- Parker Compact Servo Controller User Guide

Interfaces
Digital inputs and outputs
149
Unit
hardware
Connector
assignment / cable
Technical dataConfigurationPositioning and
control functions
Optimization
functions
InterfacesAccessories /
options
StatusParameterError list
Input I5
Starts the program data record at WAIT
START, after Power On and after STOP.
Performs the next data records (commands)
before the next WAIT START command, an
END instruction or a STOP or BREAK signal.
O4 "Ready for start" is reset.
Once a positioning process has been
interrupted by STOP (I6="1"), the process can
be continued, when START (I5="1") is
present, using a descending flank at STOP
(I6="0").
Input I6
The positioning process is interrupted using "1" and the axis is stopped in a
controlled manner.
O4 "Ready for start" and O6 "Idle after stop" ="1".
A new start command is required to complete the positioning process. When
START is present, resetting the STOP signal is sufficient (I6="0").
Input SHIFT I2
Finds the machine zero point (when using reversing initiators: process velocity:
P3 - the direction of the search can be determined using the P3 sign ; ramp
time: P7).
Once the MZ is reached, output O3 "Machine zero approached" is set. This
remains set until another "Find MZ" order is issued.
Output O5 "Programmed position reached" ="0".
The data record indicator is reset to N001.
Reference travel, prompted by the digital inputs, interrupts a positioning
command specified by the interfaces (POSA, POSR, LOOP).
Input SHIFT I3
The axis travels to the real zero point (process velocity: P4; ramp time: P8).
O4 "Ready for start" ="0" until RZ is reached.
Output O5 "Programmed position reached" ="0", and once real zero is
approached ="1".
Data record indicator is reset to N001.
In continuous mode the axis does not move; the data record indicator is set to
N001.
Input SHIFT I4
The current position of the axis is used as the reference point (real zero) for all
positioning instructions; i.e. P1 is modified.
The data record indicator is set to 1.
The real zero is stored protected against power failure.
O4 "Ready for start" is not modified.
The teach in function can be switched off using P211.
The function does not operate in continuous mode.
START
Temporal course of a start sequence:
O4 (ready for start) = "1" ?
yes
no
I5 (start signal) = "1"
O4 (ready for start) = "0" ?
I5 (start signal) = "0"
yes
no
drive to MN
Note!
STOP
Find MZ
Approach RZ
Teach in real
zero (Teach Z)