- Parker ACR Motion Controllers User Guide

Parker Hannifin
196 Aries User Guide
must cross, cross them at 90° to each other. Keep wiring supported and
close to cabinet metalwork.
Cables may require the use of ferrite core suppressors
.
Some installations may require that you take additional EMC measures.
To further increase product immunity and reduce product emissions,
you may add clip-on ferrite absorbers to all cables. Parker recommends
ferrites with at least 200 ohm impedance at 100 MHz, such as the
following:
Steward Ferrite Part number 28A2024
Fair-Rite Part number 0443164151
Note: These ferrites are available from Parker Hannifin, part number 47-015956-01.
For larger diameter cables (up to 0.722 in O.D.), Fair-Rite part number
0444176451 is recommended.
Your Installation may require additional EMC installation hardware
(as shown in illustrations).
The following clamp kits are available from Parker:
Clamp Type Parker Part Number
R-Clamp Kit (10 per) for models
AR-02xx to AR-13xx
R CLAMP KIT
R-Clamp Kit (10 per) for models
AR-20xE and AR-30xE
R LARGE CLAMP KIT
Clamshell Clamp Kit (2 per)
for all models
CLAMSHELL KIT
Table 62 Enclosure Mounting Clamps
Note: The Control power input also requires a mains power line filter,
varistors, and fuses in order to comply with the relevant CE directives.