- Parker Compact Servo Controller User Guide

Start-up manual
COMPAX-M / -S
Technical data / Connections of inputs and outputs
54
7.9.3 Technical data / Connections of inputs and outputs
0
1 over 9.15V means that "1" is recognised
1
0 over 8.05V means that "0" is recognised
1. O1...O16 Total of max. 1.6A
2. O1...O4, O5...O8,
O9...O12, O13...O16
Per group of 4, max. 0.8A; taking due account of 1.
3. O
per output, max. 0.3A and 40nF capacitive
4
; taking
into account 1. and 2.
Per output, max. 0.3A
In total a sum load for all 8 outputs of max. 0.48A and
40nF capacitive
5
;
If overload occurs, an error message appears (E43: can be acknowledged with
Power off/on); the corresponding group of four is switched off.
10nF
22K
12K
F23
22K
X8/7
PLC
24V
0V
X11/1
X11/2
22K
X11/7
100K
X19/23
X19/14
X19/.
(X19 applies for COMPAX 1000SL)
F23
PLC
24V
0V
X8/15
4.7K
X19/14
X11/1
X11/2
X11/7
X19/23
X19/.
(X19 applies for COMPAX 1000SL)
For reasons of interference protection, we would recommend that you use a
screened cable for the digital inputs and outputs.
With COMPAX 1000SL, the screen is connected with the Sub-D housing.
A protective connection is required when there is inductive load present.
F23
24V
0V
X8/15
4.7K
X19/23
X19/14
X11/1
X11/2
10nF
22K
12K
22K
X8/7
24V
0V
X11/2
22K
F23
100K
X19/.
X19/14
X19/.
X19/23
X11/1
(X19 applies for COMPAX 1000SL)
4
A maximum of 4 COMPAX – inputs can be connected to one output.
5
A maximum of 4 COMPAX – inputs can be connected to one output.
Detection of input
signals:
Load on outputs
(not applicable for
COMPAX 1000SL):
Load on outputs for
COMPAX 1000SL:
Input connection
using I7 as an
example
Output connection
using O7 as an
example
Input/output
connection for
2 COMPAXs
1st COMPAX 2nd COMPAX
COMPAX
COMPAX