Programming Guide
Table Of Contents
- Default Installer Code
- Default System Master Code
- How Do I Enter Programming Mode?
- Decimal and Hexadecimal Programming Table
- Trouble Display
- Data Display Mode (LED Keypads Only)
- Configuring the 1686H, 1686V and 1689 Keypads (V2.0 or higher)
- Zone Programming
- System Timers
- Programmable Outputs
- System Options
- Communication Settings
- Report Codes
- System Settings
- User Code Options
- Reprogram All Modules
- Paradox Memory Key (PMC-3)
- 4-PGM Output Modules V2.0
- Printer Module V2.0
- Voice-assisted Arm/Disarm Bus Module V2.0
- Wireless Features
- Zone Expansion Bus Modules
- User Operation
- Appendix A - Ademco CID Report Code List (Prog.)
- Appendix B - Ademco CID Report Code List (All Codes)
- Bus Module Connections
- Hardware Connections
Spectra 1759MG - 36 - Programming Guide
Hardware Connections
Single Zone Inputs
Connecting Fire Circuits, Keyswitches and PGMs
Program the PGM with the “[PG]/[FNC1] Key
was pressed” Activation Event so that the
smoke detectors can be reset by pressing the
[
PG] or [FNC1] key. See Event Group # 5 on
page 9.
All 4-wire smoke detectors must be
connected using the daisy chain
configuration.
Programming a Wireless Fire Zone
Fire zones cannot be assigned to expansion zones. As
a result, when installing a wireless smoke detector, the
corresponding zone must be programmed as follows:
1) Enter [5] in the Zone Definition to define it as a
24Hr Burglary Alarm (see page 7).
2) Disable [4] and enable [5] in Zone Options to set
the zone’s alarm type to a pulsed Audible Alarm
(see page 7).
3) Disable [1] and [2] in Zone Options to disable the
zone’s Auto Zone Shutdown and Bypass Enabled
features (see page 7).
Fire Circuits
4-Wire Installation
Control Panel Terminals
Keyswitch PGM
4) Change the zone’s report code from a Burglary Report Code (Prog. Value
11) to a Fire Report Code (Prog. Value 04). See Appendix A on page 30. If
using Ademco Contact I.D., set the Contact ID Options from All Codes to
Programmable (section [136] option [3] = OFF) and then enter the report
code manually (see page 14).