CM599D STOP READ ALL OF THE FOLLOWING INSTRUCTIONS BEFORE REMOVING CABINET FROM SKID
NET-ACCESS S-Type Server Cabinets (Server Configurations) INSTRUCTIONS CM599D © Panduit Corp. 2013 NOTE - Some views in this document may vary slightly from your actual cabinet configuration. Tool List: -Phillips screwdriver -Flatblade screwdriver -22mm socket wrench -15mm socket wrench -13mm socket wrench -8mm socket wrench -7mm socket wrench -T30 Torx bit -T25 Torx bit -6mm Allen Key -2.5mm Allen Key -Wire Cutter FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D Table of Contents - Net-Access S-Type Network Cabinets General Cabinet Operation Page Packaging Material Removal……………………………………………...…………… 4 Leveling…………………………..
INSTRUCTIONS CM599D Packaging Material Removal Before removal of packaging material: Check tip indicator on the outside of cabinet to ensure cabinet was shipped in the upright position. If tip indicator shows improper handling, inspect cabinet for damage before accepting cabinet. Before handling cabinet: Small glide strips are installed at various locations around the cabinet to protect the cabinet’s finish during shipping. These strips are to be removed prior to handling of cabinet.
INSTRUCTIONS CM599D Leveling • • • • Ensure that [4] Leveling Legs are fully retracted Slide Cabinet into final position Lower the [4] Leveling Legs until the cabinet weight is fully supported Adjust the [4] Leveling Legs so that the cabinet is level front-to-back and side-to-side Front-to-Back Cabinet Leveling [4] Leveling Legs (use 6mm Allen Key) Side-to-Side Cabinet Leveling Note: When ganging multiple cabinets together, ensure that adjacent cabinets are adjusted to the same height.
INSTRUCTIONS CM599D Floor Mounting • • • • Ensure that [4] Leveling Legs are fully retracted If Necessary, secure [2] “Shipping Hold Down Brackets” at front and rear of cabinet See Floor Mounting View below for floor mounting dimensions Attach the anchors to the floor with appropriate hardware for your type of floor [2] Shipping Hold Down Brackets [4] M10 Hex Head Screws (use 15mm socket wrench) Floor Mounting View 173mm [6.79”] DIM A DIM B: -600mm wide cabinets: 191mm [7.
INSTRUCTIONS CM599D Ganging • • • Ensure cabinets are level Secure Ganging Brackets to cabinets at [4] locations shown below Do not use Ganging Brackets to cinch cabinets together IMPORTANT: Ensure cabinets are level by following the guidelines on page 5. Leveling the cabinet prior to ganging is important to ensure proper door operation. [4] Ganging Brackets [8] M6 Torx Screws (use T25 Torx bit) For Technical Support: www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D Grounding • • • Attach Grounding Lug or Grounding Bar at any of the [6] location(s) shown below Grounding location is indicated by universal ground symbol Use M5 bonding screw [8] Grounding Lug Locations (Front and Rear of Beams) Note: top cap removed for clarity. For Technical Support: www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D Equipment Rail Adjustment • Loosen M10 Hex Head Screw at top and bottom of rear equipment rail • Adjust equipment rail to desired positon • Tighten M10 Hex Head Screw to 30.0 +/- 5.0 N-m [22.1 +/- 3.
INSTRUCTIONS CM599D Overhead Cable Openings • • • • • Remove Bezel Insert to allow for overhead cable entry Cut [8] tabs with wire cutter to open large cable openings - OPTIONAL Install M10 threaded rod into [6] tapped holes, if desired [2] 152.4mm x 152.
INSTRUCTIONS CM599D Cable Management Fingers (SN15F, SN25F) • • Insert tabs of Cable Management Finger into mounting slots of cabinet post Slide Cable Management Finger inward to lock into place Cable Managment Finger -Insert tabs into cabinet post -Slide inward to lock in place For Technical Support: www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D Single Hinge Door (Removal and Installation) • • • • VIEW 1 Pull down Compression Sleeve at top door hinge VIEW 1 Pull Single Hinge Door away from cabinet so that Top Hinge Screw fits through cutout of door VIEW 2 Lift bottom of door off Bottom Hinge Pin REVERSE STEPS to install Single Hinge Door Top Hinge Screw Compression Sleeve (Pull down) VIEW 1 VIEW 2 VIEW 3 Bottom Hinge Pin For Technical Support: www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D Single Hinge Door (Door Handle Direction Reversal) • • • VIEW 1, 2 Remove Top and Bottom Hinge Brackets from current location (remove top hinge screw, if necessary) VIEW 1, 2 Install Top and Bottom Hinge Brackets on opposite side of cabinet (re-install top hinge screw, if necessary) VIEW 3 Move Door catch to opposite side of cabinet frame Door Handle Reversal (Lay door on a flat surface) - VIEW 4, 5 • Remove Door Handle Backing Plate and rotate position of Door Handle 180º • Loosen Ca
INSTRUCTIONS CM599D Rear Split Doors (Removal and Installation) • • • Open Rear Split Doors to approximately 90º Lift Rear Split Doors up pull doors away from cabinet frame REVERSE STEPS to install Rear Split Doors For Technical Support: www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D In-Row Side Panel (Removal/Installation and Adjustment - optional) • Pull [2] Spring Loaded Hinge Pins to release Rear Side Panel from cabinet frame • Pull [4] Spring Loaded Hinge Pins to release Front Side Panel from cabinet frame • REVERSE STEPS to install In-Row Side Panels IMPORTANT: Install Front Side Panel First Spring Loaded Hinge Pins [2] Locations Spring Loaded Hinge Pins [2] Locations Spring Loaded Hinge Pin (Top and Bottom) Move Finger Pull into Slot to Lock Hinge Pin in OP
INSTRUCTIONS CM599D Cabinet Sealing Install [6] Latch Plugs [3 upper, and 3 lower] into the door latch cut-outs to the front side of the cabinet only. Install [2] foam seals to the upper and lower frame. Seal should be pressed up against the Equipment Rails, behind the latch plugs. [3] Latch Plugs Foam Seal Foam Seal [3] Latch Plugs For Technical Support: www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D PDU Bracket Adjustment • • • • PDU brackets are height-adjustable if PDU spacing other than the factory position is desired. Remove [2] M5 Torx Screws per bracket, as shown below Reposition brackets at desired distance, ensuring that mounting flange of PDU bracket rests on the outside of cabinet post.
INSTRUCTIONS CM599D Front and Rear Floor Seal Installation (Vertical Exhaust Duct ONLY) • Install Floor Seal to front or rear of cabinet frame using (2) M10x20mm Bolts. (Flange on floor seal will face outward away from the cabinet.) [2] M10x20mm Bolts (use 15mm socket wrench) Floor Seal For Technical Support: www.panduit.com/resources/install_maintain.
INSTRUCTIONS CM599D Cabinet Seal Kit Installation (Switch-Configured S-Type Cabinets ONLY*) • Install Horizontal Blanking Panel so that front face aligns with equipment rails • Install [2] Bottom Seal Brackets (Left Bracket is noted by diamond cutout) • Attach D-shaped Rubber Seal to Horizontal Blanking Panel • Attach 25mm x 50mm Foam Seals to bottoms of Horizontal Blanking Panel and [2] Bottom Seal Brackets * Example part number: S8512BA D-Shaped Rubber Seal [2] M5 Torx Screws (use T25 Torx bit) Horizont
INSTRUCTIONS CM599D Top of Cabinet Cable Manager Installation • • • Disassemble front fascia assemblies (packaged in cabinet) by removing (2) M5x0.8 button head screws (use T25 Torx bit). Remove (2) M5x0.8 button head screws (use T25 Torx bit) from front and rear of Cable Manager base. Install vertical walls on front and back of Cable Manager base using (5) M5x0.8 button head Torx screws (use T25 Torx bit). Reinstall screws from previous step to secure to the frame.
INSTRUCTIONS CM599D Top of Cabinet Cable Manager Installation (for vertical exhaust ducts) IMPORTANT - INSTALL VERTICAL EXHAUST DUCT PRIOR TO INSTALLING REAR VERTICAL WALL • Disassemble front fascia assemblies (packaged in cabinet) by removing (2) M5x0.8 button head screws (use T25 Torx bit). • Remove (2) M5x0.8 button head screws (use T25 Torx bit) from front of Cable Manager base. • Install vertical wall on front of Cable Manager base using (5) M5x0.8 button head Torx screws (use T25 Torx bit).
INSTRUCTIONS CM599D This page is left intentionally blank For Instructions in Local Languages and Technical Support: www.panduit.com/resources/install_maintain.asp www.panduit.com Page 22 of 22 E-mail: techsupport@panduit.