PROXIMITY compact slimline Ins-152 Date code: 180101
Contents Contents ......................................................................................................................................................................... 2 Introduction ................................................................................................................................................................. 3 About ...........................................................................................................................................
Introduction The PROXIMITY compact system is the ideal solution in access control situations where no central programming or reporting is required. Voiding and validating of users is achieved with the unique shadow card system, and all system programming is performed with the easy to use function cards. The PROXIMITY compact reader contains all the electronics inside the reader, from which come three cable pairs, connecting to the power, electric release and optionally, an exit button.
Power supplies Paxton supplied Paxton Access Ltd offer these power supply solutions. Table showing power supplies available from Paxton Access Ltd Part number 339-424 430-166 339-425 862-719 998-260 Description 12Vdc boxed backup power supply 1A 12Vdc boxed backup power supply 2A 12V 1.2AH battery for 1A boxed PSU 12V 7AH battery for 2A boxed PSU 1A 12V d.c.
Locks Fail open (fail safe) Fail open devices require power to lock, i.e. if there is no power to the device it is unlocked. An example of a fail open device is a magnetic lock (maglock). A fail open locking device is a requirement for fire doors. This is because it is not reliant on electrical power to unlock. It is advisable to have a battery backup for systems using fail open devices. Otherwise a mains power failure would lead to doors unlocking for the period of the mains failure.
Fitting Reader 1. 2. 3. 4. PROXIMITY compact slimline reader Using the base plate as a template, mark and drill holes for the cable and the four screws. Tap the four small wall plugs into the wall. Fix the base plate securely with the screws provided. Feed the reader cable through the back plate and hang the reader at an angle over the back plate. Then slot the reader into the groove at the top of the base plate and press the reader into place. Screw in the securing screw at the base of the reader.
Wiring Black Door exit (push to make). Note - this input can be connected to an entryphone but only via voltage free contacts 0V d.c. Red +12V d.c. Blue D.C. POWER SUPPLY 12V Blue DO NOT USE A.C. SUPPLY PROXIMITY compact slimline reader black 569-117BL Wiring Green 0V d.c. Yellow +12V d.c. Green/yellow lock wires will drive up to: 500mA continuous (750mA for up to 7 seconds) Positive wire is yellow Total load must not exceed PSU capacity.
Commissioning Initialising the system After the system has been wired up, be sure to check over the connections against the wiring diagrams provided BEFORE powering up for the first time. When the system is powered up for the first time all the LEDs will be lit. After just a couple of seconds all the LEDS will start flashing.
All the LEDs will now flash. The unit is waiting to be Enrolled Operation PROXIMITY User tokens This is the generic term used to describe all PROXIMITY devices created by Paxton Access. It covers PROXIMITY ISO cards, PROXIMITY cards and PROXIMITY keyfobs. All users of the system carry round the PROXIMITY User token. They can gain access through a door by presenting the PROXIMITY User token to the reader.
Using function cards – Function card pack PROXIMITY Green, Amber and Red Zone cards These 3 cards toggle the green, amber and red access levels on and off. By default all the levels are active (this means the LEDs on the reader are lit). This in turn allows the green, amber and red PROXIMITY user cards access. If the PROXIMITY Green zone card is presented to the reader, the green LED will go out and the reader will beep twice quickly.
Fault-finding See Commissioning - checking the system Tech Help The technical help line is open from 7:00am – 7:00pm, Monday – Friday, Contact us on 0870 608 0886 Before calling, run through the following: • • • • • Be prepared to give out company details Be next to or very near to the system in question Have a copy of the instructions ready to hand Have the unit serial number to hand Have appropriate tools ready to use.
Applications Standard Installation If the correct token is presented to the reader, the release is powered and the door unlocks. The lock output can drive a 12V dc load directly up to 500mA continuously or 750mA for 7 seconds. Positive wire is yellow. Total load must not exceed PSU. Exit button A standard bell push button (push-to-make) can be used to provide electronic exit. When the button is pressed the door’s electric release is activated. Any number of exit buttons can be fitted.
Changing zone operation The PROXIMITY compact reader has been set up to change the zone colour at a time set by a time clock. A standard central heating timer, with voltage free contacts, can be used to provide the timing function. This function can be used, for example, to restrict access outside working hours to senior staff only Hold door open The PROXIMITY compact reader has been set up to hold the door open at a time set by a time clock. A central heating timer is ideal for this.
Specifications Maximum number of users ................................................................................................................................... 10,000 Time clock input .......................................................................................................................................................... Yes Colour access zones ..........................................................................................................................................