Voltage
Directive
2006/95/EC
CDS (cable ducting system for impact 2 J)
Minimum storage, transport, installation, and application
temperature: -5°C (23°F)
Maximum application temperature: 60°C (140°F)
Non-flame propagating
Without electrical continuity
Cover removable without a tool
H, HS, G, F, D,
MC, FS, NNC,
NE, DRD,
and TNC
EN 50085-1
EN 50085-2-3
European Union EN 45545-2
Type NNC and Type NE: Exterior (R23) - HL1
Type TNC: Interior (R22) - HL2 & Exterior (R23) - HL2
NNC and TNC
DIN German
Institute for
Standardization
DIN 43659
Specifies dimensions for slotted trunkings used in electrical
switch-gear assemblies and that conform to DIN VDE 060 Part 506
• Channel mounting hole pattern, slot dimensions, pitch, and location
• Distance from first to last like-size mounting hole
• Minimum overall product length
MC, NNC,
and TNC
DIN 5510-2
DIN 54837
Burning Class: S4
Smoke Class: SR2
Dripping Class: ST2
TNC
AFNOR French
Association of
Normalization
NF F 16-101
NF F 16-102
Type NNC Wiring Duct Classification = F3/I4
Type TNC Wiring Duct Classification = F1/I4 NNC and TNC
UNIFER Italian
Railway Standards
EN ISO 11925-2
Pass 30-second flame application
TNC
FRA – Federal
Railroad
Administration
49 CFR Part 238
Surface Flammability: < 35
Smoke Density D
s
(1.5) < 100
D
s
(4.0) < 200
TNC
NFPA – National
Fire Protection
Association
NFPA130
National Fire
Protection Agency
NFPA 79-2015,
Section 13.3.1
IEC 60332-1
Non-metallic duct shall be permitted (inside enclosures) only when they
are made with a flame-retardant material; flame-retardant material is
defined in the standard by the IEC 60332-1 test method
All wiring duct
types and covers
(except FL)
NFPA 79-2015,
Section 13.5.2
Panduit publishes a maximum percentage wire fill for common wire
types equal to 50% of the interior cross-sectional area of the wiring duct
All wiring duct
types and covers
NFPA 79-2015,
section 13.1.6.9
Panduit bend radius control accessories can be mounted at right angles
and T junctions created using wiring duct in order to maintain cable
bend radius control
Corner strip with
1" bend radius
control
European Union
European
Directive
2011/65/EU
Meets the requirements on the Restriction of Hazardous Substances
and is free of the six substances listed in the directive
All wiring duct
products
Panduit Wiring Duct Approvals and Compliances
©2016 Panduit Corp.
ALL RIGHTS RESERVED.
WDSG03--SA-ENG
Replaces WDSG02--SA-ENG
3/2016