Datasheet
6. Press TEST button if re-test is necessary
When symbol from , , appears lower left corner,
and if the voltage exceeds 260V, the measurement will not take place
5.2.5 Using the RCD Function
You can select UL Voltage by Pressing and hold F3 button for more than two seconds (25V or 50V).
Uf value appears is the contact voltage on the screen.
RCD – Standby screen
Function Button Description
BUTTON
1
2
3
4
5
6
7
F1
AUTO
RCD t∆
RCD I∆N
F2
30mA
100mA
300mA
500mA
650mA
1A
10mA
F3
AC G
AC S
DC G
DC S
F4
0
180
G …………………….General (non-delayed) RCDs
S …………………….Selective (time-delayed) RCDs
Possible setup ratios depending on the RCD Trip Current
10mA
30mA
100mA
300mA
500mA
650mA
1A
X1/2
O
O
O
O
O
O
O
X1
O
O
O
O
O
O
O
X2
O
O
O
O
O
X
X
X5
O
O
O
X
X
X
X
AUTO
O
O
O
X
X
X
X
RAMP
O
O
O
O
O
O
X
-74-