Owner's manual

٨
٨
٨
Please be careful to wire the unit according to the following instructions. Mis-wiring will damage the internal circuitry and could cause a fire.
This product is for indoor use only. It should be used in a place where it is protected from rain and water. Moisture in the unit could cause a
breakdown of the unit or electric shock.
Warning
Do not use this product in a corrosive gas atmoshere.
Caution
8077-F
'09.4,AUTO
8077-F
T95100062
FT003
TO OPERATE THIS PRODUCT SAFELY, PLEASE OBSERVE THE FOLLOWING
㧵㧺㧿㨀㧾㨁㧯㨀㧵㧻㧺 㧹㧭㧺㨁㧭㧸
[ TYPE : PHC-100A
Thank you for purchasing the PC-Output Relay Unit,PHC-100A. To ensure proper operation, prease read
this instruction manual thoroughly before attempting to use the system. Also, when undertaking maintenance,
inspection or repair work, be sure to refer to this manual. If you have any questions regarding this product,
please feel free to contact us.
PC-Output Relay Unit
1.Parts name
5.Specifications
Model PHC-100A
Rated voltage 24V DC
Operative voltage range 108V AC132V AC (AC adaptor (bundled))
Power consumption Approx. 4W
Operative temp. range 0͠㨪40͠
Operative humidity range 85RH
Dielectric strength
Insulation resistance
To be measured by an insulation measuring device of 500VDC between the power terminal and the case. More than 1Mǡ
1000VAC being applied between the power terminal and the case for 1 minute. Not braking insulation
Anti-noise 1500Vp-pޓPals range 1Ǵsecޔ100nsec
Vibration proof
19.6m/s
2
Mass Unit: Approx. 300 g Supplied AC adaptor: approx. 160g
Serial communication
Serial interface: RS-232C compliant
Transmission modeHalf-duplex mode , Transmission codeASCII code
Synchronous modesynchronous mode , Communication speed9600bps
Data length8 bit , Stop bit1 bit
Parity, Flow Control: no setting required
Connector D-SUB9PޓMale connectorޓ
٨
٨
PATLITE Corporation disclaims all liability for any malfunction or damage occurring as a result of handling contrary to the instructions,
cautions and warnings mentioned in this manual.
Specifications are subject to change without notice.
Caution
Reset switch
Intemal contact
Output terminal
Momentary switch with green power monitor LED
On : All switch outputs are turned off
: All the communication command is invalid.
Off : Usual operation. CTS line of RS-232C is on and switch LED is on.
(
1800
)
60 41
44
Jack
O.D.㧦Ǿ5.5
I.D.㧦Ǿ2.1
ធὐኈ㊂
ޓޓޓޓޓޓޓ
߹ߢ
Contact capacity
125V AC,3A
30V DC,3A
87654321
࡝࡟࡯ធὐNo.(Relay contact No.)
㔚✢ⵍⷒ೸߈㐳ߐ㧦9mm(Strip)
න✢:
Ǿ
0.41.2mm(Single wire)
᠐✢:0.30.75mm
2
(Twist wire)
MODEL
PHC-100A
Reset switch
RS-232C
Power
24V DC
૶↪น⢻㔚✢
Applicable wire
115
117.5
100
Connect-disconnect lever
Wire insert point
AC adaptor connection
RS-232C port
(
D-SUB9 pin
)
Output terminal block
̪Lot number indicated
Reset switch with green power monitor LED
31
35
#4-40UNC Inch screw
٨
٨
ޓ
٨
Be sure to turn the power off before wiring. You may short-circuit the PCB or experience an electric shock.
Since this product uses screwless terminals, be sure to follow the instructions in this manual regarding wire type, wire diameter, and strip
length. Otherwise, there may be bad connections, excessive heating, or wires coming out of the terminals.
Make sure to insert the wire all the way to the bottom of the receptacle so that none of the stripped section is showing.
Otherwise there may be faulty operation, leakage or fire if the stripped section touches the product or if the wire comes out.
Warning
2.How to make wiring connection
٨
ޓ
٨
The capacity of the internal contact is AC125V(DC30V), 3A. When inductive loads such as bulbs or motors are used, there is an
increase in current, which may shorten the life of the internal contact.
If the load current exceeds the capacity, or there is excessive inrush current, it may cause burning or welding of the contact.
This product is to be connected to one RS-232C serial port. Do not connect other devices simultaneously.
Otherwise, the result may be malfunction or damage to the serial port or devices.
4.Before requesting service
Substance
AC adaptor (bundled)
Caution
Please check the list shown below before requesting repairs. If the product still does not work, please contact us for repairs.
Please feel free to contact our sales office with any questions concerning the product.
For inquiry, you are required to identify the number indicated on the name plate of the product.
Power lamp stays
turned off
No reply (ACK, NACK)
Confirm if supplied adaptor is securely inserted to a wall socket.
Confirm if an adapter jack is securely inserted to the main body.
Confirm if straight cable is used
Confirm a communication condition and protocol
Set ID to ??"[3FH, 3FH]
Confirm an end code "!"[21H]
Confirm if the reset switch is not being pressed
Problems What to do
Please note that any malfunction or damage resulting from modification is not guranteed under the warranty.
̪
NOTES TO BE OBSERVED FOR SAFE OPERATION
عThe indications for warning are divided into the following classes according to the degree of danger or damage incurred when the warning is not taken
into consideration and the product is not corrently used.
Note to be followed to prevent any damage to the user and other personnel or to assets are as follows:
This symbol marks important instructions that, if ignored or incorrectly followed, could conceivably lead to death or serious injury.
This symbol marks important instructions that, if ignored or incorrectly followed, could conceivably lead to injury or property damage.
Caution
Warning
Terminal : Screwless terminal, Number of terminals: 16,
Applicable wire: Solid wire Ǿ0.4㨪Ǿ1.2mm (AWG26AWG18)
ޓޓޓޓޓޓ Stranded wire Ǿ0.3㨪Ǿ0.75mmޓ(AWG22㨪㧭㨃㧳20)
̪In case of using stranded wire, make sure to use an element wire which has more than Ǿ0.18mm diameter.
Contact:Non Voltage contact, Number of contacts:8, Contact Capacity: AC125V,3A/DC30V,3A
Life: Min. 200,000 operating (Rated Load, Operating 1,800times/h)
2
㧙㧝㧙
㧙㧠㧙

Summary of content (2 pages)