Cut Sheet

www.panduit.com
2 Post Standard Equipment Rack
SPECIFICATION SHEET
specifications
The data equipment rack shall meet EIA-310D standards and be
constructed of extruded aluminum or steel capable of accepting
19" wide EIA equipment.The telecommunications rack shall be
constructed of extruded aluminum and capable of accepting
23" wide telecommunications equipment. Rack construction method
shall ensure an electrically bonded structure for ease of grounding.
The 3" channel rack shall be UL listed for 1000 lbs. load rating and
the 6" channel rack shall be UL listed for 1500 lbs. load rating. The
equipment mounting rails shall be double-sided #12-24 EIA universal
mounting hole spacing. The equipment mounting rails shall include
printed rack space identification on the front and back and be
numbered up. The channel of the rack shall be capable of mounting
NetRunner
or PatchRunner
Vertical Cable Managers. 24 #12-24
mounting screws shall be included with the rack.
key features and benefits
Rack spaces
The 8' rack with 52 rack spaces allows more equipment in the same
footprint to maximize real estate for lowest cost of ownership
Extruded
aluminum construction
Designed to be lightweight and durable for easier deployment and
reduced transportation costs; UL listed for 1000 lbs.
Heavy duty
steel construction
6" channel rack designed for higher weight capacity for large
equipment; UL listed for 1500 lbs.
Printed rack
space identification
Allows for quick location of rack mounted equipment for faster
installation and less rework; see individual customer drawings for
specific rack RU numbering
Paint piercing washers
Fully electrically bonds rack components to simplify grounding
process for improved network reliability
Double-sided #12-24
mounting holes
Provides ability to mount equipment on both sides of the rack
channel for improved system flexibility
Multiple mounting hole
locations
Provides flexibility to mount to floor using any of three hole locations.
Note: Utilizing holes closest to the vertical uprights will minimize
deflection
J-bolt accessibility
J-bolt can be attached to top bracket without violating top RU space
for added stability
technical information
Dimension:
Part Number RU Height
in. (mm)
Width
in. (mm)
Depth
in. (mm)
R2P96
52 96.1 (2441) 20.3 (514) 3.0 (76)
R2P(WH)
45 84.0 (2134) 20.3 (514) 3.0 (76)
R2P79
42 79.0 (2007) 20.3 (514) 3.0 (76)
R2P48
24 48.0 (1219) 20.3 (514) 3.0 (76)
R2PS
45 84.0 (2134) 20.3 (514) 3.0 (76)
R2P6S
45 84.0 (2134) 20.3 (514) 6.0 (152)
R2P6S96
52 96.1 (2441) 20.3 (514) 6.0 (152)
R2PW
45 84.0 (2134) 24.5 (616) 3.0 (76)
Packaging: Includes right and left mounting rack channels, top and bottom brackets,
assembly hardware with paint piercing washers and anti-oxidizing paste for
complete rack bonding
3" Channel Racks – Aluminum
96" H x 19" W
#12-24 threaded rail: R2P96
84" H x 19" W
#12-24 threaded rail: R2P^
48" H x 19" W
#12-24 threaded rail: R2P48
79" H x 19" W
#12-24 threaded rail: R2P79
84" H x 23" W
#12-24 threaded rail: R2PW
3" Channel Racks – Steel
84" H x 19" W
#12-24 threaded rail: R2PS
6" Channel Racks – Steel
84" H x 19" W
#12-24 threaded rail: R2P6S
96" H x 19" W
#12-24 threaded rail: R2P6S96
2 Post Rack Accessories for 19"
Racks – Front Mount Shelves
1.7"H x 19.0"W x 15.2"D: SRM19FM1
3.5"H x 19.0" W x 15.2"D: SRM19FM2
Cantilevered Shelf Vented
5.2"H x 19.2"W x 12.5"D: SRM19CMV3
Cantilevered Shelf
5.2"H x 19.0"W x 12.5"D: SRM19CM3
Adjustable Shelf
19.0"W x 18.0"D: SRM19X18A
19.0"W x 25.0"D: SRM19X25A
Power Distribution Unit (PDU)
Mounting Bracket
2 post rack (PDU)
bracket (set of 2): R2PPDUB
Additional Hardware
100 #12-24 screws: S1224-C
Rack anchor kit for
concrete floor: RFAKIT
Rack anchor kit for
raised floor: RFA3KIT
NetRunner
Vertical Cable Managers –
7 Foot Front and Rear
45 RU, 4" x 5": WMPV45E
45 RU, 6" x 6": WMPVHC45E
Front only
45 RU, 4" x 5": WMPVF45E
45 RU, 6" x 6": WMPVHCF45E
PatchRunner
2 Vertical Cable Managers
with Doors - 7 Foot
6" W, front and rear: PR2VD06*^
6" W, front only: PR2VFD06*^
8" W, front and rear: PR2VD08*^
8" W, front only: PR2VFD08*^
10" W, front and rear: PR2VD10*^
10" W, front only: PR2VFD10*^
12" W, front and rear: PR2VD12*^
12" W, front only: PR2VFD12*^
*Add suffix 96 to the end of the part number for 8' part numbers.
^Add suffix "WH" to end of part number for white product.
Ex: R2PWH or PR2VD06WH
Panduit 2 post standard equipment rack
provides a reliable foundation for mounting
telecommunication and data center equipment.
The rack can be used to manage high
performance copper and fiber patch cables.
This modular rack system is compatible with
Panduit horizontal and vertical cable managers.
The 2 post standard equipment rack is part of a
complete rack and cable management system
that manages, protects, and showcases your
network investment.