Specification

R-25209_000 2021 07 06 RPT - Peak AQ - 2021 ISPSC.docm Page 2
TABLE 1.1 2021 ISPSC REQUIREMENTS
RESULT CLAUSE DESCRIPTION COMMENT
N/A 305.1 The provisions of this section shall
apply to the design of barriers for
restricting entry into areas having pools
and spas. Where spas or hot tubs are
equipped with a lockable safety cover
complying with ASTM F1346 and
swimming pools are equipped with a
powered safety cover that complies with
ASTM F1346m the areas where those
spas, hot tubs or pools are located shall
not be required to comply with Sections
305.2 through 305.7.
Review for compliance
with Section 305.
Conform 305.2.1.1
Top of barrier shall be not less than 48
inches above grade where measured on
the side of the barrier that faces away
from the pool or spa, maintained for 3
feet horizontally from the outside of the
barrier.
Aquatine top of barrier is
48 inches above grade.
Conform 305.2.1.2 The vertical clearance between grade
and the bottom of the barrier shall not
exceed 2 inches for grade surfaces that
are not solid, such as grass or gravel,
where measured on the side of the
barrier that faces away from the pool or
spa.
Aquatine bottom of
barrier clearance is 2
inches maximum.
Conform 305.2.1.3
The vertical clearance between a surface
below the barrier to a solid surface,
such as concrete, and the bottom of the
required barrier shall not exceed 4
inches where measured on the side of
the required barrier that faces away
from the pool or spa.
Aquatine bottom of
barrier clearance is 2
inches maximum.
Conform 305.2.1.4
Where the top of the pool or spa
structure is above grade, the barrier
shall be installed on grade or shall be
mounted on top of the pool or spa
structure. Where the barrier is mounted
on the top of the pool or spa, the
vertical clearance between the top of
the pool or spa and the bottom of the
barrier shall not exceed 4 inches.
Aquatine bottom of
barrier clearance is 2
inches maximum.
Conform 305.2.2 Openings in the barrier shall not allow
passage of a 4 inch diameter sphere.
Aquatine openings are
maximum 4 inches in
between members.
Conform 305.2.3 Solid barrier that do not have openings
shall not contain indentations or
protrusions that form handholds and
footholds, except for normal
construction tolerances and tooled
masonry joints.
Aquatine has no solid
barriers, picket sections
only.
N/A 305.2.4
The inside of a mesh fence shall be not
closer than 20 inches to the nearest
edge of the water of a pool or spa.
Does not apply. No mesh
barriers on the system.