Programming Guide

Spectra 1759MG - 36 - Programming Guide
Hardware Connections
Single Zone Inputs
Connecting Fire Circuits, Keyswitches and PGMs
Program the PGM with the “[PG]/[FNC1] Key
was pressed” Activation Event so that the
smoke detectors can be reset by pressing the
[
PG] or [FNC1] key. See Event Group # 5 on
page 9.
All 4-wire smoke detectors must be
connected using the daisy chain
configuration.
Programming a Wireless Fire Zone
Fire zones cannot be assigned to expansion zones. As
a result, when installing a wireless smoke detector, the
corresponding zone must be programmed as follows:
1) Enter [5] in the Zone Definition to define it as a
24Hr Burglary Alarm (see page 7).
2) Disable [4] and enable [5] in Zone Options to set
the zone’s alarm type to a pulsed Audible Alarm
(see page 7).
3) Disable [1] and [2] in Zone Options to disable the
zone’s Auto Zone Shutdown and Bypass Enabled
features (see page 7).
Fire Circuits
4-Wire Installation
Control Panel Terminals
Keyswitch PGM
4) Change the zone’s report code from a Burglary Report Code (Prog. Value
11) to a Fire Report Code (Prog. Value 04). See Appendix A on page 30. If
using Ademco Contact I.D., set the Contact ID Options from All Codes to
Programmable (section [136] option [3] = OFF) and then enter the report
code manually (see page 14).