Brochure

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH
Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 11
V
R-407C (AC9000), R-22
Z
R-410A (OE only)
Capacity
Parker’s expansion valves
offer a range of capacities
from 1/8 ton to 70 tons, de-
pending on refrigerant. See
pages 15-18 for capacity
tables.
Rainbow Charge™
Refrigerant Designation
Charge Operating Temperature Range
VCP 100, VGA, ZCP200
Air Conditioning
-10 0 10 20 30 40 50 60
Evaporator Temperature °F
TEV Model Number Selection Guide
Maximum
Operating
Pressure
(MOP)
100
Valve
Charge
CP
Refrigerant
Nominal
Capacity
in Tons
15
External
Equalizer
(Optional)
E
Valve
Model
EBS V
(E) for Externally Equalized
Evaporator pressure drop > 3 psi
BLANK for Internally Equalized
Evaporator pressure drop < 3 psi
or smaller tonnage evaporators
See Catalog E-1a, TEV and AEV
Theory & Application.
Charge Type
"W” (all-purpose) liquid charge maintains nearly flat superheat control over a -40°F to +60°F (-40°C to +15°C) evaporator temperature range.
“Z” (low temperature) charge provides fast pulldown benefits like a gas charge with the non-migrating benefits of a liquid charge; usable over a -40°F to 0°F
(-40°C to -20°C) evaporator temperature range.
“X” (damped response) gas charge provides a pressure limiting (MOP) charge with anti-hunt characteristics over a -40°F to +60°F (-40°C to +15°C) evaporator
temperature range.
Notes: M.O.P. not available on “W” or “Z” charge.
*May not be used on systems in which bulb temperature will exceed 130°F (i.e. defrost). Contact Parker for pressure and temperature.
1. Maximum operational pressure 500 psig (35 bar).
2. Maximum storage temperature 130°F (55°C) .
3. Consult Parker for pressure and temperature exceptions.
4. Do not use “W” or “Z” liquid charges in applications where bulb temperatures can exceed 130°F (55°C).
For these applications use type “X” MOP gas charge only.
Nomenclature (Example) – EBS, OE Valves