Datasheet

3. Specifications
LOOP Resistance
L- PE (Hi-Amp)
Range (Ω)
Resolution(Ω)
Accuracy
0.23 9.99
0.01
±(4% of reading+ 6digits)
10.0 99.9
0.1
100 999
1
Measuring Current …………….………………………………………..………… 4.0 A
Range of the Voltage Used …………………………195V AC – 260V AC (50,60Hz)
L- PE (No Trip)
Range (Ω)
Resolution(Ω)
Accuracy
0.23 9.99
0.01
±(5% of reading+ 6 digits)
10.0 99.9
0.1
100 999
1
Measuring Current ……………..………………………………………………… < 15mA
Range of the Voltage Used ……………………………195V AC– 260V AC (50,60Hz)
LINE Resistance
L- N
Range (Ω)
Resolution(Ω)
Accuracy
0.23 9.99
0.01
±(4% of reading+ 6digits)
10.0 99.9
0.1
100 999
1
Measuring Current …………….………………………………………………… 4.0 A
Range of the Voltage Used ………………………..195V AC 260V AC (50,60Hz)
RCD (EN 61557-6)
Rcd Rating (I_n) …………………………………..10mA, 30mA, 100mA, 300mA, 500mA and 1A.
Test current …………………………………..……x1/2, x1, x2 and x5
Accuracy at applied test current
Test current
Accuracy
x1/2
±(1% of reading+ 1 ms)
x1
±(1% of reading+ 1 ms)
x2
±(1% of reading+ 1 ms)
X5
±(1% of reading+ 1 ms)
-52-
Form of the Test Current
Sine wave form (ac), Pulse wave form (dc)
RCD Form
General (G - non-delayed), Selective (S - time-delayed)
Initial Polarity of the Test Current
0°, 180°.
Voltage Range
195V AC - 260V AC (50Hz,60Hz)
Accuracy of the Timing of the RCD
± (10% of reading + 1 digits)
Resolution of the RCD Timing
0.1ms