EFBC-4L FLUORESCENT DIMMING BALLAST CONTROLLER Configuration
3?>>53D?B<575>4
CONNECTOR J1
AN1-4
0-10VDC analog inputs
COM
Analog input common
D+
DMX Data+ input signal
D-
DMX Data- input signal
COM
Data common
CCL
Contact closure input (switch to COM)
CONNECTOR J2
JUMPER TO SELECT CORRECT CARD POWER
SUPPLY VOLTAGE
JP1
DMX Termination (shorted = terminated)
JP2
FACTORY USE ONLY
Use Class 2 or Limited Voltage/Limited Current
Source only
CAUTION:
1) Before applying power, ensure that J2 is set for the correct supply voltage or damage will result
2) Use Stranded Conductors only, Rated Min 75° C / 167° F
WARNING:
1) Use only with Lutron Hi-Lume
®
FDB or ECO 10™ Electronic Ballasts
GND
AC Ground
GND
AC Ground
NEUT
Card power supply NEUTRAL input
LINE
Card power supply LINE input
SH1A
Circuit 1 AC hot circuit
SH1B
Circuit 1 switched hot
DH1
Circuit 1 dimmed hot
SH2A
Circuit 2 AC hot circuit
SH2B
Circuit 2 switched hot
DH2
Circuit 2 dimmed hot
SH3A
Circuit 3 AC hot circuit
SH3B
Circuit 3 dimmed hot
DH3
Circuit 3 dimmed hot
SH4A
Circuit 4 AC hot circuit
SH4B
Circuit 4 switched hot
CONNECTOR J3
DH4
Circuit 4 dimmed hot
Hi-Lume
®
and Eco-10™ are registered trademarks of Lutron Electric Company Inc.
OP4
REV.6 9824
OP3
OP2
OP1
LINE
120V
240V
277V
GND
GND
NEUT
LINE
SH1A
SH1B
DH1
SH2A
SH2B
DH2
SH3A
SH3B
DH3
SH4A
SH4B
DH4
RUN
FL1
FL2
FL3
FL4
RxD
For continued protection
against risk of fire,
replace only with same
type & ratings of fuse.
F1: 250 V / 200 mA
F2: 250 V / 2A
SN Serial #