Wire Fill
5.32”
[135.0 mm]
2.68”
[68.0 mm]
A=10.85in
2
[7005mm
2
]
TG-70 Raceway
T70C (Replacement Cover)
TG70
Raceway
Type and
Configuration
Fill
Area
(in²)
Electrical Cables Data Grade Cables Coax Cables
Fiber Optic
Cable
14
AWG
12
AWG
10
AWG 24 AWG 24 AWG 24 AWG 24 AWG 24 AWG 24 AWG 24 AWG
RG6 RG59/u 2 StrandTHHN/THWN/T90
Cat. 5e –
Plenum
Cat. 5e –
Riser Cat. 6 Cat. 6A Cat. 6A Cat. 6A Cat. 6A (SD)
0.111 0.130 0.164 DIA = 0.193 DIA = 0.225 DIA = 0.240 DIA = 0.289 DIA = 0.300 DIA = 0.330 DIA = 0.240 DIA = 0.275 DIA = 0.242 DIA = 0.175
FILL FILL FILL FILL FILL FILL FILL FILL FILL FILL FILL
MAX MAX MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX
SPEC MAX SPEC MAX
SPEC MAX
(UL Temp Rise Test) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%)
TG70: Data
Only using
Screw on
Faceplates
and Devices
10.09 ** ** ** 137 206 101 152 89 133 61 92 57 85 47 70 89 133 67 101 87 131 167 251
TG70: Data
Only using
Snap-on
Faceplates
and Wire
Retainer
10.68 ** ** ** 146 219 107 161 94 141 65 97 60 90 49 74 94 141 71 107 92 139 177 266
TG70: Wire
Retainer
without
Devices
10.85 40 40 38 148 222 109 163 95 143 66 99 61 92 50 76 95 143 73 109 94 141 180 270
TG70: Divided
Power and
Data (A)
3.16 28 28 26 ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** **
TG70: Divided
Power and
Data (B)
7.20 ** ** ** 98 147 72 108 63 95 43 65 40 61 33 50 63 95 48 72 62 93 119 179
TG70: Power
and Data
using
Snap-On
Faceplates
and 3 Sided
Power Box (A)
3.08 28 28 26 ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** **
TG70: Power
and Data
using
Snap-On
Faceplates
and 3 Sided
Power Box (B)
5.58 ** ** ** 76 114 56 84 49 74 34 51 31 47 26 39 49 74 37 56 48 72 92 139