WIRE JOINTS
J214-312
For 18 – 12 AWG WIRE
Tinley Park, Illinois 60487
PMPTI06 REV
• Pressure cable connector
• Non-Insulated
• Circular mil range: 5160-19590
• For solid and stranded CU wire
587H
• Use tool: CT-100A, CT-1570*
or CT-200
• Strip length 1/2" (11.1 mm)
• Twist all wires together
+ 1/32
– 0
CRIMPING INSTRUCTIONS – TOOL CT-100A, CT1570* and CT-200
1. Trim wires to specified strip length.
2. Firmly twist stripped wires together.
3. Insert wires into wire joint.
4. Insert wire joint in 12 – 10 crimping die. Center the crimping die over
the wire joint (see below) and crimp by closing handles firmly.
5. Trim off excess wire.