5. When measuring is completed, impedance of L- PE and PFC (lf) value appears on the
screen
No Trip Measurement completed
6. Press TEST button if re-test is necessary.
When symbol from , , appears lower left corner, and if
the voltage exceeds 260V, the measurement will not take place
5.2.3 Using the Hi Amp LOOP Measurement
The Hi Amp LOOP Measurement to be selected where the circuit is NOT protected by the inclusion
of an RCD.
Hi Amp Loop Standby screen
1. Turn the rotary switch to the LOOP / PFC position
2. Press F2 button to change from No Trip to Hi Amp
3. Connect the test leads as shown in the Figure 5.2.2.3
4. As soon as the instrument senses the presence of voltage at its terminals it will operate
automatically and display the measurement taken
-71-