To REPEAT the call to the same Remote Unit, it will be sufficient to press F7
"QUERY". The operation can be repeated as many times as needed and can be
used to control in real time an eventual variation of the working parameters of the
Remote Unit (line resistance, battery voltage, radio signals intensity).
To call a different Remote Unit, it will be necessary to use F9 "UNIT" as
previously described.
2.3.1 DATA MODIFICATION
Data, as received from a Remote Unit and displayed on the screen of the Base
Unit TX2000, can be edited following the show requirements.
With reference to the pictures of the previous example (data received from the
Remote Unit #3), let us see, step by step, how to proceed.
It must be pointed out first as some of the displayed data are relative to real-time
measurements or factory settings and thus they cannot be edited. In detail:
- LINE: this is the line number of a specific Remote Unit for each of its 24
lines. The line numbers are PERMANENTLY ASSIGNED for each Unit
and thus, when a Remote Unit is called, they are automatically defined.
- TER: this is the physical position of the binding posts of a specific line on the
panel of the Remote Unit. In our example, TER 3 means the third couple of
terminals of Unit #3: this couple has been permanently given the line number
51.
- RES: this is the value, measured in OHM, of the line resistance connected to
the terminals of the Unit. This measurement is made each time the Unit or a
specific line is called. All lines with a resistance greater than 99 ohm, or NOT