Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 17
Capacity Tables
Valve Type
Nominal
Capacity
(Tons)
Evaporator Temperature °F
40°F 20°F 0°F
Pressure Drop (PSI)
120 160 200 240 280 320 120 160 200 240 280 320 120 160 200 240 280 320
HC(E) 1-1/2 1.30 1.50 1.68 1.84 1.98 2.12 1.27 1.47 1.64 1.80 1.94 2.08 1.22 1.41 1.58 1.73 1.87 1.99
HC(E) 3 2.60 3.00 3.35 3.67 3.97 4.24 2.55 2.94 3.29 3.60 3.89 4.16 2.44 2.82 3.15 3.45 3.73 3.99
HC(E) 5 4.33 5.00 5.59 6.12 6.61 7.07 4.24 4.90 5.48 6.00 6.48 6.93 4.07 4.70 5.25 5.76 6.22 6.65
OZE 20 17.1 19.7 22.1 24.2 26.1 27.9 16.7 19.3 21.6 23.7 25.6 27.3 15.8 18.2 20.4 22.3 24.1 25.8
OZE 25 20.5 23.7 26.5 29.0 31.3 33.5 20.1 23.2 25.9 28.4 30.7 32.8 19.0 21.9 24.5 26.8 29.0 31.0
OZE 35 28.2 32.6 36.4 39.9 43.1 46.1
27.6 31.9 35.6 39.0 42.2 45.1 26.1 30.1 33.6 36.9 39.8 42.6
OZE 50 42.7 49.3 55.2 60.4 65.3 69.8 41.8 48.3 54.0 59.1 63.9 68.3 39.5 45.6 51.0 55.8 60.3 64.5
OZE 60 51.3 59.2 66.2 72.5 78.3 83.7 50.2 57.9 64.8 71.0 76.7 82.0 47.4 54.7 61.2 67.0 72.4 77.4
R-410A Capacities in Tons
Valve Type
Nominal
Capacity
(kW)
Evaporator Temperature °C
5°C -5°C -15°C
Pressure Drop (BAR)
8 11 14 17 20 23 8 11 14 17 20 23 8 11 14 17 20 23
HC(E) 5 4.49 5.27 5.94 6.55 6.55 7.62 4.40 5.16 5.82 6.41 6.41 7.46 4.29 5.02 5.67 6.25 6.25 7.27
HC(E) 11 8.98 10.5 11.9 13.1 13.1 15.2 8.80 10.3 11.6 12.8 12.8 14.9 8.57 10.0 11.3 12.5 12.5 14.5
HC(E) 18 15.0 17.6 19.8 21.8 21.8 25.4 14.7 17.2 19.4 21.4 21.4 24.9 14.3 16.7 18.9 20.8 20.8 24.2
OZE 70 59.8 70.1 79.1 87.1 94.5 101 58.5 68.6 77.4 85.2 92.5 99.2 55.7 65.3 73.7 81.2 88.1 94.5
OZE 88 71.7 84.1 94.9 105 113 122 70.2 82.3 92.8 102 111 119 66.9 78.4 88.5 97.5 106 113
OZE 123 98.6 116 130 144 156 167
96.5 113 128 141 153 164 92 108 122 134 145 156
OZE 176 149 175 198 218 236 253 146 171 193 213 231 248 139 163 184 203 220 236
OZE 211 179 210 237 261 284 304 175 206 232 256 277 297 167 196 221 244 264 283
R-410A Capacities in Kilowatts
Refrigerant
Liquid Temperature Entering TEV
0°F 20°F 40°F 60°F 80°F 100°F 120°F 140°F
Correction Factor, CF Liquid Temperature
R-410A 1.79 1.63 1.47 1.32 1.16 1.00 0.83 0.62
These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of 0°F. However, they may be used for any evaporator temperature from
0°F to 40°F since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature – Example: Actual capacity of an HCE-3 using R-410A
at a 40°F evaporator, 160 psi pressure drop across the TEV, and a 80°F liquid temperature entering the
TEV = 3.00 (from rating chart) x 1.16 (CF liquid temperature) = 3.48 tons
Refrigerant
Liquid Temperature Entering TEV
-10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C
Correction Factor, CF Liquid Temperature
R-410A 1.73 1.59 1.44 1.30 1.15 1.00 0.84 0.65
These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15°C. However, they may be used for any evaporator temperature from
-15°C to 5°C since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature – Example: Actual capacity of an HCE-3 using R-410A
at a 5°C evaporator, 11 bar pressure drop across the TEV, and a 30°C liquid temperature entering the
TEV = 10.5 (from rating chart) x 1.15 (CF liquid temperature) = 12.1 kW