Switch-on status
COMPAX-M / -S
10
5. Switch-on status
5.1 Configuration when supplied
When supplied, COMPAX is not configured. Parameter P149 is set to "0":
P149="0": COMPAX is not configured and switches to OFF mode when switched
on (24V DC and operating voltage) (motor switched off). In addition to
this, when switched on, all parameters (apart from bus settings P194,
P195, P196 and P250) are set to their default values.
P149="1": COMPAX is configured and once switched on (24V DC and operating
voltage) tries to engage the motor.
5.2 Commissioning
Meaning of LEDs on the front panel
COMPAX-M / -S
LED Color Meaning, when switched on
Ready green
24V DC present and initialization complete
Error red
COMPAX - Error (E1...E56) present or COMPAX is
initialized.
Mains module
LED
red
Error
LED
green
Ready
Possible errors
off on no errors
on off Heat sink temperature too high or
error in logic voltage (24V DC too low or unit is defective)
Emergency stop is activated and ready contact is
released.
on on Ballast switching unit overload or
undervoltage (<100V DC or <80V AC).
COMPAX 1000SL
Status Red LED (H2) Green LED (H1)
24V not available off off
24V are switched on, boot up on off
Unit OFF off blinking
Unit error; drive switched off on blinking
Unit error; drive powered on on
Unit RUNNING off on
Caution!
If there is no control voltage, no displays will appear to indicate
that operating voltage is present.
With Error E40, external enabling is missing with COMPAX 45XXS, COMPAX
85XXS and COMPAX 1000SL (Hardware input).