Troubleshooting an electric floor heating (single-pole application)
Should a grounding mat or other shielding be above the electric floor heating, the search can be
disturbed by it. If possible, remove the connection to grounding of the shielding.
This test can be done with a transmitter or two transmitters.
Connect the red cable to the heating wire or cable of the system and the black cable with protective
ground.
Follow the signal to interrupt.
Alternatively, connect a second receiver to the return line of the system and proceed as in the
search for line breaks in the preceding passage.
The receiver depth is 2 meters, depending on the material and application. By changing the
transmitter level of the transmitter from 1 to 3, the receiver depth can be changed by a factor of x5.
Note: Only one transmitter is supplied with the device. However, each transmitter of another device
can be used as a second transmitter.