Installation Manual

Table Of Contents
11.
Appendix: Loop and Cable Condition Test
Measure loop inductance/resistance for each order point, recommend replacement in comments section if needed.
You must conduct two separate tests on the Inductance Loop to determine it’s condition:
A.
Lineal Conductor Resistance and Inductance
This test measures the Resistance and the Inductance of the loop conductor or wire at the Basestation.
Procedure
To measure the inductance and resistance of the loop wire, use test equipment such as an LCR meter (Inductance
[L], Capacitance [C], and Resistance [R]).
A reading of 1.2 for resistance and 100120μH (or 20μH / wire turn) for inductance are acceptable measurements
that reflect good wire condition.
B.
Insulation Resistance
In addition to the factors mentioned above, ice, water, frost, etc. can contribute to the change of the conductor’s
resistance. However, measuring the conductor’s resistance alone may not provide a complete picture, as it does not
account for insulation leakage to the ground/earth. Insulation leakage can be checked by utilizing a Megohm meter
(or a Megometer or Megger Meg Out, in industry parlance) capable of testing up to 500 megohms (500 million
ohms).
In this test, a DC voltage is applied to the loop wire to check for insulation damage that may cause a short circuit when
normal power is applied. The Meggers have settings capable of delivering anywhere from 5001000 volts through the
loop. DO NOT apply more than 500 volts for this test or you may damage the insulation. The cable’s insulation is rated
at 600 volts.
Procedure
1.
Disconnect the loop wires from the loop detector so the loop is floating.
2.
Place one of the meter leads to the loop wire and the other to the ground/earth.
Resistance above 20 megohms
Acceptable
Resistance below 20 megohms
Loop wire insulation has been damaged
Loop integrity is questionable
Resistance less than 10 megohms
Loop wire must be replaced
63 Installation Instructions G5 Release A