General Information TAC TAC is a Schneider Electric Company with a long tradition of global leadership in building controls technology. We offer the most extensive line of controls and components available to today's market, including: valve bodies, valve assemblies, actuation devices and sensors, as well as interfaces, and automated systems that link these products and other building systems together.
Manufactured Parts Numbering System Primary Designation (First Letter) HS humidity sensor, electronic A Accessories HSP H Humidity humidity transmitter, electronic P Pressure S Switch or Step Controller V Valve C Controller or Controlled Device MA M Motor (Actuator) MC R Receiver-Controller or P.E.
Subject Index Accessories 500 Ohm Resistor ............................................................340 Accessory Kit ...................................................................343 Adapter Plate .......................................................... 317, 374 Angle Damper Clip ...........................................................326 Bracket .............................................................................342 Celsius Set Point Dial .............................................
Subject Index Proportional Temperature Controller (Less Sensor) ........ 209 Proportional Temperature Controller with Sensor ........... 211 Room/Discharge Low Limit Temperature Controller ....... 274 Single/Dual Output Room Temperature Controllers ........ 270 TAC System 8000 Chiller Controller .................................. 42 TAC System 8000 Eight-Stage Sequencer Controller ....... 32 TAC System 8000 Four-Step Sequence Controller ........... 27 TAC System 8000 Six Stage Programmable Controllers .....
Subject Index Sensor Outside Air Sensor ...........................................................369 Thermistor ........................................................................369 Sensors Strap-on Changeover Thermostat ................................... 258 Strap-on Thermostat ........................................................ 259 Two-Position Electric Duplex Room Thermostats ...248, 255 Two-Position Electric Room Thermostat, Heating ...........
Subject Index vi © Copyright 2006 TAC. All Rights Reserved.
Model Number Index Model Page Numerics 10-22 .......................................315 10-48 .......................................315 10-53 .......................................316 10-58 .......................................316 10-62 .......................................316 10-82-48 ...................................317 10-82-SS ..................................317 20-715 ......................................316 453-52 ......................................317 453-69 ..........................
Model Number Index Model Page Model Page Model Page AM-237 ....................................329 AM-301 ....................................329 AM-321 ....................................329 AM-332 ....................................330 AM-341 ....................................330 AM-345 ....................................331 AM-348 ....................................331 AM-363 ....................................331 AM-369 ....................................332 AM-392 ........................
Model Number Index Model Page EYZP-504-2 ..............................368 EYZP-504-3 ..............................368 EYZP-721 .................................368 EYZP-722-1 ..............................368 EYZP-722-2 ..............................368 EYZP-722-3 ..............................368 EYZP-722-4 ..............................368 EYZP-722-5 ..............................368 EYZP-xxx .................................368 H HC-101 .......................................69 HC-201 ..............
Model Number Index Model Page Model Page Model Page MP-421 ....................................138 MP-422 ....................................138 MP-423 ....................................138 MP-424 ....................................138 MP-451 ....................................138 MP-452 ....................................138 MP-453 ....................................138 MP-454 ....................................138 MP-461-600 ..............................138 MP-465 ..........................
Model Number Index Model Page SR601AT ..................................216 SR601B ....................................216 ST100AT ..................................213 SYZE-102 .................................367 SYZE-189 .................................367 SYZE-212 .................................367 SYZE-255 .................................367 SYZE-271 .................................367 SYZE-293 .................................367 SYZE-300 .................................367 SYZE-52 ...........
Model Number Index Model Page Model Page TP-8124 ...................................270 TP-8124 ................................270 TP-8232 ...................................274 TP-8232-116 .............................274 TS-291 .....................................276 TS-292 .....................................276 TS-293 .....................................276 TS-294 .....................................276 TS-5191 ...................................277 TS-57011 .................................
453L, 453H, 453R Series TAC Erie™ Two-Position Damper Actuator The 453L light duty damper actuators are designed for a variety of two-position, spring return, damper applications. They are suitable for up to 125 in2 (806 cm2) of balanced damper. The 453L uses a two-wire thermostat control. Linkage hardware must be supplied by the end user. The 453H medium duty damper actuators are designed for a variety of two-position, spring return damper applications.
453L, 453H, 453R Series Model Chart (Continued) Model No. Voltage Vac Description Drive Direction of Rotationa 453H0077GA01 453H0077GB00 453H0077GB01 453H0077GU00 453L0038GA00 453L0038GA01 453L0038GB00 453L0038GB01 453L0038GU00 453L0038GU01 453L0074GA00 453L0074GB00 453L0074GU00 453L0077GA00 453L0077GA01 453L0077GB00 453L0077GB01 453L0077GU00 453L0077GU01 453R0077GA00 453R0077GB00 453R0077GU00 a Direct Drive with End Switch Direct Drive Direct Drive with End Switch Direct Drive Torque Rating in.-oz.
453L, 453H, 453R Series Accessories Model No. 453-52 Description 6 to 12 in. damper shaft extension kit. 453-69 453-239 12 to 20 in. damper shaft extension kit. 5/16 to 1/2 in. shaft adaptor. Typical Applications 1 Model Wire Color Code 120V 1 Power 453L/453H 230, 24 453L Blk L1/White L2 Blk/Blk 453H Yellow Yellow Figure 1 Typical Wiring Diagram, 453L/453H Models.
680 Series 680 Series TAC Erie™ Seasonal Changeover Switch The 680 series low or line voltage changeover switches are designed to switch a thermostat from heating to cooling based on a change in supply water temperature. The 680 series switches can be mounted on 5/8 in. or 7/8 in. O.D. copper tube or iron pipe. Both models are easily mounted to the supply piping with a simple spring clip included with the thermostat. Each thermostat also includes the necessary wire nuts and strain relief bushing.
680 Series Typical Applications TA155-010 TB3 680-243* CHANGEOVER THERMOSTAT PIPE MOUNTED Black Blue LEAD IDENTIFICATION 1 BLK 2 BLU WHT 3 HEATING/ COOLING VALVE BLACK CLOSE ON RISE = HEAT WHITE COMMON BLUE CLOSE ON DROP = COOL Temp Drop TB2 White L1 (HOT) TB1 1 1 2 2 3 HI MED 3 4 LOW 4 5 FAN L2 OR NEUTRAL *See Figure 2. Figure 1 Typical Wiring. F-27382-1 Figure 2 Switch Action on Temperature Drop. © Copyright 2006 TAC. All Rights Reserved.
AE-20X Series, AEM-8120 Series, AEM-8240 Series AE-20X Series, AEM-812 Series, AEM-824 Series Transformers These transformers supply low voltage power for operating control equipment. The AEM-8120 series provides low voltage power sources from 50 to 100 Va, and are the only recommended transformers for use with the TAC System 8000 Series Controller. Features: • Many varieties for use with specific requirements. • Ratings that meet requirements for TAC electrical products.
AE-20X Series, AEM-8120 Series, AEM-8240 Series Specifications Electrical ratings Refer to Description Model Chart. Secondary connections AE-201 Flexible conduit fitting. AE-207 series Color coded leads. Locations NEMA Type 1. Mounting Primarily in control centers in conjunction with disconnect switch and overload circuit breaker. AE-201 is provided with a plate on the primary side for mounting on standard 4 in. outlet box. AE-207 series are provided with plate for mounting on standard 4 in.
AE-504 AE-504 Paralleling Relay Paralleling relay for controlling or manually positioning MP type proportional gear train actuators from a potentiometer (slidewire). Features: • Provides interface between a 100 to 1000 Ω potentiometer and a gear train actuator. • Mounts directly to the gear train actuator. Model Chart Transmitting Potentiometer Requirements Model No. AE-504 Max. Ω Watts per AE-504 Max. No. of AE-504s per Potentiometer 100a to 135 1.
AE-504 Typical Applications Transmitting Potentiometer 1 5 H Follow-Up Actuator 5 G 4 8 ccw cw 7 Black Brown AE-504 Paralleling Relay Brown/Yellow 7 680 Ω 7 680 Ω 4 4 Yellow/Black 1 Transmitting potentiometer typically AM-332 on actuator, manual potentimeter, or 135 Ω slidewire controller (1.5W min.). 2 Shaft rotates CW or closes valve. 3 Shaft rotates CCW or opens valve. 4 Make resistor & jumper connections on 24 V actuators only.
AE-600 Series AE-600 Series Control Cabinets Control cabinets for mounting of electric, electronic, and pneumatic controls. Features: • New lock design for AE-629, 630, 631, and 632 improves locking ability. • Available subpanels for certain cabinets for easy equipment mounting. • AE-662 Series UL listed. AE-629 AE-630 AE-631 AE-662-501 AE-662-502 AE-662-503 AE-632 Model Chart Door Model No.
AGxx, AHxx Series TAC Erie™ Spring Return Two-Position Actuator The PopTop™ series valve bodies and actuators provide easy installation for a variety of heating and cooling applications. The valve’s actuator can be installed after the valve body has been installed onto the fan coil, baseboard or air handler. Gxx, AHxx ries Features: • Synchronous motor drive with spring return. • Variety of voltages available. • Mounts directly onto the body without the need for linkages or calibration.
AGxx, AHxx Series Model Chart (Continued) Model No. Volts AC AG24T020 277 AG24U020 230 Electrical Position Temperature Range F (C) Normally Open 32 to 250°F (Fluid) @ 169° (0 to 121° @ 76°) End Of Travel Switch No No Wiring 18 in.
AGxx, AHxx Series Specifications Inputs Control signal On/off, 2 position SPST, spring return. Power 6.5 watts 7.5 VA @ 50/60 Hz. End Switch 24-240 Vac/101 mA minimum to 5A maximum and 90-30 Vdc@ 100 mA maximum. Outputs Motor Type Hysteresis synchronous. Mechanical Control action: 2-way accepts N.O or N.C. actuator, 3-way N.C. (piping determines N.O./N.C. status of flow to coil.) Timing: Environment Ambient temperature limits Refer to Model Chart. Humidity 5 to 95% RH, non-condensing.
APX3, ATX3 Series TAC Erie™ Spring Return Floating & Proportional Actuators The AP series proportional and AT series floating PopTop™ actuators incorporate equal percentage flow characteristics. The floating and proportional actuators are designed to be used on the 1/2 to 11/4 in. VM series valves for precise temperature control of fluid flow in heating or cooling applications. See valve section for details. Features: • Floating model is compatible with any 24 Vac three-wire signal.
APX3, ATX3 Series Agency Listings CE compliant. European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). Refer to F-27384, TAC Valve Catalog for compatible 1/2 to 1-1/4 in. VM Series two or three-way zone valves. General Instructions Typical Applications 24 Vac 5 6 12 10 Typical 3 T158 Controller J2 1 24 Vac 2 Closed 1 COM 2 Open J1 J3 1 The 24 Vac/COM supply must be maintained continuously for valve operation.
AP33, AT33 Series TAC Erie™ Non-Spring Return Floating & Proportional Actuators The AP series proportional and AT series floating PopTop™ actuators are designed to work with the 1/2 to 1-1/4 in. VM series valves for precise temperature control of fluid flow in heating or cooling applications. Features: • Floating model is compatible with any 24 Vac three-wire signal as long as 3 minute timeout logic resides in the controller or on the valve. • Microprocessor controlled (proportional only).
AP33, AT33 Series Typical Applications 24 Vac 14-28 AWG Close 6 COM 12 10 Typical T158 Controller Open 5 2 J1 1 100-315 C1 1 Requires a controller with a time-out feature. T158 series control includes time-out feature. 2 or equivalent SPDT center off controller with timeout. J2 Figure 1 Typical Wiring of Three-Wire Floating Non-Spring Return Valves (AT33A000). 24 Vac 18-22 AWG 100-316-3 Close 5 1 1 COM 6 Typical T158 Controller 12 10 Open J1 or equivalent SPDT center off control.
ASP-8311 Series ASP-8311 Series Power Supply Provides 20 or 24 Vdc power supply for up to six HSP-8xxx, VER-Hx, or TSP-8xxxx Transmitters. ASP-8311 series power supplies can be used for TAC System 8000 applications where added capacity is required. Features: • UL and CSA listed units available in ASP-8311 Series. • Capacity rating selected to prevent damage to hardware if misapplied. • Dual voltage capability to meet all applications. • Isolated output. Model Chart Model No.
BB1200 1200 TAC Erie™ Universal Reset Control The TAC Boiler Boss® BB1200 series universal reset control is used to control boiler water temperature applications. The supply water temperature is automatically adjusted up or down based on outside air temperature. As the outside air gets colder the BB1200 raises the hot water supply temperature through its dry contact output. As the outside air gets warmer the BB1200 provides a lower water temperature based on its control range.
BB1200 Accessories Model No. OAS-2 Description Extension cable 50 ft, for use with OAS-1.
BB3000 B3000 TAC Erie™ Injection Mixing Pump Control The TAC Boiler Boss® BB3000 injection pump mixing control with outdoor reset provides closed loop control of water temperature in the secondary (radiant) loop of a primary/secondary heating system. The TAC Boiler Boss BB3000 also protects against boiler condensation by monitoring and anticipating the boiler return water temperature. The outdoor air and loop temperatures are displayed continuously, along with the secondary loop setpoint and pump speed.
BB3000 Accessories Model No. 40-8-68 40-8-69 SENS-10K Description F1 Fuse F2 Fuse Three 10K thermistor sensors. OA, PRI, SEC.
BB3600 3600 TAC Erie™ Three-Way Mixing Valve Control The TAC Boiler Boss® BB3600 mixing valve control with outdoor reset provides closed loop control of water temperature in the secondary (radiant) loop of a heating system using a proportional control threeway mixing valve. The TAC Boiler Boss® BB3600 protects against boiler condensation by monitoring and anticipating the boiler return water temperature.
BB3600 Accessories Model No. 40-8-44 SENS-10K Description F1 Fuse Three 10K thermistor sensors, OA, PRI, SEC.
CC-810X Series C-810X ries TAC System 8000 Controlled Relays Electronic controlled relays are offered in dual, or dual with one having heat anticipation for time proportional control of electric heat. Features: • Stages individually adjustable. • Large selection of operational differentials available. • Uses standard track mounting. • Can accommodate two individual inputs. Model Chart Model No.
CC-810X Series Electrical Rating per Relay. Contact Rating 24 Vac 120 Vac 240 Vac Amps (continuous) ⎯ 1 0.5 Amps (inrush) ⎯ 10 5 Pilot duty sealed (VA) 25 125 125 Pilot duty inrush (VA) 250 1250 1250 Accessories Model No. AD-8969-901 AD-8912 TOOL-201 Description Extended relay differential jumper. Enclosure, 12 in. (305 mm). Calibration kit for TAC System 8000. Typical Applications 1 Relay No. 1 (CC-8102). Factory Set: Dropout: 6 Vdc; Differential: 1 Vdc.
CC-8104 C-8104 TAC System 8000 Four-Step Sequence Controller This controller operates up to four external AC power handling relays or loads in heating, ventilating and air conditioning systems. A second unit can be sequenced to provide up to eight steps. Features: • Usable with competitive 135 Ω slidewire controllers. • Accepts 2 to 15 volt power demand EMS signals. • Self-contained built in controller. • Solid state switching output. • Standard track mounting. Model Chart Model No.
CC-8104 Maximum Electrical Rating per Output Stage 24 Vaca. a Amps VA Pilot Duty 0.9 (continuous) 22 (sealed) 9 (inrush) 220 (inrush) Minimum load amps: 0.1. Accessories Model No. AD-8969-201 AD-8969-301 AD-8969-901 AT-8100 TOOL-201 TS-8000 Description Offset resistor kit: 5, 10, 15 and 20°F. 1 K, ±1%, WW resistor kit. Extended throttling range jumper. Remote setpoint adjuster. Calibration kit for TAC System 8000. 1000 ohm Balco sensors.
CC-8111-xxx Series -8111-xxx TAC ries System 8000 Two-Input Controller/Relay Two-input electronic controller with proportional output and a single state relay output for single input, differential and reset control in HVAC systems. Features: • True differential on-off controller. • Dual capability as proportional 2 to 15 Vdc signal and individual relay output. • Self contained built in dual input controller. • Standard track mounting. Model Chart Model No.
CC-8111-xxx Series Specifications (Continued) Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: 40 to 140°F (4 to 60°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1. Connections Coded screw terminals for 14 to 20 AWG. Cover Aluminum. Mounting Unit is provided with a plastic track for panel installation. Dimensions 4 H x 7-1/2 W x 2-1/2 D in. (102 x 191 x 63 mm). Agency Listings UL Recognized, CSA.
CC-8111-xxx Series Typical Applications Single Input. Bridge and Input Action Input A Internal Connections Sensor Connection Direct acting J1 to COM, J2 disconnect and tape ISA and +6.2 Reverse acting J1 to +6.2, J2 disconnect and tape ISA and COM Dual Input. Input A Action Sensor A Between J1 to Pin Direct actinga +6.2 and ISA COM Reverse acting ISA and COM +6.2 a Reset Action of Input B J2 to Pin Sensor B Between a +6.2 ISB-COM Reverse reset COM ISB-+6.
CC-8118-120 CC-8118-1 20 TAC System 8000 Eight-Stage Sequencer Controller This controller is an electronic linear sequencer for sequencing external low or line voltage contactors or other loads. This unit also has a 2-15 Vdc proportional output for use with other controlled devices. Features: • Dual sensing input capability. • 2 to 15 volt control signal for additional functions. • Can be adapted to competitive 135 Ω controllers. • Power demand input for load shedding ability.
CC-8118-120 Specifications (Continued) Control output voltage Control of TAC System 8000 devices 2 to 15 Vdc paralleling or sequencing five additional TAC System 8000 devices. Factory calibrated for 7.5 Vdc with sensor at setpoint temperature. Proportional control of electric heat 6 to 9 Vdc between each HTG relay outputs. Power requirements Refer to Model Chart. Power supplies available 6.2 Vdc, 4 mA 20 Vdc, 35 mA These regulated and filtered power supplies must not be connected to +20 (red) or +6.
CC-8118-120 Typical Applications Relay Contact Electrical Ratings. Volts AC 50/60 Hz Contact Va Rating Inrush VA N.O. 125 1250 N.C. 67 670 N.O. 25 250 N.C. 13 130 120 24 OPV CC-8118-120 IV2 OP1 Sensing Element B 3 From COM of CC-8118-120 (Blue) COM (Red) +20 2 4 5 Additional TAC System 8000 Controlled Devices (Yellow) IV1 ISB 1 ISB Sensing Element A ISA 6 100% Prop. Output 6-9Vdc 1 Except MP-52xx Series Actuator. See General Rules for Wiring Controllers to Controlled Devices.
CP-5341 Fan Speed Controller CP-5341 An electronic motor speed controller for use with shaded pole and permanent split capacitor type motors without integral starting switches and starting windings, up to 120 Vac with a maximum of 5 amps running current. Used in heating and/or cooling applications. MA X Features: • Adjustable minimum cutoff speed setting to match specific motor characteristics. • Direct and reverse action through summer/winter selection.
CP-5341 Typical Applications TS-5181 CP-5341 C. H. Wiring Junction Box or Motor Wiring Compartment Black White Green Building Ground L2 L1 Motor Black Green Black Figure 1 Typical Installation Wiring. 36 © Copyright 2006 TAC. All Rights Reserved.
CP-8102, CP-8102-116 P-8102, TAC P-8102-116 System 8000 Two-Input Temperature or Humidity Controller This two-input temperature or humidity controller provides heating, cooling, humidification, or dehumidification control in HVAC systems. Features: • Individual setpoints for each input element. • Self contained package incorporating two bridges and amplifiers. • One input element has a 0.5 to 1 through 25:1 ratio adjustment. • Accommodates all temperature/humidity TAC System 8000 devices.
CP-8102, CP-8102-116 Specifications (Continued) Typical controlled devices Maximum of six TAC System 8000. CC-8100 Series relays. MF-63123 Floating valve actuator. MFC-8000 Control module card for MF-62123 actuator. MM/MMR-400 Series Modular actuators w/MMC-8000 control module. MM/MMR-500 Series Modular actuators w/MMC-8000 control module. MP-300-600 Series Actuators. MP-400-600 Series Actuators. MP-5000 Series Actuators. MS-1233 Series Damper actuators. MS4D-x0x3-030 Actuators.
CP-8102, CP-8102-116 Typical Applications Jumper Connections. Jumper Connections Required Controller Function Bridge “A” Bridge “B” Direct actinga J4 to JC6 J3 to JC5 J5 to JC5 J6 to JC6 Reverse acting J4 to JC5 J3 to JC6 J5 to JC6 J6 to JC5 Internal setpoint active a J1 to JC1 J2 to JC3 Internal setpoint inactive for remote setpoint J1 to JC2 J2 to JC4 Disable Bridge “B” for single sensor input Remove jumper from AB2 to AB3 a As supplied from factory.
CP-8122 CP-8122 TAC System 8000 Two-Input Temperature or Humidity Controller This controller provides precision control for mixed air dampers, heating and cooling valves, make up air units, chillers, laboratories, computer rooms, test chambers, and other applications. Features: • TAC System 8000 two input controller. • Automatic reset action. • Control signal inversion capability. • High signal selection. • Ramp up and ramp down operation. • Anti wind-up capability. Model Chart Model No.
CP-8122 Specifications (Continued) Typical controlled devices CC-8100 Series Relays. MF-63123 Floating valve actuator. MFC-8000 Control module card for MF-62123 actuator. MM/MMR-400 Series Modular motor with MMC-8000 control module. MM/MMR-500 Series Modular motor with MMC-8000 control module. MP-300-600 Series Actuators. MP-400-600 Series Actuators. MP-5000 Series Actuators. MS-1233 Series Damper actuators. MS4D-x0x3-030 Actuators. MS40-7043-MP Actuators. MS40-7043-MP5 Actuators.
CP-8142-024 CP-8142-0 TAC System 8000 Chiller Controller This chiller controller provides electronic control for centrifugal chillers with electric or hydraulic loading vane actuators. Features: • TAC System 8000 two input controller design. • Precise zero droop control action. • Auto ramp-up of chiller designed into unit. • Motor current limit action for start-up. • Standard auto/manual control switches. • LED indication of control action. • Standard TAC System 8000 track mounting.
CP-8142-024 Specifications (Continued) Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: 40 to 125°F (4 to 60°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1. Wiring connections Control Coded screw terminals for 14 to 20 AWG. Power Color coded pigtails, 10 in. (254 mm). Cover Aluminum. Mounting Unit is provided with a section of plastic track for panel mounting. Dimensions 3-7/8 H x 11 W x 3-1/4 D in. (98 x 279 x 83 mm).
CP-8142-024 CP-8142 Unload 3 Load 2 COM X MP-485 L1 L2 120 Vac 60 Hz Continuous Power Figure 2 Connections to an Electric Vane Actuator. 120 Vac 60 Hz Continuous Power (Black) L1 (White) L2 2 Transformer COM 1 Hot 1 Unload 1 Load 1 CP-8142 Terminals. 2 24 Vac Secondary. Load Valve Unload Valve Figure 3 Connections to Hydraulically Controlled Vane Valves. Paralleling or Power Demand 10-0 Vdc Input 24 Vac 50/60 Hz Continuous Power +20 Vdc 35 mA Power Supply Control Prop.
CP-8161-333, CP-8161-433 (Slave) CP-8161- TAC System 8000 Six Stage Programmable 333, CP-8161Electronic six stage programmable controller with 433 proportional output for heating, cooling and mixed (Slave) air. The six stages can be programmed for heating, Controllers cooling and fan operation. Features: • Six stages of control, any heat-cool combination programmable. • Two individual heat-cool setpoints. • Two input TAC System 8000 controllers. • Automatic integrated mixed air control cycle.
CP-8161-333, CP-8161-433 (Slave) Relay Contact Ratings. Volts AC 50/60 Hz 120/240 24 Contact Va Rating Inrush VA N.O. 125 1250 N.C. 67 670 N.O. 25 250 N.C. 13 130 Specifications Sequenced control Staged and/or proportional heating, proportional control of outside and return (mixed air) damper, staged and/or proportional cooling. Heating and cooling cannot operate simultaneously. Single sensor control Heating, cooling, and ventilation with individual heating and cooling setpoints.
CP-8161-333, CP-8161-433 (Slave) Typical Applications Blue Yellow Red 2 CP-8161 NO1 COM C1 OP3 TS-8405 TS-8422 TS-8201 Mixed Air Sensor Heat Stage 1 NC1 Black ISB NO2 Black +6.
CP-8261-333, CP-8261-702 TAC System 8000 Six Stage Programmable Controllers The six stage electronic programmable controllers provide proportional control of outside and return (mixed air) dampers in sequence with staged heating and cooling equipment. Programming of the heating and cooling stages and relay assignment of heating and/or cooling plus operating level are accomplished by dual-in-line package (DIP) switches.
CP-8261-333, CP-8261-702 Specifications Sequenced control Staged and/or proportional heating, proportional control of outside and return (mixed air) damper, staged and/or proportional cooling. Heating and cooling cannot operate simultaneously. Single Setpoint (SPB) 55 to 85°F (13 to 29°C). Heating, cooling, and ventilation are controlled from a single sensor and a single setpoint. Nullband Adjustment (SPA) 2 to 14°F (0 to 8°C); factory set at 3°F (2°C).
CP-8261-333, CP-8261-702 Relay Contact Ratings. Volts AC 50/60 Hz 120/240 24 Contact Va Rating Inrush VA N.O. 125 1250 N.C. 67 670 N.O. 25 250 N.C. 13 130 Accessories Model No. AD-8969-201 AT-8122 AT-8155 AT-8158 AT-8258-101 CP-8161-433 TC-4111 THC-2 TS-8101 TS-8131 TS-8201 TS-8261 TS-8405 TS-8422 TS-8501 TS-8601 TSP-8101-103 TOOL-201 Description Offset resistor kit; 5, 10, 15, and 20°F. Remote setpoint adjuster, dual scale 20 to 120°F (-6 to 49°C).
CP-8261-333, CP-8261-702 Relay Staging Reference Relay Selection 9V 8.5V 8V 7.5V 7V 6.5V 6V 5.5V 5V Heating Stages Fan Cycle (Relay 1 Only) ON Cooling Stages OFF Heating (IO1) and Cooling (IO2) Signal Ramps 9V REV DIR Proportional Cooling Proportional Heating 6V 9V ON OFF Mixed Air Section OP3 Signal Ramp (5-12 Vdc) Adj. Min. Pos. 6V -16 -14 -12 -10 Open 100% Proportional Mixed Air Closed 0% OP3 -8 -6 -4 SPA Nullband (Adj. 0-14° F) 0 SPB +2 +4 Temp Setpoint Nullband (Adj.
CP-8301-xxx Series CP-8301xxx Series 2 to 15 Vdc Input Electronic Actuator Drive The CP-8301-xxx Series electronic actuator drive is designed to process a variable 2 to 15 Vdc signal from a controller to provide proportional control of an electric gear train actuator. Features: • Mounts directly onto TAC proportional, electric, gear train actuators. • 24, 120, and 240 Vac models available. • Color-coded pigtail leads. Model Chart Model No. Power Requirement Vac, 4.
CP-8301-xxx Series Specifications Inputs Control signal Range: 2 to 15 Vdc. Span: refer to Model Chart. Start point: refer to Model Chart. Power requirements Refer to Model Chart. Power supplies Refer to Model Chart. Outputs Connections Color coded pigtail leads. Mounting Directly to an actuator. Case Bakelite. Environment Ambient temperature limits Shipping and storage: -40 to 140° F (-40 to 60°C). Operating: -40 to 140° F (-40 to 60°C). Humidity 5 to 95% RH, non-condensing.
CP-8301-xxx Series Typical Controllers TP-8101 CP-8102 +20 (Red) 1 Blue Yellow Red Brown/Black Brown/White CP-8301-024 OP (Yellow) COM (Blue) 1 CP-8301-024 can be used with the following electric actuators: MP-465, 475,483, 485, 486, 2150-500, and 9750. 2 Case Ground. Brown Red/Black 4 Actuator 7 8 3 3 Red Blue/Black Yellow/Black Black Black/Blue 4 2 X AC Supply 2 L1 L2 3 Actuator rotates clockwise on increase in input signal.
CP-8391-456 CP-839 1-456 Electronic Actuator Drive This drive provides proportional control of an electric gear train actuator from a variable voltage DC signal produced by a controller. Features: • Variable Vdc signal acceptance and proportional drive of certain MP-400, MP-4000, MP-2100, and MP-9000 series actuators. • Rugged aluminum case. • Direct actuator mount model. • Adjustable start point, span, and hysteresis. • Driving capability of up to three actuator drives by typical controller.
CP-8391-456 Specifications Electronic Actuator Drive inputs Grounding: Either or both input wires grounded will not cause damage. Compatible with variable Vdc input signal Maximum: 40 Vdc. Isolation: Optically. Requirements: 120 or 240 Vac, ±10%, with fixed input signal offset of ±1% maximum. 24 Vac units not available. Power Consumption: 3.5 VA at 120 or 240 Vac, 50 or 60 Hz. Connections CP-8391-456 mounts directly to the actuator.
CP-8391-716 Series P-83916 Series 4 to 20 mA Input Electronic Actuator Drive The CP-8391-716 Series electronic actuator drive is designed to process a variable 4 to 20 mAdc signal from a controller to provide proportional control of an electric gear train actuator. Features: • Mounts directly onto TAC proportional, electric, gear train actuators. • 4 to 20 mAdc operating range.
CP-8391-716 Series Specifications Inputs Range: 4 to 20 mAdc, non-adjustable. Span: Adjustable 4 to 16 mAdc. Start point: Adjustable from 2 to 16 mAdc. Impedance: 250 Ω. Control signal Grounding: Either input wire can be grounded and will not cause damage, provided the electric gear train actuator is ungrounded. Hysteresis: 3 to 5% of 16 mAdc span, nonadjustable.
CP-8391-716 Series Black-Blue Red + White-Blue Black - To mAdc Controller Brown 5 4 6 7 Yellow 8 3 Orange CP-8391-716 Actuator Drive Red-Yellow Actuator 2 L1 X 1 L2 Blue (120 Vac) Violet (COM) Black-White (240 Vac (Wire to L1 on 240 Vac Actuators and Tape Blue Lead.) Note: All references to direction of actuator shaft rotation are determined by looking at actuator output shaft.
CP-8391-91x Series 4 to 20 mA Input Electronic Actuator Drive CP-8391 91x Seri The CP-8391-910 Series electronic actuator drive is designed to process a variable 4 to 20 mAdc signal from a controller to provide proportional control of an electric gear train actuator. Features: • Mounts directly onto TAC proportional, electric, gear train actuators. • Fixed 4 to 20 mAdc operating range. with 250 Ω impedance. • 24 and 120 Vac models available. • Color-coded pigtail leads. Model Chart Model No.
CP-8391-91x Series Specifications Inputs Range: 4 to 20 mAdc, non-adjustable. Span: 16 mAdc. Start point: 4 mAdc. Impedance: 250 Ω. Control signal Grounding: Either input wire can be grounded and will not cause damage, provided the electric gear train actuator is ungrounded. Hysteresis: 6 to 9% of 16 mAdc span, nonadjustable. (Hysteresis is the difference in input signal between that signal which will drive the actuator shaft one way and the signal which will drive it the other way.
CP-8511-xxx Series CP-8511xxx Serie Electronic to Pneumatic Transducer The CP-8511 transducer receives a variable electronic input signal and produces a 3 to 15 psig (21 to 103 kPa) pneumatic output signal to position pneumatic damper and valve actuators in HVAC systems. Features: • Durable enclosure with easily accessible wiring terminations. • Panel or DIN rail mounting for quick, snap-on installation. • High accuracy with low hysteresis. • Long-term driftless operation with high repeatability.
CP-8511-xxx Series Specifications (Continued) Air consumption for sizing air compressor Maximum 0.012 scfm (5.66 ml/s). Air capacity for sizing air mains 550 scim (150.24 ml/s). Air connections Male barbed fittings for flexible 1/4” O.D. pneumatic tubing. Wiring connections Screw terminals for use with 16 to 22 AWG wire. Outputs 3 to 15 psig (21 to 103 kPa). Maximum pneumatic output 1 to 18 psig (7 to 124 kPa). Action Refer to Model Chart.
CP-8551, CP-8552 CP-8551 CP-8552 Electronic to Pneumatic Transducer The CP-8551 and CP-8552 transducers receive a variable electronic input signal and produce a 3 to 15 psig (21 to 103 kPa) pneumatic output signal to position pneumatic damper and valve actuators in HVAC systems. Features: • Durable enclosure with easily accessible wiring terminations. • Panel or DIN rail mounting for quick, snap-on installation. • Two-wire loop powered or three-wire voltage input. • High accuracy with low hysteresis.
CP-8551, CP-8552 Specifications (Continued) Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: 32 to 140°F (0 to 60°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1. Dimensions 4-1/4 H x 2-13/16 W x 2-5/32 D in. (108 x 71 x 55 mm) Agency Listings UL 873 Underwriters Laboratories (File #E9429 Category Temperature-Indicating and Regulating Equipment. CUL Canadian Standards C22.2 No. 24-93.
CP-9301-xxx Series, CP-9302-xxx Series Electronic Actuator Drive The CP-9301 and CP-9302 electronic actuator drives process a variable input signal from a controller to provide proportional control of an electric gear train actuator. The CP-9301 is preset at the factory for voltage input. The CP9302 is factory preset for current input and has additional wiring for connection to an override switch, for those applications requiring an external override of the input signal.
CP-9301-xxx Series, CP-9302-xxx Series Specifications Mounting Directly to an actuator. The drive may be mounted on either the left or right side of the actuator, in a conduit opening adjacent to the low voltage wiring compartment. Case Injection molded plastic with stamped aluminum cover. Inputs - Voltage and Current Input Refer to Model Chart. Input Span Adjustment Refer to Model Chart. Start Point Adjustment Refer to Model Chart. Input Impedance Voltage Input Greater than 10,000 ohms.
CP-9301-xxx Series, CP-9302-xxx Series Typical Applications Yellow MP-3xx, MP-4xx, MP-21xx, or MP-97xx Series Actuator Blue Wire Nuts Drive Input Violet/White 1 2 Violet CP-9301 or CP-9302 Actuator Drive Brown/White 3 Brown Brown/Black Red/Black 3 3 Blue/Black 3 Yellow/Black Green/Yellow 6 To Controller Common Purge Input (Override Input) Purge + (Override +) Actuator Terminals 7 7 100 Ohm Slidewire 4 8 Purge Override (Input Signal Override) 8 Shading Windings 3 1 Caution: Before installi
HC-101 Series, HC-201 C-101 eries, C-201 Two-Position Electric Controller These controllers provide low or line voltage on-off single stage control of humidifiers, dehumidifiers, valves, solenoid valves, compressors, relays, etc. 20 Features: • SPDT switching for humidification/dehumidification. • Agency listed room and duct units. • Long life nylon elements. • Standard locking feature. 40 60 80 HC-201 HC-101 Model Chart Description. Differential % RH Model No.
HC-101 Series, HC-201 Accessories Model No. Accessories for HC-101 only AT-504 AT-505 AT-546 AT-1104 AT-1155 AT-1165 Description Aux. mounting base. Wall box cover plate. Aux. mounting base. Cast guard. Plastic guard. Plastic guard. Typical Applications 1 (Brown) N.O. (Red) N.C. Drop in R.H. Common (Orange) 1 Brown makes contact with a drop in humidity. All units provided with green grounding lead. Figure 2 HC-101, and HC-201 Switch Action and Terminal Identification. 70 © Copyright 2006 TAC.
MA-3xx Series, MA-4xx Series A-3xx ries, A-4xx ries Two-Position, Oil-Submerged Actuators These actuators provide two-position operation of dampers, valves, and other equipment requiring the return to normal position upon power interruption. Features: • SPST controller. • Spring return. • 24, 120, 208, and 240 Vac models. • SPDT auxiliary switch if actuator part number suffix is “-500.” • Rugged die cast aluminum. • Oil immersed motor and gear train.
MA-3xx Series, MA-4xx Series Part Numbers for Hazardous Location Applicationsa b. Model No.
MA-3xx Series, MA-4xx Series Accessories Model No. Description Damper linkage. AM-111 Crank arm for 5/16 in. diameter damper shaft. AM-112 Crank arm for 3/8 in. diameter damper shaft. AM-113 Crank arm for actuator or 1/2 in. diameter damper shaft. AM-115 Crank arm for 7/16 in. diameter damper shaft. AM-116 Splined crank arm for actuator. AM-122 Linkage connector straight type. AM-123 Damper clip. AM-125 5/16 in. diameter x 20 in. damper rod. AM-125-048 5/16 in. diameter x 48 in. damper rod.
MA4D-xxxx Series Spring Return TAC DuraDrive™ Two-Position Actuator TAC DuraDrive overshaft actuators are designed to provide an economical and reliable solution for many overshaft damper and ball valve requirements. All products accommodate shaft sizes up to 1/2 in. (13 mm) in diameter. Spring return models provide 30 in-lb (3.4 N-m) of torque. Features: • Controlled by SPST controller. • 30 in-lb (3.4 N-m) of torque. • Polymer housing rated for NEMA 2/IP54. • Overload protection throughout stroke.
MA4D-xxxx Series Specifications Inputs Control signal Two-Position SPST. Power See Model Chart. All 24 Vac circuits are Class 2. All circuits 30 Vac and above are Class 1. Connections 3 ft (91 cm) appliance or plenum cables, enclosure accepts 1/2 in. (13 mm) conduit connector. For M20 Metric conduit, use AM-756 adapter. 24 Volt models: 10 ft. plenum cable. Outputs Timing: See Model Chart. Travel: 93o nominal. Mechanical Manual Override: Allows positioning of damper or valve using manual crank.
MA-5200 Series, MA-5300 Series MA-5200 Series, MA-5300 Series Two-Position Actuators These actuators are used for electric two-position control of globe valves and dampers which require a return to the normal position upon power interruption. Features: • Two-position actuators controlled by an SPST controller. • Spring return. • Available 24, 120, and 240 Vac models. • An actuator with the part number suffix "-500" has a built-in, adjustable, SPDT auxiliary switch.
MA-5200 Series, MA-5300 Series Specifications (Continued) Actuator outputs Auxiliary switch (MA-5xxx-500), 10 amps, 120/240 Vdc adjustable SPDT, factory set to close the N.C. contact at the retracted end of stroke. Electrical Stroke damper: Approximately 2 in. (51 mm) from fully retracted to fully extended (includes AM-601 linkage). Mechanical Stroke valve: Approximately 9/16 in. (14.3 mm) from fully retracted to fully extended.
MA-5200 Series, MA-5300 Series Typical Applications (Brown) N.O. (Orange) N.C. (Red/White) C Aux. Switch Leads (-500 Actuators only) L1 Thermostat or Switch Black 1 L2 Ground Green MA-5xxx Actuator 1 Actuator Voltage (Vac) 24 120 240 2 Color(s) of L2 Lead Black/Blue White White/Black 2 Actuator extends when contacts are closed and retracts when contacts are open. Figure 1 Wiring for MA-5xxx Series Actuators. 78 © Copyright 2006 TAC. All Rights Reserved.
MA40-704x Series, MA41-707x Series, and MA41-715x Series Spring Return TAC DuraDrive ® Two-Position Actuator For spring return applications that require twoposition control of dampers and valves in HVAC system. Features: • 35 lb.-in. (4 N-m), 60 lb.-in (7 N-m), 133 lb.-in (15 N-m). • On-off control. US • Rugged die cast housings rated for NEMA 2/IP54. • Overload protection throughout rotation. • Optional built-in auxiliary switch to provide for interfacing or signaling. • Provides 95o of rotation.
MA40-704x Series, MA41-707x Series, and MA41-715x Series Specifications Inputs Control signal On-off SPST contacts or Triacs (500 mA). Power Refer to Model Chart. Connections 3 ft. (0.9 m) long, appliance cable, 1/2 in. conduit connectors. For M20 Metric conduit, use AM-756 adaptor. Outputs Motor Type MA40-704x, MA41-707x: Brush. MA41-715x: Brushless DC. Electrical MA40-7043-501: One auxiliary switch available, SPDT 6A resistive @ 24 Vac, adjustable 0 to 95° (0 to 1 scale).
MA40-704x Series, MA41-707x Series, and MA41-715x Series Accessories Model No. Description MA41-707x, MA41-715x AM-671abcd AM-672abcd AM-673a AM-674 AM-675 AM-676 Mounting bracket. Mounting bracket. Mounting bracket. Weather shield. Weather shield base. Universal shaft extension, approximately 9-1/2 in. long (242 mm) for use on 3/8 to 11/16 in. (10 to 17 mm) round shafts, 3/8 to 9/16 in. square shafts. AM-753 clamps required). Position indicator. V-clamp for 1.05 in. round shafts.
MA40-704x Series, MA41-707x Series, and MA41-715x Series Typical Applications 24 Vac Transformer or 22-30 Vdc Line Volts Black Red 24 Vac 1 MA41-7153 MA41-7073 Common MA41-7153-502 Hot (+DC) MA41-7073-502 Green/Yellow 2 Orange Violet Com Yellow N.O. Orange/White Violet/White SPST Control Contact 120 Vac or 230 Vac Optional Auxiliary Switches L1 N L2 H Wire No. 1 Common Wire No.
MA40-717x Series Spring Return TAC DuraDrive ® Two-Position Actuator For spring return applications that require two position control of dampers and valves in HVAC systems. Features: • 150 lb.-in. (17 N-m) rated torque. • On-off control. • NEMA Type 4 housing (IEC IP56). • Custom automatic current sensing motor control provides extended reliability and repeatable timing. • Direct coupled to the damper shaft with dual industrial hardened universal mounting clamps.
MA40-717x Series Specifications Inputs Control signal On-off SPST control contacts or Triacs (500 mA) rated. Power Refer to Model Chart. Connections 2 ft (61 cm) long appliance cable & 1/2 in. conduit connectors. Outputs Motor Type Brushless DC. Direction of rotation: CW or CCW rotation is available through reverse mounting. Mechanical Dual shaft clamps: Direct coupled using a through hole output hub. Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C).
MA51-7x0x Series, MA61-720x Series Spring Return TAC DuraDrive ® Two-Position Actuator TAC DuraDrive Linear Actuators are designed to mount directly onto two-way or three-way globe valves without the use of linkages. They provide linear travel to operate valves from 1/2 to 2 in. VB7xxx valves and discontinued 1/2 to 1-1/4 in. VB9xxx valves, 2-1/2 to 4 in. VB-9xxx valves and VB8xxx 2-1/2 to 5 in. valves in chilled water, hot water and steam applications up to 366°F (186°C).
MA51-7x0x Series, MA61-720x Series Model Chart(Continued) Actuator Power Input Running Part No. Control Action 50 Hz Voltage Holding 60 Hz 50/60 Hz VA W VA W DC Amps W MA51-7203 24 Vac ±20% 22-30 Vdc 9.8 7.5 9.7 7.5 .29 2.8 MA51-7200 120 Vac ±10% 11.7 8.8 10.0 8.4 N/A 3.6/5.0 230 Vac ±10% 15.5 9.5 10.6 8.5 N/A 4.6/3.3 MA61-7203 24 Vac ±20% 22-30 Vdc 9.8 7.5 9.7 7.5 .29 2.8 MA61-7200 120 Vac ±10% 11.7 8.8 10.0 8.4 N/A 3.6/5.0 MA61-7201 230 Vac ±10% 15.
MA51-7x0x Series, MA61-720x Series Specifications (Continued) Environment Ambient temperature limits Shipping and Storage: -40 to 160°F (-40 to 71°C). Operating: MA51-720x/MA61-720x: 0 to 140°F (-18 to 60°C). MA51-710x: -22 to 140°F (-30 to 60°C). Temperature Restrictions: For maximum ambient 140°F (60°C) the maximum allowable fluid temperature should not exceed valve rating. See F-27252 Selection Guide for specific ratings. Actuator MA51-720x MA61-720x MA61-720x Max. Allowable Ambient @ Max.
MA51-7x0x Series, MA61-720x Series Valve Size Chart.
MA51-7x0x Series, MA61-720x Series Accessories Model No. MA51-72xx, MA61-72xx AM-731 AM-732 AM-733 AM-734 AM-756 AM-763 MA51-710x AM-756 AM-770 AM-764 Description Mounting kit - Mx51 - 720x (included with actuator). Mounting kit - Mx61 - 720x (included with actuator). Retrofit kit - discontinued VB-9xxx 1-1/2 to 2 in. valves after 9404 date code. Retrofit kit 1 - discontinued VB-9xxx - 1/2 to 2 in. valves prior to 9404 date code. Metric conduit adapter M20 x 1.5 to 1/2 in. NPT. 1/8 in.
MC-351, MC-421, MC-431, MC-4311, MC5-4311 MC-351, M 421, MC-431, MC-4311, MC5-4311 Two-Position, Non-Spring Return Actuators This actuator provides two-position operation of dampers or valves in heating, ventilating, and air conditioning systems, and similar applications where return-to-normal position is not required. Features: • Two-position actuators controlled by SPDT controller. • Non-spring return. • 24, 120, and 240 Vac models available. • SPDT auxiliary switch is standard.
MC-351, MC-421, MC-431, MC-4311, MC5-4311 Accessories Model No. Damper linkage accessories AM-111 AM-112 AM-113 AM-115 AM-116 AM-122 AM-123 AM-125 AM-125-048 AM-132 AM-161 AM-161-1 AM-301 Miscellaneous actuator accessories AM-321 AM-341 AM-363 Valve linkage accessories AV-30 & AV-300 AV-352 AV-393 AV-394 AV-396 Description Crank arm for 5/16 in. (7.9 mm) diameter damper shaft. Crank arm for 3/8 in. (9.5 mm) diameter damper shaft. Crank arm for actuator or 1/2 in. (12.7 mm) diameter damper shaft.
MF-5x13 Series, MF-5x33 Series MF-5x13 Series, MF-5x33 Series Floating Hydraulic Actuator These hydraulic spring return actuators provide floating control of hydronic heating and cooling globe valves or dampers. Features: • Floating actuators controlled by SPDT center off floating controllers or DDC controllers with 2 SPST (drive open, hold, drive close) outputs. • Spring return. • All models 24 Vac 50/60 Hz. Optional AM-610 transformer available for 120, 208, or 240 Vac.
MF-5x13 Series, MF-5x33 Series Specifications Inputs Control signal SPDT Center Off Floating Control Output or 2 SPST Control Contacts: Minimum rating of 1 A at 24 Vac, inductive load. Refer to Figure 1. Triacs: DDC controller output must be able to switch 1 A inductive load (200 V minimum). Power req. Refer to Damper Actuators Model Chart and Valve Actuator Power Input Model Chart. Connections Color coded 4 ft. (1.2 m) leads. All 24 Vac circuits are Class 2.
MF-5x13 Series, MF-5x33 Series Accessories Model No. Common AM-610 Damper Only AM-111 AM-112 AM-113 AM-115 AM-122 AM-123 AM-125 AM-125-048 AM-132 AM-161-3 AM-601 Description Nipple-mounted transformer 120/208/240 Vac 50/60 Hz 40 VA (for mounting on conduit box). Crank arm for 5/16 in. diameter damper shaft. Crank arm for 3/8 in. diameter damper shaft. Crank arm for 1/2 in. diameter damper shaft. Crank arm for 7/16 in. diameter damper shaft. Linkage connector straight type. Damper clip. 5/16 in.
MF-2xxx3 Series Floating Valve Actuator The MF-22xx3 and MF-23xx3 series floating valve actuators are non-spring return actuators used with floating DDC controllers and standard 1/2 to 2 in. two-way and three-way globe valve bodies for control of heating and cooling coils. Typical applications include VAV terminals with reheat coils, fans coil units, and unit ventilators. Certain models are thermally isolated for use with chilled fluids.
MF-2xxx3 Series Specifications Inputs SPDT Center Off (Floating) Control Contacts or Two SPST Control Contacts, minimum rating of 250 mA at 24 Vac inductive load. MF-23xx3 models require a controller with a timeout feature. Control signal Two Triacs: DDC output must be able to switch 250 mA (24 VA) inductive load (150 Vac minimum). Power Refer to Model Chart. Connections 4 foot (1.2 M) color coded 18 AWG, plenum cable rated for UL. Outputs Position feedback signal 15k ohm nominal potentiometer.
MF-2xxx3 Series Typical Applications Grn Blk SPDT To 24 Vac Floating Controller 2 MF-22xx3 MF-23xx3 White (Retract) Red (Extend) 1 4 3 Grn Blk 2 SPST To 24 Vac Output Controller 3 MF-22xx3 MF-23xx3 White (Retract) 4 Red (Extend) CAUTION: Each actuator must have its own separate controller output or relay. 1 Provide overload protection and disconnect as required. 2 Two-position 3-wire control is possible by use of a form-C controller output (MF-22xx3 series).
MF-631x3 Series Floating Valve Actuator MF-631x3 Series This valve actuator is a non-spring return actuator compatible with floating and optional proportional controllers. Features: • Floating actuator controlled by SPDT floating controller (drive open-hold-drive closed) or a DDC controller with equivalent control action (contact or triac). • Optional control module cards for proportional control (MF-63123 only): MFC-8000 for Vdc and MFC-420 for 4 to 20 mAdc.
MF-631x3 Series Specifications (Continued) Outputs Auxiliary switch (-500 models): SPDT, adjustable over actuator stroke of 1 in. The N.C. contact is factory set to make contact at 3/8 in. from the fully extended position. Electrical Rating: 1 amp at 24 Vac, 50/60 Hz. Pilot duty rating; 24 VA at 24 Vac. Connections: Color coded leads for auxiliary switch, terminal block for control. Refer to Model Chart (cannot be used when MFC control module card is installed).
MF-631x3 Series Brown Closed at extended end NO Red/White Common Orange Closed at retracted end NC Factory settings are adjustable. Figure 2 Auxiliary Switch Models MF-631x3-500. MF-63123-201 (+) Vdc Vdc Controller (-) Vdc MFC-8000 2 3 1 H G 24 Vac Transformer L1 L2 1 Factory installed in actuator. Set for 0 to 10 Vdc control signal, reverse action. Consult MFC-8000 General Instructions, F-25124 for further information. Figure 3 Basic Wiring Diagram for MF-63123-201. 100 © Copyright 2006 TAC.
MF40-7043 Series, MF41-7073 Series, MF41-7153 Series Spring Return TAC DuraDrive ® Floating Actuator For spring return applications that require floating control of dampers and valves in HVAC system. 0-7043 es, 1-7073 es, 1-7153 es Features: • 35 lb.-in. (4 N-m), 60 lb.-in (7 N-m), 133 lb.-in (15 N-m). • Direct mount to round or square damper shaft. • Overload protection throughout rotation.
MF40-7043 Series, MF41-7073 Series, MF41-7153 Series Specifications (Continued) Outputs Motor Type Electrical Mechanical Brushless DC. One auxiliary switch available with MF40-7043-501, SPDT 6A resistive @ 24 Vac, adjustable 0 to 95° (0 to 1 scale). UL Listed, switch meets VDC requirements for 6 (1.5)A, 24 Vac. Two auxiliary switch available with MF40-7153-501 or MF40-7073-502, SPDT 7A resistive @ 24 Vac, one fixed @ 5° and one adjustable 0 to 95°. UL Listed, switch meets VDC requirements for 6 (1.
MF40-7043 Series, MF41-7073 Series, MF41-7153 Series Typical Applications 1 24 Vac Transformer or 22 to 30 Vdc Black Line Volts Common Red Blue + Hot 4 Yellow/Black 1 Provide overload protection and disconnect as required. MF41-7153 MF41-7073 Drive CW 2 2 Actuators may be wired in parallel. All actuator black wires are connected to the transformer common and all red wires are connected to the hot lead. Power consumption must be observed.
MF40-7173 Spring Return TAC DuraDrive ® Floating Actuator For spring return applications that require floating control of dampers and valves in HVAC system. F40-7173 Features: • 150 lb.-in. (17 N-m) rated torque. • Direct mount to round or square damper shaft. • Overload protection throughout rotation. • True mechanical clockwise or counterclockwise spring return operation for positive close-off in tight seal damper applications. • Visual position indicator.
MF40-7173 Specifications (Continued) Outputs Motor Type Brushless DC. Direction of rotation: CW or CCW rotation is available through reverse mounting. Mechanical Dual shaft clamp: Direct coupled using a through hole output hub. Stroke: Electronically limited to 93° ± 1°. Environment Ambient Temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: -25 to 140°F (-32 to 60°C). Humidity 5 to 95% RH, non-condensing.
MF40-7173 Typical Applications 1 Red 4 CCW White Black 4 CW 3 2 COM Black 24 Vac MF40-7173 24H Black/Blue 24G Green/Yellow GRD 1 SPDT Floating or Switch/Controller or 2 SPST. 2 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating. 3 Ground wire may be Green on some models. 4 As viewed from "L" side. Figure 1 Typical SPDT Controller Wiring Diagram.
MF41-60xx Series Non-Spring Return TAC DuraDrive ® Floating Actuator The TAC DuraDrive direct coupled 24 Vac nonspring return rotary electric actuators are designed for three-position (floating) control of dampers. F41-60xx ries Features: • Compact, lightweight design. • Manual override. • Factory pre-positioned at 5° from 0 to assure damper or valve close-off. • Plenum cabling. • Feedback potentiometer models available. • cUL and UL listed; plenum versions also CE certified.
MF41-60xx Series Specifications (Continued) Environment Ambient temperature limits Shipping and Storage: -40 to 158°F (-40 to 70°C). Operating: -25 to 130°F (-32 to 55°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA 2, IP54 to EN60529. Dimensions 5-7/16 H x 2-3/4 W x 2-3/8 D in. (140 x 70x 60 mm). Agency Listings UL UL-873, Underwriters Laboratories. European Community EMC Directive (89/336/EEC). Emissions (EN50081-1). Immunity (EN50082-2). CUL Canadian Standards C22.2 No. 24-93.
MF41-6153 Series Non-Spring Return TAC DuraDrive ® Three Position Actuator The TAC DuraDrive direct-coupled, 24 Vac, nonspring return electronic actuator is designed for three-position control of building HVAC dampers. F41-6153 ries Features: • Synchronous motor technology with stall protection. • Unique self-centering shaft coupling. • Manual override. • 133 lb-in (15 Nm) torque. • Factory pre-positioned at 5° from 0 to assure damper or valve close-off. • Mechanical range adjustment capabilities.
MF41-6153 Series Specifications (Continued) Environment Ambient temperature limits Operation: -25 to 130°F (-32 to 55°C) Storage: -40 to 158°F (-40 to 70°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1, IP54 According to EN 60 529. Dimensions 8-3/8 H x 3-1/4 W x 2-2/3 D in. (210 x 80 x 70 mm). Agency Listings UL UL-873, Underwriters Laboratories. European Community EMC Directive (89/336/EEC). Emissions (EN50081-1). Immunity (EN61000-6-2). CUL Canadian Standards C22.2 No. 24-93.
MF41-6343 Non-Spring Return TAC DuraDrive ® Floating Actuator For non-spring return applications that require floating control of dampers and valves in HVAC systems. F41-6343 Features: • Direct mount to round or square damper shaft. • 300 lb.-in. (34 N-m) torque rating. • Overload protection throughout rotation. • Oil immersed gear train provides continuous lubrication. • NEMA 4 housing (IEC IP56). • Manual override to allow positioning for installation and manual operation.
MF41-6343 Specifications (Continued) Environment Ambient Temperature limits Shipping and Storage: -40 to 160°F (-40 to 71°C). Operation: -25 to 140°F (-32 to 60°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA 1, NEMA 4 (IEC IP56) with customer supplied water tight connectors. Agency Listings UL UL-873, Underwriters Laboratories Listed (File #9429 Category: Temperature-Indicating and Regulating Equipment). European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
MF41-6343 5 Controller 1 DOX Red CCW DOY White CW C 2 Black COM MF41-6343 3 GRD AC Black 24 Vac 4 24H Black/Blue 24G Green/Yellow GRD 1 Triacs switching to 24G. 2 Do not connect drive wiring to C terminal of controller. 3 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating. 4 Ground wire may be Green on some models. 5 As viewed from Left (L) side.
MF4D-60x3 Series Non-Spring Return TAC DuraDrive™ Floating Actuator TAC DuraDrive overshaft actuators are designed to provide an economical and reliable solution for many overshaft damper and ball valve requirements. All products accommodate shaft sizes up to 1/2 in. (13 mm) in diameter. Non-spring return models provide either 35 in-lb (4 N-m) or 70 in-lb (8 N-m) in proportional control. Features: • Floating models controlled by SPDT floating controllers.
MF4D-60x3 Series Specifications (Continued) Environment Ambient temperature limits Shipping and Storage: -40 to 160°F (-40 to 71°C). Operating: -22 to 140°F (-30 to 60°C). Humidity 15 to 95% RH, non-condensing. Locations NEMA 1, NEMA 2, UL Type 2 (IEC IP54) with customer supplied water tight conduit connectors. Enclosure is air plenum rated. Agency Listings UL 873 Underwriters Laboratories (File #E9429 Category Temperature-Indicating and Regulating Equipment).
MF4D-60x3 Series 24 Vac Transformer or 20 to 30 Vdc 1 Line Volts Common Hot 6 Black Common Red Hot (+DC) MF4D-x033-x00 Drive CW Blue Yellow/Black Drive CCW Violet AO 3 4 5 Controller Feedback Signal (-) 2 to 10 Vdc (+) Figure 3 Triac Sink.
MF4D-x033 Series Spring Return TAC DuraDrive™ Floating Actuator TAC DuraDrive overshaft actuators are designed to provide an economical and reliable solution for many overshaft damper and ball valve requirements. All products accommodate shaft sizes up to 1/2 in. (13 mm) in diameter. Spring return models provide 30 in-lb (3.4 N-m) of torque. F4D-x033 ries Features: • Controlled by SPDT floating controllers. • 30 in-lb (3.4 N-m) of torque. • Polymer housing rated for NEMA 2/IP54 rated for plenum use.
MF4D-x033 Series Specifications (Continued) Environment Ambient temperature limits Shipping and Storage: -40 to 160°F (-40 to 71°C). Operating: -22 to 140°F (-30 to 60°C). Humidity 15 to 95% RH, non-condensing. Locations NEMA 1, NEMA 2, UL Type 2 (IEC IP54) with customer supplied water tight conduit connectors. Enclosure is air plenum rated. Agency Listings UL 873 Underwriters Laboratories (File #E9429 Category Temperature-Indicating and Regulating Equipment).
MF4D-x033 Series 24 Vac Transformer or 20 to 30 Vdc 1 Line Volts Common Hot Black Common Red Hot (+DC) 6 MF4D-x033-x00 Drive CW Blue Yellow/Black Drive CCW Violet AO 3 4 5 Controller Feedback Signal (-) 2 to 10 Vdc (+) Figure 3 Triac Sink.
MF4E-60x3x Series Non-Spring Return TAC DuraDrive™ Floating Actuator The MF4E-6043x series 35 lb-in. (3.3 N-m) and MF4E-6083x series 70 lb-in. (6.6 N-m) non-spring return, direct-coupled actuators provide affordable floating control for dampers and rotary valves. They are suitable for use with single pole, double throw (SPDT) floating thermostats or Direct Digital Control (DDC) systems. Features: • Visual position indicator.
MF4E-60x3x Series Specifications Inputs Control signal Floating control, 24 Vac +20%/-15%. Power Input See Model Chart. All 24 Vac curcuits are Class 2. Electrical Connections 10 ft plenum rated cable. Outputs Stroke: 95o ± 3o of rotation. Stroke limit is adjustable 0o to 95o in both clockwise (CW) and counterclockwise (CCW) directions. Manual Override: Allows free shaft rotation to any position from 0o to 95o. Mounting: Mounts directly onto a 1/2 in. (13 mm) round shaft.
MF4E-60x3x Series Typical Applications 24 Vac Transformer 1 Common Black Line Voltage Typical Floating Controller 1 Provide overload protection and a disconnect as required. 2 Actuators may be wired in parallel only if they have the same rotational speed (stroke timing). When doing so, be sure to observe power consumption limits. 3 To increase actuator life, design the system with a time-out feature that removes power from the actuator between uses.
MF51-7x03 Series, MF61-7203 Spring Return TAC DuraDrive ® Floating Actuator TAC DuraDrive Linear Actuators are designed to mount directly onto two-way or three-way globe valves without the use of linkages. They provide linear travel to operate globe valves from 1/2 to 2 in. VB-7xxx valves and discontinued 1/2 to 1-1/4 in. VB-9xxx valves, 2-12/ to 4-inch VB-9xxx valves, and 2-1/2 to 5-in VB-8xxx valves in chilled water, hot water and steam applications up to 366°F (186°C).
MF51-7x03 Series, MF61-7203 Specifications Inputs Control signal See Model Chart for actuator models and control type. Power See Model Chart. All 24 Vac circuits are Class 2. All circuits 30 Vac and above are Class 1. Half wave device. Connections Models with -0xx have 3 ft. (91 cm) appliance wire connections. Models with -1xx have 3 ft. (91 cm) plenum wire connections. Enclosure accepts 1/2 in. (13 mm) conduit connectors. For M20 Metric connector, use AM-756 adaptor.
MF51-7x03 Series, MF61-7203 Valve Size Chart.
MF51-7x03 Series, MF61-7203 Typical Applications Black 1 24 Vac Transformer Line Volts or 20-30 Vdc Common MFx1-7x03-xxx Hot (+DC) MF61-7203 Red Blue Typical Floating Controller Extend Yellow/Black Retract 2 1 Provide overload protection and disconnect as required. If controller uses a full wave power supply and does not provide isolated outputs, a separate transformer must be used. 3 2 Actuators may be wired in parallel.
MFC-420 FC-420 Control Module Card This Control Module Card is designed as a plug-in module for the MF-63123 Floating Valve Actuator. The MFC-420 card allows the actuator to accept proportional mAdc signals. Features: • Acceptance of all commonly used proportional mAdc input signals. • Factory set for 4 to 20 mAdc applications. • Switch selectable control input signal extend point and span for quick, accurate field setup. • Control module plugs into MF-63123 actuator for quick, easy installation.
MFC-420 Specifications (Continued) Agency Listings UL File E9429 Temperature Indicating and Regulating Equipment. CUL Canadian Standard C22.2 #24-93 European Community EMC Directive (89/336/EEC). Typical Applications 4 to 20 mAdc Controller (+) mAdc 2 (-) mAdc 3 MFC-420 L1 H G L2 MF-63123 Figure 1 Typical Wiring Diagram for MF-63123 with MFC-420. 1 2 3 Transformer G H T4 (G) T5 (H) MF-63123 1 2 3 Transformer G H T4 (G) 3 H Factory Set for 4 to 20 mAdc D.A.
MFC-420 Direct/Reverse Action Shorting Blocks Hysteresis (9, 10) Top Switch Blocks with Dip Switches Wiring Terminal Not Used (+) Positive mAdc Input (-) mAdc Input (Common) Extend Point SW1 1 2 3 Span (1-8) SW2 Mounting Pin Brackets Figure 3 MFC-420 Control Module Switch and Adjustment Locations. Showing Wiring Designations and Typical Factory Settings for Switches and Shorting Blocks.
MFC-8000 MFC-800 Control Module Card This card acts as a plug-in module for the MF-63123 Floating Valve Actuator. It allows the actuator to accept proportional voltage Vdc signals. Features: • Acceptance of all commonly used proportional Vdc input signals (0 to 10 Vdc and 6 to 9 Vdc). • Factory set at 6 to 9 Vdc for TAC System 8000 applications. • Switch-selectable control input signal extend point and span for quick, accurate field setup. • MF-63123 actuator plug-in for quick, easy installation.
MFC-8000 Specifications (Continued) Agency Listings UL File E9429 Temperature Indicating and Regulating Equipment. CUL Canadian Standard C22.2 #24-93 European Community EMC Directive (89/336/EEC). Typical Applications Vdc Controller (+) Vdc 2 (-) Vdc 3 MFC-8000 L1 1 H G L2 MF-63123 1 Factory installed in actuator. Set for 6 to 9 mAdc control signal. Consult MFC-8000General Instructions, F-25124 for further information. Figure 1 Typical Wiring Diagram for MF-63123 with MFC-8000.
MFC-8000 Direct/Reverse Action Shorting Blocks Hysteresis (9, 10) Top Switch Blocks with Dip Switches Wiring Terminal Not Used (+) Positive mAdc Input (-) mAdc Input (Common) 1 2 3 Extend Point SW1 Span (1-8) SW2 Mounting Pin Brackets Figure 3 MFC-8000 Control Module Switch and Adjustment Locations Showing Wiring Designations, Typical Factory Switch, and Shorting Block Settings. Note: Extend point is the voltage required to drive an actuator to fully extended position. This is set at SW1.
MM-400 Series, MM-500 Series, MMR-400 Series, MMR-500 Series Electric/Electronic Gear Train Modular Actuators For operation of air control dampers and water valves in HVAC systems. The modular actuators are designed to be used with MMC-Series control modules. M-400 ries, M-500 ries, MR-400 ries, MR-500 ries Features: • 50 lb-in. spring return and 150 lb-in. non-spring return models featuring the TAC patented load sensing feature.
MM-400 Series, MM-500 Series, MMR-400 Series, MMR-500 Series Specifications Optional MMC series control modules The MMC series control module determines the control signal (order separately). MMC-90: 135 Ω slidewire. MMC-401: TS-5721-102 temperature sensor. The economizer module can only be used with the MM-500 series actuator. Control signal MMC-420: 4 to 20 mAdc. MMC-421: 2 to 20 mAdc. MMC-468: Two position SPST or SPDT. MMC-8000: 0 to 20 mAdc or 0 to 20 Vdc. Power req.
MM-400 Series, MM-500 Series, MMR-400 Series, MMR-500 Series Accessories Model No. Common AD-8961-407 AD-8961-408 AM-231 AM-232 AV-632 Damper Only AM-111 AM-112 AM-113 AM-115 AM-122 AM-123 AM-125 AM-125-048 AM-132 AM-230 AM-234 AM-235 AM-301 Valve Only AV-630 TOOLS TOOL-16 F-27382-1 Description Parallel resistor kit for MM series. W973 interface kit for MM series. Transformer kit (if power voltage is not 24 Vac). Weather resistance kit (factory installed).
MMC Series MMC Ser Control Module For MM, MMR 400 and 500 series actuators. These plug in control modules are used with the MM-400, MM-500, MMR-400, and MMR-500 Series actuators. Features: • Plugs into the MM, and MMR actuators. • Accepts various control signals. • Johnson and Honeywell interface models. • Economizer control models. Model Chart Control Signals Model No.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series Reversible and Proportional Electric Actuators The MP Series Actuators are used for two-position, floating, and proportional control of dampers, valves, and program switches in heating, ventilation, and air conditioning applications or similar applications. MP-3xx eries, MP-4xx eries, MP-2xxx eries, nd MPxxx eries Features: • Proportional actuators with built-in feedback potentiometers.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series MP-4xx Series Model No. Solid State Application Drive CP-9301 CP-9302 Power Requirements Volts Hz Amps Output Shaft Torque lb.-in. (N-m) Timing Seconds (No Load) MP-421 25 MP-422 25 to 250 (Adj.) 60 (6.8) MP-423 Proportional Available 0.65 MP-452 MP-453 refer to footnotec MR-461-691 Proportional Available MP-470 refer to footnote c MP-471-691 180 SPDT ⎯ 40 90 (Adj. b) 180 (Adj.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series MP-2xxx Series. Model No. Application Solid State Drive CP-9301 CP-9302 MP-2113-500 Power Requirements Volts Hz 24 MP-2130-500 Proportional Available Amps Output Shaft Timing Torque Degrees of Seconds lb.-in. Rotation (N-m) (No Load) 60 0.5 50 (5.6) 25 MP-2150-500 MP-2151-500 a 240 Aux. Switch Built-in Transformera 180 (nonAdj.) 2.2 120 Spring Return 0.22 30 90 (nonAdj.) ⎯ No SPDT Yes 180 (nonAdj.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series Specifications Input Control signals Floating Refer to the Model Charts for input control signal capability versus specific actuator models. Requires one Single Pole Double Throw (SPDT) switch with floating (center off) position rated at 0.9 amps at 24 Vac or two Single Pole Single Throw (SPST) switches rated at 0.9 amps at 24 Vac. SPDT: Requires snap acting switch rated at 0.9 amps at 24 Vac.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series Accessories Model No. Description Damper linkage accessories AM-111 Crank arm for 5/16 in. (7.9 mm) diameter damper shaft. AM-112 Crank arm for 3/8 in. (9.5 mm) diameter damper shaft. AM-113 Crank arm for 1/2 in. (12.7 mm) diameter damper shaft. AM-115 Crank arm for 7/16 in. (11.1 mm) diameter damper shaft. AM-116 Splined crank arm for actuator. AM-122 Linkage connector, straight type. AM-123 Damper clip. AM-125 5/16 x 20 in. (7.9 mm x 0.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series Max. Amp Rating 120V 240V Running 5.8 2.9 Locked Rotor 34.8 17.4 Non-inductive 12 6 1 6 Terminal Identification 5 Cam Action Factory Setting CCW CW Figure 2 Adjustable Auxiliary Switch SPDT. 1 1-Feedback. 4 PP-220 Series 1 1 Controller R 3 B 4 2 C 2 X 2 MP-300 MP-400 MP-2000-500 MP-4000 Series Actuator 3 7 Green AC Supply 2 C-Common. 3 R-Closes on pressure drop and rotates actuator CCW.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series AE-504 Parallel Relay Factory Installed to the Actuator 1 Resistor & jumper present on 24V actuators only. Black Slidewire Input 2 These terminals marked L1 and L2 on line voltage actuators. CCW 3 Brown 3 Direction actuator will drive. CW 3 4 Case ground screw.
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series Yellow MP-3xx, MP-4xx, MP-21xx, or MP-97xx Series Actuator Blue Wire Nuts Drive Input Violet/White 1 2 Violet CP-9301 or CP-9302 Actuator Drive Brown/White 3 Brown Brown/Black Red/Black 3 3 Blue/Black 3 Yellow/Black Green/Yellow 6 To Controller Common Purge Input (Override Input) Purge + (Override +) Actuator Terminals 7 7 100 Ohm Slidewire 4 8 Purge Override (Input Signal Override) 8 Shading Windings 3 1 Caution: Before ins
MP-52xx Series P-52xx ries Electronic Hydraulic Actuator These actuators provide electronic proportional control of dampers, valves, or program switches requiring the return to normal position upon power interruption. Features: • Compatibility with 2 to 15 Vdc TAC System 8000 input signals. • Proportional control by variable Vdc input signal. • Spring return. • Fixed 3 Vdc operating span. • Non-adjustable start point and non-positive positioning.
MP-52xx Series Maximum Allowable Ambient Air Temperature for Valve Actuators.
MP-52xx Series Accessories Model No. Damper Only AM-111 AM-112 AM-113 AM-115 AM-122 AM-123 AM-125 AM-125-048 AM-132 AM-161-3 AM-601 Description Crank arm for 5/16 in. (7.9 mm) diameter damper shaft. Crank arm for 3/8 in. (9.5 mm) diameter damper shaft. Crank arm for 1/2 in. (12.7 mm) diameter damper shaft. Crank arm for 7/16 in. (11.1 mm) diameter damper shaft. Linkage connector straight type. Damper clip. 5/16 in. (7.9 mm) diameter x 20 in. (508 mm) damper rod. 5/16 in. (7.9 mm) diameter x 48 in. (1,219.
MP-54xx Series MP-54xx Series Electronic Positive Positioning Hydraulic Actuator These actuators provide electronic proportional control of dampers, valves, or program switches requiring the return to normal position upon power interruption. Features: • Proportional control by variable Vdc input signal. • Compatibility with 2 to 15 Vdc TAC System 8000 input signals. • Spring return. • Fixed 3 Vdc operating span. • Adjustable 2 to 12 Vdc start point for paralleling or sequencing of actuators.
MP-54xx Series Maximum Allowable Ambient Air Temperature for Valve Actuators.
MP-54xx Series Accessories Model No. Damper only AM-111 AM-112 AM-113 AM-115 AM-122 AM-123 AM-125 AM-125-048 AM-132 AM-161-3 AM-601 Valve only AV-600 AV-601 AV-7600-1 TOOLS (factory available) TOOL-12 TOOL-19 TOOL-37 TOOL-202 150 Description Crank arm for 5/16 in. diameter damper shaft. Crank arm for 3/8 in. diameter damper shaft. Crank arm for 1/2 in. diameter damper shaft. Crank arm for 7/16 in. diameter damper shaft. Linkage connector straight type. Damper clip. 5/16 in. diameter x 20 in. damper rod.
MP-54xx Series Typical Applications CP-8102 TP-810x TP-8121 TP-8124 TP-8232 Typical Controllers MP-54xx Figure 1 Typical Control Wiring for up to Six MP-54xx Series Actuators to Controllers Requiring External 20 Vdc Power Supply. CC-8111 CC-8118 CC-8218 CP-8161 CP-8261 Typical Controllers MP-54xx MP-54xx Figure 2 Typical Control Wiring for Up to Six MP-54xx Series Actuators to Controllers Having Internal 20 Vdc Power Supply. Note: 1.
MP-55xx Series Electronic Positive Positioning Actuator MP-55xx Series The MP-5500 Series Actuators are for the electronic proportional control of dampers, valves, or program switches which require the return to normal position upon power interruption. This series is compatible with 0 to 10 Vdc input signals. Features: • Proportional actuators controlled by variable Vdc input signal. • Spring return. • Fixed 10 Vdc operating span. • 10,000 ohms or greater input impedance.
MP-55xx Series Maximum Allowable Ambient Air Temperature for Valve Actuators. Temperature of Media in the Valve Bodya (Check the Rating of the Valve) °F (°C) Maximum Allowable Ambient Air Temperature of MP-55xx Series AV-600 Only for Chilled Water Applications °F (°C) 366(180) 88 (31) 340 (171) Do Not Use 281 (138) 181 (83) 93 (34) 103 (39) 120 (48) 80 (26) a AV-600 and AV-601 °F (°C) 140 (60) 140 (60) Maximum allowable ambient temperature of the actuator 140 F (60 C), minimum -20 F (-29 C).
MP-55xx Series Accessories Model No. Damper only AM-111 AM-112 AM-113 AM-115 AM-122 AM-123 AM-125 AM-125-048 AM-132 AM-161-3 AM-601 Description Crank arm for 5/16 in. diameter damper shaft. Crank arm for 3/8 in. diameter damper shaft. Crank arm for 1/2 in. diameter damper shaft. Crank arm for 7/16 in. diameter damper shaft. Linkage connector straight type. Damper clip. 5/16 in. diameter x 20 in. damper rod. 5/16 in. diameter x 48 in. damper rod. Ball joint connector. Damper linkage kit.
MP-9xxx Series P-9xxx ries Proportional or Floating Actuators These actuators provide control of heavy dampers, large valves, and other high torque applications in heating, ventilating, air conditioning, and similar applications which do not require return to a normal position. Features: • High torque proportional gear train actuators accept the following signals: - 100 to 1,000 Ω slidewire (requires AE-504). - SPDT floating or snap-acting controller. - Variable Vdc . - Variable mAdc.
MP-9xxx Series Actuator Drive Compatability Actuator Drives Input Type Actuators Actuator Model Vdc Vdc mA Vdc/mA mA/Vdc CP-8301-xxxa CP-8391-456a CP-8391-716a CP-9301 CP-9302 MP-9610 — X X — — MP-9713 X — — X X MP-9750 X X X X X MP-9810 — X X — — MP-9830 — X X — — MP-9910 — X X — — a May require close nipple conduit extensions for mounting x-6680. Specifications Control circuit Requires SPDT switch with neutral (floating) or two-position and proportional.
MP-9xxx Series Accessories Model No. Damper Linkage Accessories AE-504 AM-321 AM-332 AM-341 AM-342 AM-345 AM-369 AM-392 Description 100 to 1000 Ω input actuator drive. Two step switch kit. 100 Ω single potentiometer. Four step switch kit. Two step switch and potentiometer kit. Actuator mount, time delay relay for MP-9810, MP-9830 and MP-9910, field modified for panel mounting. NEMA 4 gasket kit.a Crank arm for actuator, 1/2 in. slot provides for adjustable radius from 1 in. (25 mm) to 5 in.
MP-9xxx Series 1 Terminals 1, 5, & 6 are used for built-in auxillary switch. 2 Rotates CW or valve stem down. 3 Rotates CCW or valve stem up. 4 SPDT neutral off switch may be used on manual positioning application. 3 3 SPDT Floating Control or Two-Position Switch 4 5 2 2 MP-9610 MP-9810 MP-9830 MP-9910 1 L1 L2 5 Switch control circuit is 1.8 amp at 120 Vac. 120 Vac 60Hz Figure 4 Typical Reversible Floating or Two-Position.
MPR-5600 Series PR-5600 ries Proportional Actuators These actuators provide electronic proportional control of dampers and valves requiring return to normal position upon power interruption. They are compatible with controllers generating 4 to 20 mA input signals. Features: • Spring return. • 24, 120, and 240 Vac models available. • Damper models with linkage or base models requiring separate damper or valve linkage available. • Die cast lower housing with 1/2 in.
MPR-5600 Series Specifications Actuator inputs Control circuit Input impedance Power input Connections Actuator outputs Electrical Mechanical MPR-561x and -563x series: Two-wire. 4 to 20 mA. 82.5 Ω for 40 to 20 mA input. Refer to Valve (Basic) Actuators Model Chart and Damper Actuators Model Chart. Color coded 4 ft. (1.2 m) leads. Position signals: Internal feedback circuitry provides positive positioning of the damper in relation to the controller signal.
MPR-5600 Series Restrictions on Maximum Ambient Temperature for Valve Actuators. Maximum Temperature of Media in the Valve Body (Check Rating of the Valve) °F (°C) Maximum Ambient Temperature of MPR-561x and MPR-573x Series. AV-600 (only) °F (°C) AV-600 and AV-601 °F (°C) 88 (31)a 366 (186) 340 (171) 93 (34) Do Not Use 281 (138) 103 (39)b 120 (48) b 181 (83) 80 (26) 140 (60) b 140 (60) b a Minimum allowable ambient temperautre of the actuators is -20°F (-29°C).
MPR-5713 MPR-5713 Proportional Actuators The MPR-5713 actuator provides electronic proportional control of dampers and valves which require a return to the normal position upon power interruption. The actuator is compatible with 135 ohm slidewire controllers (Series 90). Features: • Spring return. • Available in damper models or base models that require damper or valve linkage. • Die cast lower housing with 1/2 in. conduit opening and painted steel upper housing.
MS-22353 Proportional Valve Actuator The MS-22353 proportional valve actuator is a non-spring return actuator used with proportional 2 to 10 Vdc or 4 to 20 mA controllers and 1/2 to 1-1/4 in. two-way and three-way globe valve bodies for control of heating and cooling coils. Typical applications include VAV terminals with reheat coils, fan coil units, and unit ventilators. S-22353 Features: • Proportional non-spring return actuator controlled by 2 to 10 Vdc or 4 to 20 mA.
MS-22353 Specifications (Continued) Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: Minimum 40°F (4°C). Refer to “Restrictions on Ambient Temperature for Valve Actuators” for maximum temperatures. Fluid Temperature Limits Refer to “Restrictions on Ambient Temperature for Valve Actuators.” Humidity 5 to 95% RH, non-condensing. Refer to “Restrictions on Ambient Temperature for Valve Actuators” for dew point temperature. Locations NEMA Type 1.
MS-22353 L1 L2 24 Vac Transformer 24H Black 24G Red 24G Green Earth 0 to 10 Vdc Controller 24H 1 MS-22353 2 White (+) 0 to 10 Vdc Output Unused (wire nut) (+) VDC IN Brown (+) mA DC IN (-) Common Orange (-) Common Blue Feedback Input (+) VFB Feedback Signal 3 1 The MS-22353 actuator contains a half-wave rectifier power supply. When connecting multiple devices to a common transformer connect 24H and 24G with half-wave rectifier or isolated power supplied devices, only.
MS40-7043, MS41-7073, MS41-7153 Spring Return TAC DuraDrive ® Proportional Actuator For spring return applications that require proportional modulation control of dampers and valves in HVAC systems. Features: • Proportional models controlled by 6-9 Vdc, 2-10 Vdc or 4-20 mA with the addition of a 500 ohm resistor. • 35 lb.-in. (4 N-m), 60 lb.-in (7 N-m), 133 lb.-in (15 N-m). • Direct mount to round or square damper shaft. • Overload protection throughout rotation.
MS40-7043, MS41-7073, MS41-7153 Specifications Inputs Control signal Proportional, 6 to 9 Vdc, 2 to 10 Vdc, or 4 to 20 mA with 500 ohm resistor. Power All 24 Vac circuits are Class 2. Refer to Model Chart for AC and DC ratings. Half wave device. Connections MS41-7073, MS41-7153: 3 ft. (0.9 m) long, appliance cables, 1/2 in. conduit connectors. For M20 metric conduit, use AM-756 adaptor. MS40-7043: 3 ft. (0.9 m) long, plenum-rated cables, 1/2 in. conduit connectors.
MS40-7043, MS41-7073, MS41-7153 Accessories Model No. MS40-7043, MS41-7073, MS41-7153 AM-673a AM-674 AM-675 AM-676 Description AM-703 AM-704 AM-705 AM-706 AM-707 AM-708 AM-756 AM-714 AM-715f AM-762 Mounting bracket. Weather shield. Weather shield base. Universal shaft extension, approximately 9-1/2” long (242 mm) for use on 3/8” to 11/16” (10 to 17 mm) round shafts, 3/8” to 9/16” square shafts. (AM-753 clamps required). Span adjustment. Modulating interface. Positioner. Positioner. Digital indication.
MS40-7043, MS41-7073, MS41-7153 Typical Applications 24 Vac Transformer 1 Grey Black Red Yellow/Black Line Volts Control Signal 2 to 10 Vdc Common Common MS40-7043 MS40-7043-501 Hot AI 2 Actuators may be connected in parallel. Power consumption and input impedance must be observed. Green/Yellow (-) (+) 1 Provide overload protection and disconnect as required. L R 2 Figure 1 2 to 10 Vdc Control of MS40-7043 and MS40-7043-501 Actuator.
MS40-7043, MS41-7073, MS41-7153 1 24 Vac Transformer Grey Common Common Black Red Line Volts Control Signal 4 to 20 mA Auxiliary Power +20 Vdc 25 mA (-) (+) Hot (DC) 2 AI Yellow/Black (-) (+) MS40-7043-MP MS40-7043-MP5 Blue AO Green/Yellow L R 3 1 Provide overload protection and disconnect as required. 2 For unison operation in 4 to 20 mA applications, actuators may be wired in series and mounted on separate shafts.
MS40-7043, MS41-7073, MS41-7153 Figure 5 Typical Wiring Diagrams for Proportional Control 24 Vac Basic and Double Auxiliary Switch Models. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
MS40-717x Series Spring Return TAC DuraDrive ® Proportional Actuator For spring return applications that require proportional modulation control of dampers and valves in HVAC systems. Features: • 150 lb.-in. (17 N-m) rated torque. • Direct mount to round or square damper shaft. • Overload protection throughout rotation. • True mechanical clockwise or counterclockwise spring return operation for positive close-off in airtight applications. • Oil immersed gear train provides continuous lubrication.
MS40-717x Series Specifications Inputs Control signal Proportional, 2 to 10 Vdc or 4 to 20 mAdc with integral 500 ohm resistor. Power Refer to Model Chart. Connections 2 ft. (0.6 m) appliance cables, 1/2 in. conduit connector. For M20 metric conduit, use AM-756 adaptor. Outputs Motor Type Brushless DC. Direction of rotation: CW or CCW rotation is available through reverse mounting. Dual shaft clamp: Direct coupled using a through hole output hub.
MS40-717x Series Typical Applications 2 to 10 Vdc + Unused (wire nut) 1 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating. White +IN Red 500Ω Black COM Black 120 Vac 2 Ground wire may be Green on some models. 2 White MS40-7170 1 L1 3 L2 Green/Yellow GRD 3 See "Power and Control Wiring Color Codes" for L1 and L2 wire colors. Figure 1 Typical MS40-7170 2 to 10 Vdc Wiring Diagram (120 Vac).
MS41-60xx Series Non-Spring Return TAC DuraDrive ® Modulating Actuator The TAC DuraDrive direct coupled 24 Vac nonspring return rotary electric actuators are designed for modulating control of dampers. S41-60xx ries Features: • Compact, lightweight design. • Self-adapting capability for maximum flexibility in damper positioning. • Manual override. • 5° offset from 0° as shipped from factory. • Offset and slope (zero and span) adjustment models available.
MS41-60xx Series Specifications Inputs Control signal MS41-60x3: Proportional, 0 to 10 Vdc; input resistance 100KΩ. Control signal adjustment available with MS41-60x3-522 and MS41-60x3-522. Start point (offset): 0 and 50 Vdc (factory setting = 0 Vdc) Span 2 to 30 Vdc. Power 24 Vac, +20%-15%, rated Class 2, Class III per EN60730. MS41-6083: 24 Vac +20%/-10% at 90 to 130°F (32 to 55°C) ambient. Half wave device. Connections 3 ft. (0.9 m) long, 18 AWG leads, plenum-rated.
MS41-60xx Series Typical Applications 1 24 Vac Transformer Black Red Line Volts Common (2) MS41-6043 Hot (1) (-) (+) Grey AI (8) 0 -10 Vdc Feedback Signal (-) 2 to 10 Vdc (+) Pink AO (9) 2 - 10 Vdc output Vdc Control Signal Figure 1 Typical Wiring for Proportional Control, 24 Vac, 0-10 Vdc Input. Switch A S1 (COM) S3 (N.O.) Black Leads S2 (N.C.) Switch B S6 (N.O.) S5 (N.C.) S4 (COM) Figure 2 Typical Wiring for Auxiliary Switch Models MS41-60x3-502, -522, or -202.
MS41-6153 Series Non-Spring Return TAC DuraDrive ® Modulating Actuator The TAC DuraDrive direct-coupled, 24 Vac, nonspring return electronic actuator is designed for modulating control of building HVAC dampers. Features: • Synchronous motor technology with stall protection. • Unique self-centering shaft coupling. • Manual override. • 133 lb-in (15 N-m) torque. • 5° offset from 0° as shipped from factory. • Mechanical range adjustment capabilities.
MS41-6153 Series Specifications (Continued) Outputs Position output signal wires 9 and 2. Output voltage: 0 to 10 Vdc. Maximum output current: ± 1 mA Dual auxiliary switches available on MS41-6153-502. Switch contact rating: 6A resistive, 2A inductive. Switch voltage: 24 Vac. Electrical Switching hysteresis: 2. Switch range: Switch A: 0 to 90° range in 5° intervals; Recommended range usage: 0 to 45°; Factory setting: 5°.
MS41-6153 Series Typical Applications 1 24 Vac Transformer Black Red Line Volts Common (2) (-) (+) Gray AI (8) Feedback Signal (-) 2 to 10 Vdc (+) Pink AO (9) Input Control Signal MS41-6153 Hot (1) Figure 1 Typical Wiring for Proportional Control 24 Vac, 0-10 Vdc Input Standard. Switch A Gray/Pink Gray/Blue S3 (N.O.) S2 (N.C.) Gray/Red S1 (COM) Black/Pink Black/Blue S6 (N.O.) S5 (N.C.
MS4D-60x3 Series Non-Spring Return TAC DuraDrive™ Proportional Actuator TAC DuraDrive overshaft actuators are designed to provide an economical and reliable solution for many overshaft damper and ball valve requirements. All products accommodate shaft sizes up to 1/2 in. (13 mm) in diameter. Non-spring return models provide either 35 in-lb (4 N-m) or 70 in-lb (8 N-m) in proportional control.
MS4D-60x3 Series Specifications Inputs Control signal See Model Chart for actuator models and control types. Power See Model Chart. All 24 Vac circuits are Class 2. Half wave device. Connections 10 ft. plenum cables, enclosure accepts 1/2 in. (13 mm) conduit connector. For M20 Metric conduit, use AM-756 adapter. Outputs Electrical Position Feedback Voltage: For voltage ranges, the feedback signal is the same range as the input signal. The 4 to 20 mA current range has a 2 to 10 Vdc feedback signal.
MS4D-60x3 Series Typical Applications 4 to 20 mAdc or Vdc Proportional Control 4 to 20 mAdc Controller Output Driving 2 to 10 Vdc Actuators 24 Vac Transformer 1 or 20-30 Vdc Blk Com Line MS4D-xxx3-xx0 Red Hot (+DC) Volts AI Yel/Blk 2 3 Violet AO Vdc or mAdc (-) 5 Control Signal (+) 1 24 Vac Transformer or 20-30 Vdc Blk Red Line Volts 500 Ω Control Signal (-) 4 to 20 mAdc (+) 4 (-) Feedback Signal 2 to 10 Vdc (+) 6 (-) Vdc Feedback signal (+) 2 Com MS4D-xxx3-100 Hot (+DC) 5 2 Yel/Blk AI Vio
MS4D-7033 Series, MS4D-8033 Spring Return TAC DuraDrive™ Proportional Actuator TAC DuraDrive overshaft actuators are designed to provide an economical and reliable solution for many overshaft damper and ball valve requirements. All products accommodate shaft sizes up to 1/2 in. (13 mm) in diameter. Spring return models provide 30 in-lb (3.4 N-m) of torque. Features: • Controlled by 0 to 3 Vdc, 6 to 9 Vdc, 0 to 10 Vdc, 2 to 10 Vdc or 4 to 20 mAdc. Control function direct/reverse action is jumper selectable.
MS4D-7033 Series, MS4D-8033 Specifications Inputs Control signal See Model Chart for actuator models and control types. Power See Model Chart. All 24 Vac circuits are Class 2. Half wave device. Connections 10 ft. plenum cables, enclosure accepts 1/2 in. (13 mm) conduit connector. For M20 Metric conduit, use AM-756 adapter. Outputs Electrical Position Feedback Voltage: For voltage ranges, the feedback signal is the same range as the input signal.
MS4D-7033 Series, MS4D-8033 Typical Applications 24 Vac Transformer 1 or 20-30 Vdc Blk Com Line MS4D-xxx3-xx0 Red Hot (+DC) Volts AI Yel/Blk 2 3 Violet AO Vdc Control Signal (-) 5 6 (+) (-) Vdc Feedback signal (+) 1 24 Vac Transformer or 20-30 Vdc Blk Red Line Volts Control Signal (-) 4 to 20 mAdc (+) 4 (-) Feedback Signal (+) 2 to 10 Vdc 2 500 Ω Com Hot (+DC) MS4D-xxx3-xx0 5 2 Yel/Blk AI Violet AO 3 6 To Additional Actuators 2 to 10 Vdc Figure 1 Typical Wiring Diagrams for Proportional Con
MS41-634x Series Non-Spring Return TAC DuraDrive ® Proportional Actuator For non-spring return applications that require proportional modulation control of dampers and valves in HVAC systems. S41-634x ries Features: • Direct mount to round or square damper shaft. • 300 lb.-in (34 N-m) rated torque. • Overload protection throughout rotation. • Oil immersed gear train provides continuous lubrication. • NEMA 4 housing (IEC IP56). • Manual override to allow positioning for installation and manual operation.
MS41-634x Series Specifications (Continued) Environment Temperature limits Shipping and Storage: -40 to 160°F (-40 to 71°C) ambient. Operating: -25 to 140°F (-32 to 60°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA 1, NEMA 4 (IEC IP56) with customer supplied water tight connectors. Dimensions 10-27/32 H x 4 W x 4 D in. (275 x 102 x 102 mm). Agency Listings UL UL-873, Underwriters Laboratories Listed (File #E9429 category: Temperature-Indicating and Regulating Equipment.
MS51-7103 Series, MSx1-7203 Series Spring Return TAC DuraDrive ® Proportional Actuator TAC DuraDrive Linear Actuators are designed to mount directly onto two-way or three-way globe valves without the use of linkages. They provide linear travel to operate globe valves from 1/2 to 2 in. VB-7xxx valves, discontinued 1/2 to 1-1/4 in. VB-9xxx valves, 2-1/2 to 4 in. VB-9xxx valves, and 2-1/2 to 5 in. VB-8xxx valves in chilled water, hot water and steam applications up to 366°F (186°C).
MS51-7103 Series, MSx1-7203 Series Model Chart Actuator Power Input Running Part No. MS51-7103000b MS51-7103100 b MS51-7103020 b MS51-7103120 b Control Action 50 Hz Voltage Holding 60 Hz 50/60 Hz VA W VA W 6.6 4.2 6.6 4.2 DC Amps Linear Stroke Inches Approximate Timing in Seconds @ 70°F (21°C)a Output Force Rating lb.-in. (N-m) Powered Spring Return Min. Max. Stall 1/2 in.
MS51-7103 Series, MSx1-7203 Series Specifications Inputs Control signal See Model Chart for actuator models and control type. Power See Model Chart. All 24 Vac circuits are Class 2. All circuits 30 Vac and above are Class 1. Half wave device. Connections Models with -0xx have 3 ft. (91 cm) appliance wire connections. Models with -1xx have 3 ft. (91 cm) plenum wire connections. Enclosure accepts 1/2 in. (13 mm) conduit connectors. For M20 Metric connector, use AM-756 adaptor.
MS51-7103 Series, MSx1-7203 Series Valve Size Chart.
MS51-7103 Series, MSx1-7203 Series Typical Applications mAdc or Vdc Proportional Control 1 1 Provide overload protection and disconnect as required. 24 Vac Transformer or 20-30 Vdc Blk Com Red Hot (+DC) AI Yel/Blk Violet AO Line Volts (-) (+) (-) Vdc Feedback Signal (+) Vdc or mAdc Control Signal MS51-7103-xxx 2 3 4 5 2 Actuators may be wired in parallel. All actuator black wires are connected to the transformer common and all red wires are connected to the hot lead.
MS51-7103 Series, MSx1-7203 Series 24 Vac Transformer or 20-30 Vdc 1 Line Volts Blk Com Red Hot (+DC) MS51-7103-x40 2 White/Red Typical Controllers CP-8102 TP-810X TP-8121 TP-8124 TP-8232 5 Yel/Blk Red (+20) 3 Yellow (OLP1) Blue (COM) 3 If the controller uses a full-wave power supply and does not provide isolated outputs, a separate transformer is required. TAC System 8000 controller requiring external 20 Vdc power from actuator 1 1 Provide overload protection and disconnect as required.
MS51-7103 Series, MSx1-7203 Series 24 Vac Transformer 1 or 22- 30 Vdc Line Volts Gra Com Blk Com Red (-) (+) Control Signal 4 to 20 mA 4 Feedback Signal 2 to 10 Vdc 500 1 Provide overload protection and disconnect as required. MSx1-7203 Hot (+DC) 3 (-) (+) 6 AI AO Yel/Blk Blu Grn/Yel 2 With four actuators wired to one 500 ohm resistor, a +2% shift of the control signal may be required. (Actuator input impedance is 80 k ohm.
MU-12313 MU-12313 Electronic Gear Train Economizer Actuator This actuator provides modulating operation of dampers and other equipment which require the return to normal position upon power interruption. Adjustable minimum position control 0 to 90°. Replaces Honeywell M-7415A and functionally replaces White-Rodgers 3420-4. Features: • Proportional damper economizer actuator with built-in controller. • Adjustable mixed air setpoint, throttling range, minimum positions, and travel. • Spring return.
MU-12313 Specifications (Continued) Case Glass reinforced thermoplastic (PET) cover, plated steel case. Mounting Any position. Five 9/32 in. (7.1 mm) mounting holes provided. Crank arm for actuator AM-112 included with actuator. 3/8 in. (9.5 mm) slot provides for adjustable radius from 7/8 in. (22 mm) to 3-1/8 in. (79 mm). Dimensions 5-1/2 H x 5 W x 7-9/32 D in. (140 x 127 x 185 mm). 3/8 in. (9.5 mm) shaft diameter. General Instructions Refer to F-22174. Throttling Rangesa a Degree Rotation T.
PC-1xx Series PC-1xx Series Pneumatic-Electric Pressure Switch For on-off control of electrical devices such as air compressors, fans, pilot lights, etc., by the use of a predetermined air pressure signal. Features: • One, two, and three switch models to meet a variety of applications. • One and two switch models have adjustable setpoints. • Indication scales on one and two switch units. • Agency approved. PC-110 Model Chart Model No.
PC-1xx Series Electrical Ratings. Model No. PC-110 Volts (Vac) FLA Amps LRA Amps 24 — — Non-Ind. Amps 120 13.8 82.8 208 9.6 57.6 9.6 240 8.3 49.8 8.3 277 — — 7.2 — 12 72 12 125 at 120/600 Vac 277 — — 16 Pilot Duty VA 100 650 750 120 PC-131a PC-132 PC-151 a 208 240 120 6 36 208/240 3 18 6 3 277 — — 2.6 125 at 24/277 Vac The only parts available to Uni-Line. Specifications Diaphragm Non-metallic, positioned by air pressure changes to actuate switches.
PC-301 PC-301 Two-Position Air Flow Pressure Switch This switch provides low or line voltage control of pressure for air and non-combustible gases. It controls static pressure, total pressure, or differential total pressure. Features: • High/low pressure taps. • Adjustable from 0.07 to 1 in. (1.8 to 25.4 mm) W.C. • Universal mounting. • Agency approved. Model Chart Model No. Description PC-301 Refer to Specifications. Specifications Setpoint Factory setting 0.07 in. (1.8 mm) W.C.
PC-301 Accessories Model No. AP-302 AP-305 AT-208 Description Duct static pressure sensing tip for pressure 1 in. (25.4 mm) W.C. and up. Duct static pressure sensing tip for pressure 0.01 in. (0.3 mm) W.C. and up. Duct mounting bracket for probes other than AP-302 and AP-305. Typical Applications N.C. Increase pressure Common N.O. N.O. makes on increase of pressure. Figure 1 Switch Action for PC-301 Switch. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
PF-126 PF-126 Floating Differential Pressure Switch For use with reversible electric actuated valves, actuators, or sequence controllers for control of steam, air, gas, or liquid pressure differential. Features: • Adjustable setpoint. • Usable on steam, air, gas, or liquid. • Floating action for MP-gear train actuators. Model Chart Model No. PF-126 Description Refer to Specifications. Specifications Control range 8 to 60 psi (57 to 414 kPa). Graduated scale and external adjustment screw.
PF-30x Series -30x ries Floating Pressure Air Flow Switch These switches are used with reversible electric actuators to control differential pressures, low static pressures, or air velocities in duct systems. Features: • Low static control for ±0.5 in. control unit. • Built-in arc suppression. • Liquid level control usability. • Highly reliable product. • Universal mounting. Model Chart Adjustable Null Spana Model No. Differential Pressure Setpoint Range in. (mm) of Water At Minimum Setpoint in.
PF-30x Series Accessories Model No. AP-302 AP-305 AT-208 N1-81 N1-52 N1-53 Description Duct static pressure sensing tip for pressure 1 in. (25.4 mm) W.C. and up. Duct static pressure sensing tip for pressure below 1 in. (25.4 mm) water. Duct mounting bracket for probes other than AP-302 and AP-305. Velocity pressure probe, 3 in. Velocity pressure probe, 6 in. Velocity pressure probe, 9 in. PF-30x Series 6 NC Decrease in Differential 1 Adjustable speed actuators are recommended such as MP-382 and MP-486.
PP-22x Series -22x ries Proportional Pressure Controllers For the proportional pressure control of steam, air, gases, or liquids. Features: • Usable on steam, air, and water. • Built in arc suppression. • Adjustable throttling range. • Locking feature for setpoint. Model Chart Throttling Range (psig) Model No. Control Knob Range (psig) PP-221 20 in. Hg. Vac to 10 psig PP-222 0 to 20 Factory set at Adj.
PP-22x Series Typical Applications 4 3 PP-22x 2 2 C 1 X B 2 4 1 R 3 AC Supply MP-361 6 MP-371 Blue MP-381 MP-382 Red MP-475 MP-485 MP-486 MP-2113-500 MP-2150-500 7 100 W 5 1 C - Common. 2 B - Closes on pressure rise & rotates actuator CW. 8 5 H 7 3 R - Closes on pressure drop & rotates actuator CCW. G 7 5 Make resistor and jump connection from 8 to H, on 24V actuators only. 4 1- Feedback. 6 Transformer leads on line voltage actuators.
PP-8311 Series -8311 ries Pressure Transducer This transducer converts a 3 to 15 psig (21 to 103 kPa) or a 0 to 20 psig (0 to 137 kPa) pneumatic input signal to a proportional 4 to 20 mAdc or 1 to 5 Vdc electronic output signal. Features: • 4 to 20 mAdc load capability to 625 Ω maximum. • Dual outputs for 4 to 20 mAdc and 1 to 5 Vdc. • 3 to 15 psig factory calibrated. • Does not consume any air. • Can be calibrated for 0 to 20 psig. • Requires less panel spaces than former model.
PP-8311 Series Accessories Model No. TOOL-95-1 Description Pneumatic calibration tool kit. Typical Applications Supply Voltage (see Model Chart) L2 24G L1 Hot 24H Earth Ground GND Cover removed Neutral 1 When using 0 to 20 psig input (P2 to P3), GAIN and CAL adjustments must be made.
SLC-811x Series C-811x ries Proportional Temperature Controller (Less Sensor) Electronic temperature controller for single loop control of media in ducts, tanks, and liquid lines. Features: • Dual sensor capability. • Optional reset sensor. • Direct acting, reverse acting, pin selectable. • TAC System 8000 compatible. • 100°F spans. • Reset ratios switch selectable. 18 12 24 6 30 0 36 42 ˚C 48 SLC-811x Series Model Chart Model No.
SLC-811x Series Accessories Model No. AD-8122 AD-8123 AD-8124 AT-226 TS-8201 TS-8405 TS-8422 TS-8501 Description Signal adaptor for dual outputs (two direct acting). Signal adaptor for dual outputs (one direct, one reverse acting). Signal adaptor for dual outputs (one reverse, one direct acting). Brass bulb well. Duct/immersion sensor. Averaging sensor 5 ft. (1.5 m). Averaging sensor 22 ft. (6.7 m). Outdoor air sensor.
SLC-832x, SLC-833x C-832x, C-833x Proportional Temperature Controller with Sensor Electronic temperature controller for single loop control of media in ducts, tanks, and liquid lines. Features: • Dual sensor capability. • Optional reset sensor. • Direct acting, reverse acting, pin selectable. • TAC System 8000 compatibility. • Span of 100°F. • Switch selectable reset ratios. SLC-832x Duct/Immersion SLC-833x Duct Averaging Model Chart Model No.
SLC-832x, SLC-833x Specifications Power requirements 20 Vdc (+1.0, -1.5), 13 mA. Output voltage 2 to 15 Vdc direct acting; field changeable to 15 to 2 Vdc reverse acting. Calibrated at 7.5 Vdc when dial setting matches temperature sensed by integral sensor. Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: 40 to 140°F (4 to 60°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1.
SR100 Series R100 ries TAC Erie™ Universal Control Relay The SR100 series zone control relay incorporates a double pole/double throw relay to control a circulator and a boiler operating control in a single zone hydronic heating system. Features: • Field replaceable relay. • High capacity 10 VA transformer. • Large terminal connections. • Common 24 Vac transformer terminal. • Optional auto-test function to test system operation. US Model Chart Model No Description SR100 Single zone relay.
SR100 Series Typical Applications LOW VOLTAGE THERMOSTAT 72 OPTIONAL FOR 3-WIRE THERMOSTAT C W T R T 1 G/T R/T C 5 Boiler/Burner Control GNO GNC SR100 N L1 3 4NO 4NC 2 Zone Circ. 1 5, 6NO and 6NC are Class 2 dry contact. 2 3, 4NO and 4NC are line voltage Hot 120 VAC 120 V contacts. Com Figure 1 SR100 Relay Typical Wiring.
SR100 Series T T Boiler/Burner Control ZONE 2 THERMOSTAT 72 HOT WATER TEMPERATURE CONTROLLER G/T C R/T 5 C GNO GNC W R G/T R/T SR100 N L1 3 4NO 4NC 5 GNO GNC SR100 HOT WATER Circ. N L1 3 4NO 4NC Zone 2 Circ. Hot 120 VAC Com Figure 3 SR100 Series With Domestic Hot Water Priority. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
SR201/301/601 Series SR201/301 01 Series TAC Erie™ Multi-Zone Circulator Control Relay The SR multiple-zone series control relays incorporate up to six double pole/single throw relays (SR601/601AT) providing control of up to six circulators and a boiler operating control in a multi-zone hydronic heating system. Field selectable priority for zone 1 eliminates the need for additional relays to provide domestic hot water priority. Features: • Field selectable priority zone.
SR201/301/601 Series Accessories Model No. EXP10 T155 Series T200 Series T500 Series TA-1xxx Series TC-1xx Series Description Replacement relay. Thermostats. Thermostats. Thermostats. Thermostats. Thermostats. Typical Applications Optional for 3-wire Thermostats Zone 1 T-Stat Zone 2 T-Stat Zone 3 T-Stat 72 72 72 SR301 R C T1 T1 T2 T2 K1 T3 T3 K2 K3 Bypass Enable K1 L2 CP L1 ZC X2 X1 ZR K2 K1 Pri- Priority ority C1 C1 C2 C2 C3 C3 Zone 1 Circ. Zone 2 Circ. Zone 3 Circ.
SR201/301/601 Series Zone 1 T-Stat Zone 2 T-Stat Zone 3 T-Stat 72 72 72 Optional for 3-wire Thermostats SR301 R C T1 T1 T2 T2 K1 T3 T3 K2 K3 Bypass Enable K1 L2 CP L1 ZC X2 X1 ZR K2 K1 Pri- Priority ority C1 C1 C2 C2 C3 C3 Zone 1 Circ. Zone 2 Circ. Zone 3 Circ. Com L2 120 VAC L1 High Limit Hot 120/24 Volt Transformer BURNER Figure 2 Typical Wiring SR301 - 24 VAC High Limit and Gas Valve.
SR201/301/601 Series Zone 1 T-Stat Zone 2 T-Stat Zone 3 T-Stat 72 72 72 SR301 R C T1 T1 T2 T2 K1 T3 T3 K2 K3 L8124 T T-stat Bypass Enable T ZC ZR K1 K2 K3 B1 Burner B2 L2 CP L1 ZC X2 X1 ZR Pri- Pri- C1 C1 ority ority C2 C2 C3 C3 Zone 1 Circ. Zone 2 Circ. Zone 3 Circ. C1 Circulator C2 Com L2 1 120 VAC L1 Hot 2 Figure 4 Typical Wiring SR301 - Tankless Coil Application. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
T200 Series TAC Erie™ Digital, On/Off Thermostat T200 Serie T200 series thermostats provide temperature control on a variety of heating, cooling and single stage heat pump applications. The large LCD window displays room temperature including 1/5th of a degree increments indicated by a series of up to 5 dashes. The system heat output cycles on a 1 or 2F degree field selectable differential. The cool output differential is fixed at 2F degrees.
T200 Series Specifications Inputs 20 to 32 Vac, 75 mA to 1.2 amps (power-stealing thermostat, 75 mA required at all times. 250Ω, 5 watt resistor may be needed). Power input Outputs Electrical Battery: Setpoint backup Energizer 357 or similar (battery included). 1.2 A inductive load max. Setpoint range: 50 to 86°F (10 to 35°C). Control ranges Operating differential: Heating 1 or 2 F degrees field selectable, (0.6 or 1.1 C degrees), Cooling 2 F degrees (1.1 C degrees). Material: Rigid vinyl.
T200 Series 24 VAC HEATING TRANSFORMER 24 VAC TRANSFORMER RH FACTORY INSTALLED JUMPER 120 VAC 24 VAC W 1 Y HEATING RELAY W G REVERSING VALVE B 1 Optional 250W 5 watt resistor is needed 1 120 VAC 24 VAC RC RH 2 O only if power drops below 75 milliamps. 1 HEATING RELAY COOLING RELAY 2 FAN RELAY Optional 250W 5 watt resistor is needed only if power drops below 75 milliamps. Either the B or O output will be connected to the reversing valve.
T500 Series 00 Series TAC Erie™ Non-Digital, On/Off Low/Line Voltage Thermostat/Controller The T500 series thermostats are available in four basic models for low and line voltage control of valves, relays, and fan motors in fan coil and packaged units for commercial, industrial, and residential installations. Features: • Set point dial stop (optional). • Bellows type sensor for constant and close temperature differential. • System and fan switches. • Fahrenheit and celsius models.
T500 Series Accessories Model No. WP500 680-243 PIN 500 Description 5-1/2 x 5-1/2” (140 x 140 mm) adapter plate. Auto seasonal changeover switch. Dial stop pin. Typical Applications Figure 1 T511/T511F, 2-Pipe Heating & Cooling With Changeover Switch. H M L H ON OFF L2 OR NEUTRAL L1 (HOT) 1234 FAN MOTOR 5678 LOW MED HI VALVE If heating is desired, replace the cooling valve with a heating valve and connect input to terminal 5 Figure 2 T511/T511F, 2-Pipe Cooling. 224 © Copyright 2006 TAC.
T500 Series H M L C O H H L2 OR NEUTRAL L1 (HOT) 1234 FAN MOTOR LOW MED HI 5678 COOLING VALVE HEATING VALVE Figure 3 T513/T513F, 4-Pipe Heating/Cooling. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
TA-155 Series, TB-155 Series TA-155 Series, T 155 Serie TAC Erie™ Non-Digital, Electronic On/Off Thermostat/Controller The T155 series thermostat provides on/off control for low voltage and line voltage control of valves, relays and fan motors. Applications include twopipe and four-pipe fan coil units, air handling units, and heating and cooling applications. Features: • Manual or automatic changeover models. • Line voltage 3-speed fan control.
TA-155 Series, TB-155 Series Specifications Inputs Power input 24 to 277 Vac @ 50/60 Hz, full wave device. Power consumption 0.88 watts at maximum. Power: Up to 14 AWG wire. Connections Control: Up to 14 AWG wire. Outputs Thermostatic heat/cool output switch ratings: 10 VA @ 24 Vac, Pilot duty 20 VA @ 120 - 277 Vac. Full wave device. Electrical Operating differential: 1 F degree (0.6 C degree). Control ranges Changeover deadband (TB155 only): 4 F degrees (2.2 C degrees).
TA-155 Series, TB-155 Series HEATING VALVE 680-243 CHANGEOVER THERMOSTAT PIPE MOUNTED TA-155-17 TB3 1 2 3 COOLING VALVE BLK HEATING/ COOLING VALVE WHT BLU L2 OR NEUTRAL TA-155-10 FAN RELAY TB3 1 2 3 TB2 FAN RELAY TB1 1 2 3 4 5 4 3 2 1 L1 (HOT) HI MED LOW FAN L2 OR NEUTRAL TB2 TB1 1 2 3 4 5 4 3 2 1 L1 (HOT) HI MED LOW FAN Figure 4 Typical 2-Pipe Heating/Cooling Fan Runs with System Switch On or Off.
TA-158 Series, TB-158 Series -158 ries, TB8 Series TAC Erie™ Digital, 3-Wire Floating Thermostat/Controller The T158 series microprocessor based thermostat/controller with digital display provides 3-wire floating, on/off control, or a combination of 3-wire floating and on/off control. This series controls a variety of two-pipe and four-pipe fan coil units, air handling units, and various heating and cooling applications.
TA-158 Series, TB-158 Series Outputs. Fan Switch Rating, Terminals 1 - 4 Control Outputs Inductive Voltage Resistive Amps FLA Pilot Duty Terminals 7, 10, 11, 12, 13, and 14 10 VA LRA 24 N/A N/A N/A 24 VA 120 5.8 34.8 6.0 125 VA 240 2.9 17.4 5.0 125 VA 277 2.4 14.4 4.2 125 VA N/A Specifications Inputs Power input 20 to 28 Vac, nominal 24 VA. Full wave device. Power consumption 25 mA maximum at 24 Vac. Connections Power: Up to 14 AWG wire. Control: Up to 14 AWG wire.
TA-158 Series, TB-158 Series Typical Applications L1 (HOT) 1 2 3 4 1 LO MED FAN LINE VOLTAGE CONNECTIONS L2 OR NEUTRAL HI L1 (HOT) 2 LO 3 MED 4 HI L2 OR NEUTRAL FAN 5 5 6 7 10 11 12 13 14 15 16 17 6 24 VAC XFMR SETBACK INPUT OPEN MAIN OUTPUT OPEN 7 SETBACK SWITCH 6 COM 7 MAIN 10 CLOSE SECONDARY COM OUTPUT CLOSE LOW VOLTAGE CONNECTIONS OUTSIDE AIR DAMPER 11 SECONDARY 12 2ND HEAT OUTPUT 13 OPTIONAL REMOTE TEMP SENSOR 15 16 OPTIONAL PIPE/AIR CHANGEOVER SENSOR OPTIONAL R
TA-158 Series, TB-158 Series T158 Terminal Function and Model Table.
TA-167 Series, TB-167 Series A-167 ries, TB7 Series TAC Erie™ Non-Digital, Proportional Thermostat/Controller The T167 series microprocessor based thermostat/controller provides 0-10 Vdc control. This series controls a variety of two-pipe and fourpipe fan coil units, air handling units, unitary equipment, and various heating and cooling applications. Heat Off Cool Features: • 0-10 Vdc heat and/or cool outputs. • Fahrenheit standard. Optional Celsius setpoint dial.
TA-167 Series, TB-167 Series Accessories Model No. 65-821 680-243-5 680-243-6 65170 65345 65410 65860 68671 Description. Solid blank cover. Changeover switch with clamp and 36 in. leads. Changeover switch with conduit connector and 36 in. leads. Warmer/cooler set point dial. 4-3/4” x 4-3/4” adapter plate. Celsius set point dial, 10 to 34°C. Set point dial stop kit. Remote sensor, 60” leads 10k Ω @ 77°F (25°C).
TA-167 Series, TB-167 Series 100% % of Output 0 to 10 Vdc 50% 0% -3F° -2F° -1F° Set Point +1F° +2F° +3F° Auto Heat Auto Cool Proportional Output Signal Operation: At 3 F degrees from setpoint either the heat or cool output signal goes to 10 Vdc, based on ambient temperature being above or below setpoint. As the ambient temperature starts to move closer to setpoint the output signal remains at 10 Vdc until ambient temperature is within 2 F degrees of setpoint.
TA-168 Series TA-168 Series TAC Erie™ Digital, Proportional Thermostat/Controller The T168 series microprocessor based thermostat/controller provides 0-10 Vdc or 4-20 mA control. This series controls variety of two-pipe and four-pipe fan coil units, air handling units, and various heating and cooling applications. The microprocessor combines a proportional plus intergral control algorithm with advanced adaptive logic.
TA-168 Series Outputs. Fan Switch Rating, Terminals 1 - 4 Control Output Inductive Voltage Resistive Amps FLA Pilot Duty Terminals 7, 12, 13, and 14 10 VA LRA 24 N/A N/A N/A 24 VA 120 5.8 34.8 6.0 125 VA 240 2.9 17.4 5.0 125 VA 277 2.4 14.4 4.2 125 VA N/A Specifications Inputs Power input 20 to 28 Vac, nominal 24 Vac. Full wave device. Power Consumption 25 mA maximum at 24 Vac. Outputs Electrical Control signals Demand and aux. heat: 10 VA @ 24 Vac.
TA-168 Series Typical Applications 3 SPEED FAN CONTROL 1 24 - 277 VAC VOLTAGE CONNECTION 2 3 4 2 5 1 6 5 7 L1 (Hot) MED FAN 11 Terminals 12, 13, and 14 are connected to the devices respective input, terminal 5 to the devices respective common. 3 For demand fan control, power a 24V fan relay using Terminal 12 as the output. Output limited 10 VA. 4 Can be used for second stage 24 Vac heat output or single stage 24 Vac electric heat output by setting dipswitch #2.
TA-170 Series, TB-170 Series A-170 ries, TB0 Series TAC Erie™ Digital, Proportional Thermostat/Controller The T170 series microprocessor based stand-alone controller supplies line or low voltage relay control of heat, cool, outside air and fan. Designed for 1 heat, 1 cool, on/off vent damper and fan speed control applications. Features: • 1H/1C and on-off vent damper. • Fan swtich auto/on/off. • Fan control manual, staged, or auto. • 24-277 Vac power. • Large backlit ADA compliant display/buttons.
TA-170 Series, TB-170 Series Specifications Inputs Power input 24 to 277 Vac @ 50/60 Hz ±10%. Power Consumption 45 mA. Connections Five inch 18 ga pigtails. Outputs Relays H/C/Damper relays and up to three fan relays based on model. See switch rating table for capacity. Deadband 3 F degrees (1.6 C degrees ). Control Proportional plus integral. Set Point Range Housing 50 to 90°F (10 to 32°C). Vinyl plastic white. Environment Ambient temperature limits 130°F (-34°C) maximum.
TA-110X Series, TA-1501 Series A-110X ries, A-1501 ries Two-Position Electric Room Thermostat, Heating For on-off control of electric heaters, actuators, relays, unit heater motors, high input motor starter coils, and motor pull-up coils. 90 80 70 60 50 Features: • Separate units for °C and °F. • 2F degrees differential. • Dial stop pins to limit dial range. • Lock cover screw kits available. • Agency approval. • Switch bases AT-602 and AT-603 available for custom applications.
TA-110X Series, TA-1501 Series Maximum Electrical Ratings. Full Load Amps Model No. TA-1101 Series TA-1102 Series Locked Rotor Amps Non-Inductive Amps Pilot Duty VA 24/120 Vac 240 Vac 24/120 Vac 240 Vac 120 Vac 240 Vac 277 Vac 24 Vac 120/240 Vac 7.2 3.6 44 22 7.5 7.
TA-110X Series, TA-1501 Series Typical Applications R Temp. C Drop Common 10F Degree Night Depression R makes ON Resistor (See Options) temp. drop. -602 only. 5 4 Figure 3 TA-110x Switch Action and Terminal Identification. TA-1501 Temp. Drop 1 2 Brown Black/Yellow Orange L2 L1 Load 1 SPST Action Contacts Close on Temperature Drop. 2 Adjustable H.A. Resistor. Figure 4 TA-1501 Switch Action and Lead Identification. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
TA-3432, TA-3433, TA-3434, TA-3441 TA-3432 TA-3433 TA-3434 TA-3441 High/Low Temperature Thermostats For line voltage on-off control of media temperatures in ducts, tanks, liquid lines, pipes, etc. Features: • Dual marked °F and °C scale. • 5 and 10F degrees differential. • Locking screw standard. • Agency approval. • Manual reset standard. Model Chart Model No.
TA-3432, TA-3433, TA-3434, TA-3441 Typical Applications B R C Common Temperature Drop TA-343x opens circuit on rise of tempererature above set point. TA-3441 opens circuit on drop of tempererature below set point. Figure 1 Switch Action and Terminal Identification. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
TC-97 Series, TC-98 Series TC-97 Series, TC-98 Series Single Stage, Multi-Stage, and Heat Pump Digital Thermostats Designed for both commercial and residential needs, the TC97 and TC98 series thermostats handle single stage, multi-stage, and heat pump applications. They also provide short cycle protection during normal operation. Features: • Slim, contemporary design. • Automatic changeover. • Memory retention (battery not required). • Easy-to-read LCD display with informative icons.
TC-97 Series, TC-98 Series Specifications Control Range Heating 38 to 88°F (5 to 30°C). Cooling 60 to 108°F (16 to 40°C). Minimum Deadband 2 F degrees (1 C degree) between heating and cooling. Shipping and Storage Temperature -40 to 124°F (-40 to 48°C). Operating Temperature 28 to 124°F (0 to 48°C). Humidity 5 to 85% RH, non-condensing. Wiring Terminals Terminal block in wall plate. AWG #14 maximum. Power Supply 24 Vac nominal 20 to 30 Vac, 50/60 Hz.
TC-1xx Series, TC-11xx Series, TF-1111 Series Two-Position Electric Duplex Room Thermostats TC-1xx Series, TC-11xx Series, TF-1111 Series These thermostats provide on-off control of heating/cooling systems. 2 Features: • Separate units for °C and °F. • All units except TC-114. - Parallel heat and/or cooling anticipation capability. - Dial stop pins to limit range. - Lock cover screw/sets available. - Agency approval. - Switch bases AT-602 and AT-603 available for custom applications. • TC-18x and TC-19x.
TC-1xx Series, TC-11xx Series, TF-1111 Series Model Chart (Continued) Model No. Application Setpoint Dial Range TC-1101 55 to 85°F 2 (1.1) TC-1101-116 13 to 29°C 1 C° (1.8 F°) TC-1101-500a TC-1102 TC-1102-116 TC-1102-500 a TC-1102-602b TC-1103 Low or line voltage on-off control of fan coils, fans, motor starters, contactors, twoposition electric actuators.
TC-1xx Series, TC-11xx Series, TF-1111 Series Specifications Thermostats mounted on concrete walls or surfaces that change temperature slowly, have reduced response to changes in air temperature. Response is further delayed by guards that restrict air flow to the thermostat. Anticipators are required (parallel for cooling, series or parallel for heating) for any of these conditions and in spaces intended for continuous occupancy; i.e., hotel guest rooms and offices.
TC-1xx Series, TC-11xx Series, TF-1111 Series Electrical Ratings (Continued). Fan Switch Model No. Thermostat Contacts Volts (AC) Full Load Amps Locked Amps Volts (AC) Full Load Amps Locked Rotor Amps Pilot Duty (VA) ⎯ ⎯ ⎯ 24/120/240 Heat, 4.4/4.4/2.2 Cool, 3.0/3.0/1.5 Heat 26.4/26.4/13.2 Cool, 18/18/9 40/210/210 Non-Inductive Amps TC-1191 TC-1191-116 TC-1191-500 TC-1191-602 — TC-1191-770 TF-1111 TF-1111-116 — — — 24 0.16 at 24 Vac — — TF-1111-770 Accessories Model No.
TC-1xx Series, TC-11xx Series, TF-1111 Series Cooling Anticipator 1 C B Cooling (Red) Temp. Drop 1 Thermostat. Brown makes ON temp. drop. Heating (Brown) 2 Fan switch shown in off position. R Hi High (Yellow) 2 Med To Fan Motor Medium (Black) Off Low (Blue) Low L1 (Orange) Ground (Green) Figure 3 TC-18x Series Switch Action and Terminal Identification. Red (Orange) L1 Brown Temp. Drop Black/Yellow 1 Brown makes ON temp. drop. 1 Heat Anticipation Black/Yellow 10 F˚ (14.
TC-200 Series Single Bulb Thermostats -200 ries These units are used for on-off control of media temperature in ducts, tanks, etc. Features: • Mechanism enclosed in rugged die cast case with metal cover. • Large coded terminals. • Liquid-filled thermal element actuates one snap-acting SPDT per stage. • Setpoint adjustment knob is clearly marked and has recessed locking screw. • Copper thermal element is suitable for either immersion or duct mounting.
TC-200 Series Accessories Model No. AT-201 AT-203 AT-208 AT-211 Description Copper bulb well (order separately). Stainless steel bulb well (order separately). Bulb duct mounting kit (order separately). Outside bulb shield (order separately). Typical Applications B C R Temp. drop Figure 1 Typical of TC-202, Single Stage. High B Low C B C Temp. drop R First stage Second stage R Temp. drop Heat Cool R High R Low B High B Low R makes on temp.
TC-1151 Series, TC-1161 Series -1151 ries, -1161 ries Two-Position Electric Duplex Room Thermostats These thermostats provide temperature control for on-off applications requiring two individually adjustable thermostats under one cover. Typical applications include, day/night control, night and warm-up control, summer/winter and other energy conserving systems. Features: • Fixed switch differential. • Dial stop pins to limit dial range. • Lock cover screw kits available. • Agency approval.
TC-1151 Series, TC-1161 Series -400 -401 -402 -403 -404 Figure 2 Options for Quantities of 24 or more of each part number. Add dash number to base part number for desired option. Specifications Setpoint dial range See Description Model Chart. Sensing element Bimetal. Switching: 2 F degrees (1.1 C degrees). Differential Staging: Adjustable 2 to 10 F degrees (1.1 to 5.6 C degrees), factory adjusted between 2 and 4 F degrees.
TC-1151 Series, TC-1161 Series Typical Applications B1 Temp. Drop R1 Temp. Drop B R C 1st Stage Heat (R) 2nd Stage Cool (B) C1 2nd Stage Heat (R1) 1st Stage Cool (B1) 7 1 4 8 Optional Heat Anticipation 10 2 Optional Night Depression Note: Thermostat is designed for either heat or cool applications, not heat and cool. Optional Heat Anticipation Figure 3 TC-1151 Series Switch Action and Lead Identification.
TC-2931, TC-2942 TC-2931 TC-2942 Strap-on Changeover Thermostat This thermostat provides summer-winter changeover in hydronic heating-cooling systems. Features: • Fixed control point. No adjustment required. TC-2942 Enclosed Type TC-2931 Open Type Model Chart Switch Ratings (AC only) Model No. TC-2931 Strap-on TC-2942 Strap-on encloseda a Vac FLA (amps) LRA (amps) Pilot Duty (VA) Blue-Yellow Close on Rise °F (°C) 120 240 5.8 2.9 34.8 17.
TC-2974 Strap-on Thermostat 100 80 120 140 1 6 0 0 18 This thermostat provides hot water unit heater control and summer-winter changeover. May be used as either an open high control or an open low control. 60 C-2974 200 Features: • Available lock cover and concealed setpoint kit. • Adjustable setpoint. Model Chart Model No. Voltage (Vac) Full Load Amps Locked Rotor Amps 120 9.8 58.8 240 8 48.
TC-4100 Series, TC-4200 Series TC-4100 Series, TC-4200 Series Two-Position, Single & Dual Bulb Thermostats For on-off control of media temperature in ducts, tanks, liquid lines, etc. Features: • Heating or cooling applications. • Adjustable differential on all except TC-4166. • 1/2 in. conduit connections. • Agency approval. • Duct/immersion/outside mounting kits available. • Concealed adjustment plate. Typical Single Bulb Typical Dual Bulb Typical Return Air Bulb Model Chart Model No.
TC-4100 Series, TC-4200 Series Differential, Setpoint Adjustment, and Safe Bulb Temperature Ranges.
TC-4100 Series, TC-4200 Series Electrical Ratings (Except TC-4115a). Switch Rating (50/60 Hz) Full Load Amps 24 V 120 V 240 V 16 16 8.0 Locked Rotor Amps 96 96 48.0 Pilot Duty VA 60 360 360 Single Stage 22 22 22 Two Stage 16 16 8.0 Non-Inductive Amps (Resistive) a TC-4115 for TAC System 8000 and applications requiring less than one (1) amp. Electrical Rating: 1.0 amp at 24 Vac; 0.25 amp at 24 Vdc. Accessories Model No.
TC-5231 Series, TC-5232, TC-5241 Series Low Temperature Thermostats The TC-5231, TC-5232, and TC-5241 low temperature thermostats are used to control temperature in air conditioning or refrigeration systems. TC-5231 Series, TC-5232, TC-5241 Series Features: • 20 ft. (6.1 m) element senses temperature over a large area. Control responds to coldest one-foot section of the sendor. • Adjustable setpoint with 5 F degrees (3 C degrees) fixed differential. • SPST, SPDT and DPST versions.
TC-5231 Series, TC-5232, TC-5241 Series DC Ratings for TX-5232 Only. a Volts FLAa LRA a NIA a PD VA a 120 4.6 240 2.3 46 3 57.5 23 0.5 600 — 57.5 — — 57.5 FLA — Full Load Amps. LRA — Locked Rotor Amps. NIA — Non-Inductive Amps. PDVA — Pilot Duty VA. Specifications Setpoint dial range Dual marked 35 to 60°F (1.7 to 15.5°C). TC-5242: 15 to 55°F (-9.4 to 12.8°C). Sensing element Vapor pressure type, copper construction.
TC-5231 Series, TC-5232, TC-5241 Series Fan Motor AC Supply L 1 L T T Indication Circuit 1 Terminals L-T open on temperature drop. Figure 2 TC-5232 Switch Action and Terminal Identification. Fan Motor AC Supply Line 2 L L 1 T T Line 1 Indication Circuit M2 Main M1 Aux 1 Action on temperature drop. Figure 3 TC-5242 Switch Action and Terminal Idenfication Manual Reset. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
THC-2, THC-3, THCR-4 THC-2, THC-3, THCR-4 Two-Position Enthalpy Controller This controller provides on-off (two-position) low voltage control of the amount of air brought into the cooling system with respect to the “total heat” (enthalpy) of the outside air. THC-3 and THCR-4 controllers replace Honeywell H250A series. DC Features: • Direct acting and reverse acting applications from all units. • Long life nylon element. • 1/2 in. conduit units available. • Competitive replacement units listed.
THC-2, THC-3, THCR-4 Specifications (Continued) Connections THC-2, THCR-4 Three 6 in. (150 mm) color coded leads. THC-3 Three 1/4 in. male quick connect (spade lug) terminals. Cover All metal; THC-2 and THCR-4 with 1/2 in. conduit opening. Mounting In any position where it is exposed to freely circulating outdoor air. Dimensions THC-2, THCR-4 4-3/4 H x 6-1/2 W x 3-1/2 D in. (121 x 165 x 89 mm). THC-3 3-1/2 H x 5-1/8 W x 1-1/8 D in. (89 x 130 x 29 mm). General Instructions Refer to F-20009.
TP-1011, TP-1031 Series TP-1011 TP-1031 Series Electric Proportional Room Thermostats For proportional temperature control of electric actuated valves, damper actuators, and sequence controllers. Features: • Proportional control of MP actuators. • Night set back (TP-1011). • Concealed adjustments to eliminate tampering optional. • Accepts actuator feedback for precise control. • Temperature indication. • Direct actuator control without interface devices.
TP-1011, TP-1031 Series Typical Applications 1 5 6 7 Blue 8 Red 1 4 1 4 5 2 2 TP-10X1 R B Make 100 ohm resistor and jumper connections on 24 V actuators only. 2 Transformer leads on line voltage actuators only. 3 Marked L1 and L2 on line voltage actuators. Built-in transformer required. R Closes on temperature drop (rise for TP-1031 and rotates actuator CCW. B Closes on temperature rise (drop for TP-1031) and rotates actuator CW.
TP-8101, TP-8102, TP-8121, TP-8124 TP-8101, TP-8102, TP-8121, TP-8124 Single/Dual Output Room Temperature Controllers These temperature controllers are used in heating and air conditioning systems. Features: • Dual output adapters for TP-8101 and TP-8102. • TP-8124 meets ASHRA 90-75 DOE requirements. • Heating and cooling cannot operate simultaneously. • Heating/cooling deadband obtained by adjustable dual setpoints and throttling range. • Concealed adjustments to eliminate occupant tampering.
TP-8101, TP-8102, TP-8121, TP-8124 TP-810x†† TP-810x-116†† TP-812x†† TP-812x-116†† with Blank Cover Only insert insert Figure 1 Standard Cover with Inserts. F TP-810x-399 C TP-810x-398 Figure 2 Blank Cover Only. -400 -410 -403†† -413†† -404†† -414†† ††5/64 in. Allen screw used to secure cover. Figure 3 Options for Quantities of 24 or More of Each Part Number. Specifications Construction Self-contained room controller with a 1000 Ω Balco sensing element with single or dual output(s).
TP-8101, TP-8102, TP-8121, TP-8124 Typical Applications TP-810x Optional Remote Sensor Except TS-8601 +20 (Red) IV1 (Yellow) COM (Blue) To Controlled Device 3 3 1 2 4 7 5 1 Clip out internal sensor if remote sensor is used. 8 3 2 4 to 5 = Direct Acting. 3 4 to 3 = Optional Reverse Acting. 1 1K Ω 4 For reverse acting only add jumper 1 to 6, blue to 7, and cut jumpers.
TP-8101, TP-8102, TP-8121, TP-8124 Controlled device to max. of 5 additional (Yellow) IVdevices with filtered (Blue) COM regulated or unregulated power supplies. 1 Red Yellow TP-8124 OP2 +20 Blue MP-52xx Series Actuator (cooling) OP1 COM Red Yellow Blue MP-52xx Series Actuator (heating) Controlled device to 1 (Yellow) IV- max. of 5 additional devices with filtered (Blue) COM regulated or unregulated power supplies. 1 Tape off if red lead. Figure 6 TP-8124 Typical Wiring with Two MP-52xx Actuators.
TP-8232, TP-8232-xxx Series TP-8232 TP-8232 xx Serie Room/Discharge Low Limit Temperature Controller These electronic room and low limit supply air temperature controllers are used in heating and air conditioning systems. Features: • Low cost replacement for unit vent packages. • TAC System 8000 compatible for control functions. • Individual supply air setpoint with concealed adjustments eliminate occupant tampering. • Day/night input capability. • Remote setpoint input.
TP-8232, TP-8232-xxx Series Accessories Model No. AD-8969-201 AT-101 AT-104 AT-504 AT-505 AT-546 AT-1103 AT-1104 AT-1155 AT-1165 AT-8122 AT-8155 AT-8158 TS-8131 TS-8201 TS-8261 TS-8405 TS-8422 TOOL-82 TOOL-201 Description Offset resistor. Lock cover kit. Dial stop pins. Plaster hole cover kit (small). Surface mounting base. Auxiliary mounting plate. Wire guard. Cast aluminum guard. Plastic guard, 6-1/4 H x 5-1/2 W x 3-1/4 D in. Plastic guard, 8 H x 5-1/2 W x 3-1/2 D in.
TS-29x Series TS-29x Series Dial Thermometers Dial thermometers for continuous visual indication of temperature in ducts, pipes and tanks. 50 75 50 75 90 11 0 11 0 0 Features: • Large dial readout. • Corrosion resistant. • Universal mounting availability. 90 30 30 0 12 0 12 0 -40 -40 13 0 13 0 14 0 14 0 Model Chart Model No.
TS-5191 Series -5191 ries Adjustable Wall Sensor This sensor provides electronic sensing of room temperature through a wall mounted device. It is designed for use with the CP-5341 Fan Speed Controller. Features: • Remote setpoint and control of CP-5341. • Available with lock cover screw kits. • Dial stop pins limit dial range. Model Chart Model No. TS-5191 Description Refer to Specifications. Specifications Sensing element Thermistor.
TS-5xxx, TS-8xxx Series TS-5xxx, T 8xxx Serie Room Sensor Platinum Balco and Thermistor Electronic Room Sensors for Wall Mount Locations. Features: • High accuracy. • Wide choice of styles. • Industry standard elements. TS-8111 TS-8111-116 TS-81011 TS-57011 TS-57011-850 TS-58011 TS-81011 TS-5711 TS-5711-850 TS-5811 TS-8101 TS-81031 TS-57031 TS-57031-850 TS-58031 TS-81031 Model Chart Model No.
TS-5xxx, TS-8xxx Series Model Chart (Continued) Model No. TS-5811 TS-58011 TS-58011-770 Sensor Type 1K Ω Thin Film Platinum @ 32°F (0°C) Max. Error Over 100°F (55.6°C) Span Temperature Coefficient of Resistance ± 1.08°F (0.6°C) 2.12 Ω Per °Fa (3.85°C) Operating Range F-23405 F-22932 F-23770 TS-8101 TS-81011 TS-81031 F-22633 1K Ω Balco @ 70°F (21°C) TS-81031-770 TS-8111* TS-8111-116* Refer to Complete Applications 40 to 140°F (4 to 60°C) ± 0.1% 2.2 Ω Per °F (0.
TS-5xxx, TS-8xxx Series Specifications Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating 40 to 140°F (4 to 60°C). Humdity 5 to 95% RH non-condensing. Locations NEMA Type 1. Connections Coded screw terminals or wire leads. Cover TS-5811, TS-5711, TS-5711-850, Beige plastic. TS-81x1 TS-58011, TS-57011, TS-57011-850, TS-81011 Shadow white plastic. TS-58031, TS-57031, TS-57031-850, TS-81031 Grey plastic.
TS-5xxx, TS-8xxx Series Typical Applications TS-57xx TS-58xx TS-810xx Brown 1 Brown 1 To Energy Management Sensor Input 1 TS-5811, TS-810xx screw terminals 7 & 8. TS-58011 screw terminals 1 & 2. Figure 1 Typical Wiring Diagram for TS-5700, TS-5800, and TS-810xx Series Sensors. TS-5700-850 Brown 11k 0.1% 10k Thermistor Brown To Building Automation System Controller Input Figure 2 Typical Wiring Diagram for TS-5700-850 Series Sensors.
TS-5700 Series, TS-5700-850 Series TS-5700 Series, TS-5700 50 Serie Remote Thermistor Temperature Sensors Electronic thermistor sensing of temperature at remote room locations, ducts, liquid lines, tanks, outdoor air, etc. for use with microprocessor-based energy management systems. Features: • High accuracy. • Low drift. • Wide choice of styles. • TS-57xx-85x units have shunt resistor included. • Duct/immersion models. • Outdoor air models.
TS-5700 Series, TS-5700-850 Series Models with 11K Ohm Shunt Resistor. Dimensions in. (mm) Model No. Description Mounting Connection Wiring Connections Element Dia. x L Wiring Enclosure TS-5721-850 Duct/ immersiona Plate 1/4 in. NPT a 1/4 x 8 (6 x 203) TS-5721-851 TS-5722-851 Immersionb 1/4 in. NPT nut b 1/4 x 4 (6 x 102) TS-5721-853 TS-5722-853 Immersion 1/4 in.
TS-5700 Series, TS-5700-850 Series Ambient Temperature Limits °F (°C).
TS-5700 Series, TS-5700-850 Series Typical Applications TS-57xx-xxx 1 TS-5771 has 1/4" spade lugs. Brown 1 Brown 1 To Energy Management Sensor Input Figure 1 TS-57xx Series Sensor Connections. TS-57xx-85x Brown 1 11kΩ 0.1% 10kΩ Thermistor Brown 1 Utilized Characterized Inputs 1 TS-5771-854 wires have 1/4" spade lugs. Figure 2 TS-57xx-85x Series with 11K Shunt Sensor Connections. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
TS-5800 Series TS-5800 Series Remote Platinum Temperature Sensors These electronic devices provide remote temperature sensing at sites such as room locations, ducts, liquid lines, tanks, outdoor air, and others. Features: • DIN class 43760 platinum elements. • ±0.12% error at 32°F (0°C). • Pure metal providing long term stability. • Universally accepted measured technology. • Extremely linear capability. TS-5871 TS-5821-101 TS-5821 TS-5851 TS-5821-110 Model Chart Model No.
TS-5800 Series Temperature vs. Resistance Nominal Resistance Values in Ω Temperature °F (°C) TS-5821, TS-5821-101, TS-5821-110, TS-5851, TS-5871 -40 (-40) 842.7 -22 (-30) 882.2 - 4 (-20) 921.6 14 (-10) 960.9 32 (0) 1000 50 (10) 1039 68 (20) 1077.9 77 (25) 1097.3 86 (30) 1116.7 104 (40) 1155.4 122 (50) 1194 140 (60) 1232.4 158 (70) 1270.7 176 (80) 1308.9 194 (90) 1347 212 (100) 1385 230 (110) 1422.9 248 (120) 1460.6 Accessories Model No.
TS-8000 Series TS-8000 Series Remote Balco Temperature Sensors These temperature sensors provide electronic sensing of temperature at remote room locations, ducts, plenum chambers, liquid lines, tanks, outdoor air, etc. Features: • Accuracy of ±0.1% on all but averaging elements and high temperature. • TAC System 8000 compatibility. • Usable over wide temperature range. • Meets all system applications requirements.
TS-8000 Series Specifications Sensing element 1000 Ω ±1% at 70°F (20°C). Balco resistance TS-8405, TS-8422 ±1% at 70°F (20°C). Changes 2.2 Ω per 1°F (0.5°C) at 70°F (21°C). TS-8204 only 1657 Ω ±0.1% at 300°F (149°C); changes 2.5 Ω per 1°F (0.5°C) at 300°F (149°C). General Instructions Refer to F-22668, F-22575. Ambient Temperature Limits °F (°C).
TS-8811, TS-8811-116 TS-8811 TS-8811 16 Room Temperature Sensor, Remote Setpoint Electronic sensing of room temperature at wall locations for use with Energy Management Systems (EMS) using Balco inputs. 90 80 70 60 50 Features: • EMS adaptable. • TAC System 8000 compatible. • High accuracy 0.1% sensing element. • Dial stop pins to limit dial range. • Lock cover screw kit available. Model Chart Model No. TS-8811 TS-8811-116 Description Refer to Specifications.
TS-8811, TS-8811-116 Specifications Sensing element Temperature sensitive Balco element. 1000 Ω ±0.1% at 70°F (21°C); changes 2.2 Ω per 1°F (0.5°C) at 70°F (21°C). Remote setpoint dial range 55 to 85°F or 13 to 29°C, with resistance change equal to sensor resistance change. Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: 40 to 140°F (4 to 60°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1. Connections Coded screw terminals.
TSMN-57011-xxx, TSMN-58011, TSMN-81011 Electronic Room Temperature Sensor TSMN-570 -xxx, TSMN-580 , TSMN-810 The Electronic Room Temperature Sensor is a resistance-temperature device (RTD) that provides electronic sensing of room temperature at wall locations. Features: • Available in four models: one containing a Balco sensor, one with a platinum sensor, one with a thermistor sensor, and one with a thermistor that includes an 11K shunt resistor. • Contemporary, low-profile packaging.
TSMN-57011-xxx, TSMN-58011, TSMN-81011 Specifications Sensing element Refer to Model chart. Environment Ambient temperature limits Shipping and storage: -40 to 160°F (-40 to 71°C). Operating: Refer to Model Chart. Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1. Mounting Direct-wall, 2 x 4 electrical box, 1/4 DIN, and surface box. Dimensions 4-3/4 H x 3-1/16 W x 13/16 D in. (121 x 78 x 21 mm). Agency Listing UL Accessories Model No.
TSP-84xxx Series Room 4 to 20 mAdc Temperature Transmitters with Platinum Sensors These transmitters use platinum electronic sensors to control room temperature from a wall location. The sensed temperature is converted to a rapid response 4 to 20 mAdc output signal for microprocessor-based energy management systems. Features: • Two wire 4 to 20 mA current loop. • Adaptability to TAC System 8000 controllers. • Class A DIN platinum high accuracy elements • Low electrical noise transmission.
TSP-84xxx Series Specifications (Continued) Environment Ambient temperature limits Shipping and storage: -40 to 140°F (-40 to 60°C). Operating: 50 to 100°F (10 to 38°C). Humidity 5 to 95% RH, non-condensing. Locations NEMA Type 1. Connections Coded screw terminals. Cover Plastic, no thermometer. Mounting Vertical, wall; TSP-84252 and TSP-85251 plenum rated. Dimensions TSP-84152 4-3/8 H x 2-3/4 W x 1-5/8 D in. (111 x 70 x 43 mm). TSP-84252 4-13/16 H x 3-1/4 W x 1-31/64 D in.
TSP-84x04, TSP-84x5x, TSP-85x03, & TSP-85x5x Series TSP-84x0 TSP-84x5 TSP-85x0 & TSP85x5x Series Remote 4 to 20 mAdc Temperature Transmitters These remote, electronic temperature transmitters with integral sensors accurately measure and transmit temperature readings to the input of an Energy Management System (EMS). Features: • Two wire 4 to 20 mA current loop. • Adaptable to TAC System 8000 controllers.
TSP-84x04, TSP-84x5x, TSP-85x03, & TSP-85x5x Series Specifications Construction Self-contained temperature transmitter employing a platinum sensing element, 1000 Ω (±0.1%) at 32°F (0°C). Duct averaging models TSP-84704, TSP-84804, TSP-85703 and TSP-85803 employ Balco sensing element, 1000 Ω ±1.0% at 70°F (21°C). All models are housed in a sturdy plastic enclosure. Output signal Variable 4 to 20 mAdc for linear signal.
VER-HD Series, VER-HO Series Electronic Humidity and Humidity/Temperature Transmitters Electronic humidity transmitters VER-HD are used for duct applications requiring humidity and/or temperature indication and/or humidity control. Electronic humidity transmitters VER-HO are used for outside air applications requiring humidity and/or temperature indication and/or control. Features: • Microprocessor profile sensor with on-board nonvolatile memory. • Accuracy ± 2 or 3% RH models.
VER-HD Series, VER-HO Series Specifications Sensing element RH sensing element Thin-film capacitive, digitally profiled. Temperature element 10K thermistor with 11K shunt or 1K platinum. 385 1000 ohms @0°C. Accuracy RH ± 2% or ± 3% at 10 to 90%. Stability ± 1% at 68°F for two years. Operating range 0 to 100% RH. Temperature coefficient 0.1% RH below 25°C, -0.1% RH above 25°C. Inputs 4 to 20 mA Two-wire 12 to 24 Vdc 30 mA. Minimum 750 ohm max loop resistance.
VER-HD Series, VER-HO Series + Blue – Blue + 24 Vdc Power Supply – – RH Transmitter + Orange Analog Input Orange Controller 1 1 Optional temperature sensor. Note: 4-20 mA models humidity and temperature are not polarity sensitive. 0-5/0-10 RH transmitter models must observe polarity. Figure 2 Typical Wiring for 4 to 20 mA External 12 to 24 Vdc. 24 Vdc L1 L2 + Controller + Blue – 4-20 mA loop 750 ohm max – Blue RH Transmitter COM 1 Optional temperature sensor.
VER-HW Series R-HW ries Electronic Humidity and Combination Humidity Transmitters/Temperature Sensors VER-HxW room unit electronic humidity transmitters are used in applications requiring humidity and temperature indication and/or control. Features: • Microprocessor profile sensor with on-board nonvolatile memory. • Accuracy ± 2 or 3% RH models. • Multi-point digital calibration. • Field selectable 4 to 20 mA or 0 to 5/0 to 10 Vdc. • Field replaceable RH element, no recalibration required.
VER-HW Series Specifications Sensing element RH sensing element Thin-film capacitive, digitally profiled. Temperature element Optional 1K platinum, 10K thermistor, or 10K thermistor with 11K shunt. Accuracy RH ± 2% or ± 3% at 10 to 90%. Stability ± 1% at 68°F for two years. Operating range 0 to 100% RH. Temperature coefficient ± 0.1% RH °C over 0 to 60 °C. Inputs 4 to 20 mA Two-wire 12 to 24 Vdc 30 mA. Minimum 750 ohm max loop resistance. Vdc 0 to 5 or 0 to 10 Vdc, 12 to 24 Vdc or 24 Vac.
VER-HW Series Power Supply 12-24 Vdc + – + – – 1 RH Transmitter 2 + Controller 3 COM 1 4 Out 4-20 mA loop 750 ohm max 1 Optional temperature sensor. Figure 2 Typical Wiring for 4 to 20 mA External 12 to 24 Vdc Power Supply. 24 Vdc L1 + L2 – Red RH Transmitter 1+ 2 COM RH + 2 RH out 3 COM 3 COM 4 Out 1 Controller 1 Optional temperature sensor. 2 0-5 Vdc or 0-10 Vdc outboard selectable Figure 3 Typical Wiring for Three-Wire 0 to 5 or 0 to 10 Vdc Mode.
VER-PHx Series Pressure Transducer VER-PH Series The VER-PHx Series Pressure Transducer is used for the proportional pressure control and/or monitoring pressure of steam (steam siphon required), air, gases, or liquids. Microprocessor based for improved accuracy and reliability. Features: • ± 1% accuracy (including linearity, hysteresis, and repeatability). • Micromachined silicon pressure sensor. • Up to 200% overpressure without zero shift. • Over 500% burst pressure.
VER-PHx Series Accessories Model No. TOOL-95-1 Description Pneumatic calibration tool kit. Typical Applications + POWER SUPPLY 12 to 24 VDC/24 VAC - VIN Response OUT Slow COMMON Fast B C - A TEST CONTROLLER Analog Input 0-5V/0-10V or 4-20mA REMOTE Zero Zero Range VOLT mA 0-5 0-10 Output PHx Series MO DEL 07-S 08-S 09-S RANGE psig A B C 25 50 100 62.5 125 250 125 250 500 Figure 1 Typical Wiring for mA Output Pressure Transducers. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
VER-PxD Series VER-PxD Series Duct Pressure Transducer The VER-PxD Series Duct Pressure Transducer is used to monitor and control building static pressure and duct static pressure. Microprocessor based for high accuracy and reliability. Features: • ± 1% accuracy (including linearity, hysteresis, and repeatability). • Advanced ceramic capacitance sensor. • Duct pressure transducer and static pressure tip integrated as one unit. • Up to three PSID overpressure without zero shift.
VER-PxD Series Accessories Model No. TOOL-95-1 Description Pneumatic calibration tool kit. Typical Applications 0 to 10 V Controller Out VER-PxD Power Source 24Vac/DC + COM 4 - 20 mA Power Figure 1 Typical Wiring for VER-PxD Series Three Wire Vdc Output. COM Controller - VER-PxD Power Source 24Vdc only + 4 - 20 mA Power Figure 2 Typical Wiring for VER-PxD Series Two Wire mA Output. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
VER-PxP Series Static & Differential Pressure Transducer VERPxP Series The VER-PxP Series Static and Differential Pressure Transducer is used to monitor and control building static pressure, air flow, and filter pressure drop. Microprocessor based for increased accuracy and reliability. Features: • ±1% accuracy (including linearity, hysteresis, and repeatability). • Advanced ceramic capacitance sensor. • As low as 0.1” W.C. • Up to three PSID overpressure without zero shift.
VER-PxP Series Specifications Inputs Media compatible Clean dry air or any inert gas. Load impedance capability 600 ohm minimum. Proof pressure 3 PSID. Burst 5 PSID. Operating characteristics Accuracy: ± 1% FS includes: linearity, hysteresis, and repeatability. Air consumption None. Connections 1/8 inch brass hose barb fitting air connections. Cage clamp terminal block electrical connections. Outputs Electrical Signal 4 to 20 mA, 2-wire. 0 to 5 Vdc or 0 to 10 Vdc, 3-wire.
VL500 VL500 TAC Erie™ Zone Valve Control Center The VL500 zone control system provides control of up to five zone valves, 7 VA or less per valve, a circulator and boiler control in a multi-zone hydronic heating system. Field selectable priority for zone 1 eliminates the need for additional relays to provide domestic hot water priority. Additional zones can be added. Features: • Field selectable Priority Plus™ zone. • Unlimited zone expansion.
VL500 Typical Applications JUMPER 3 & 4 WHEN USING 2-WIRE ZONE VALVES 3-WIRE ZONE VALVE MOTOR 72 2-WIRE THERMOSTAT 2 WIRE ZONE VALVE 1 2 3 JUMPER 3&4 T1 T1 1 2 3 4 T2 T2 1 72 12:00 R W C 24VAC (Hot) 4-WIRE ZONE VALVE 2 3 4 T3 T3 1 2 3 4 T4 T4 1 2 3 4 Switched 2-WIRE THERMOSTAT 24VAC (Com) T5 T5 1 PRIORITY ZONE 1 2 ZONE IN 2 3 4 COM. 24VAC Fuse 3.
2 3 4 OFF P P+ 4 S M ZONE OUT 3 PRIORITY ZONE 1 2 ZONE IN T1 T1 1 Z1 T1 Z3 T3 2 3 Z4 T4 4 © Copyright 2006 TAC. All Rights Reserved. T BOILER CONTROL T PL Z5 ES/CIRC T5 T3 T3 1 SYSTEM STATUS Z2 T2 T2 T2 1 72 2 X 3 4 3 4 CIRC. #1 C1 N 2 1 2 3 3-WIRE ZONE VALVE T4 T4 1 X JUMPER 3&4 2-WIRE ZONE VALVE MOTOR 4-WIRE ZONE VALVE MOTOR NOTE: JUMPER 3 & 4 WHEN USING 2-WIRE ZONE VALVES 2 3 4 COM. 120 VAC L1 N 120VAC Fuse T1 10A/125V Slo-Blo Fuse F2 3.
WA300 300 TAC Erie™ Two Zone Hydro-Air Relay The WA300 hydro-air control relay incorporates double pole/single throw relays to provide control for up to two hydro-air systems including two air handlers/AC controller, two system heating circulators, one boiler/burner circulator, and one domestic hot water controller. Domestic hot water priority zone eliminates the need for additional relays to provide domestic hot water for indirect fired hot water tanks.
WA300 Typical Applications Figure 1 Typical Wiring WA300 -Boiler Controller and Two Fan Centers With Domestic Hot Water Priority.
Accessories and Tools 6-371 (20-642) Application 2 X 2 Sensor Installation. Mounting Ring Description Steel mounting ring for mounting sensors mounting head. Includes two #6 flat head screws. Specifications • For use with: - TS-57031. - TS-58031. - TS-81031. 6-371 10-22 Application 2 X 2 Sensor Installation Wall Box. Mounting Box Description Plain deep mounting box 2-1/2 H x 1-7/8 W x 1-3/4 D in., 1/2 in. conduit knockout, for use with 2 x 2 in. sensors and 10-77 (or 1078) plate.
Accessories and Tools 10-53 (20-707) Application 2 X 2 Sensor Guard. Thermostat Guard Description 5-3/16 in. sq. cast metal guard. Will fit over 2 x 2 in. sensors. Specifications • For use with: - TS-57031. - TS-58031. - TS-81031. 10 53 10-58 (20-711) Application 2 X 2 Sensor Mounting Ring. Mounting Ring Description Stamped metal mounting ring for use with 2 x 2 in. devices. Used with N5-52 for drywall mounting. Specifications • For use with: - TS-57031. - TS-58031. - TS-81031.
Accessories and Tools 10-82-SS, 10-82-48 Application 2 X 2 Sensor Installation Mounting Plate. Mounting Plates Description 10-82-SS: Sensor mounting plate provides 2 x 2 in. device mounting to a 2 x 4 in. vertical or horizontal outlet box. Includes two wing bolt screws. Color: stainless steel. 10-82-48: Sensor mounting plate provides 2 x 2 in. device mounting to a 2 x 4 in. vertical or horizontal outlet box. Includes two wing bolt screws. Color: Euro-white. Specifications • For use with: - TS-57031.
Accessories and Tools 65410 Application TAC Erie™ Celsius Set Point Dial Set point dial for use with T155, T167. Specifications • Setpoint: 10 to 39°C. 65170 Application TAC Erie™ Warmer/Cooler Set Point Dial Set point dial for use with T155, T167. 65671 Application TAC Erie™ Sensor for use with T158, T167, T168. May be used as either a remote sensor or a changeover sensor. For both functions two separate sensors are required. Remote Sensor Specifications • 60 inch leads, 10 kΩ @ 77°F (25°C).
Accessories and Tools AD-8101 Application TAC System 8000 Module provides sequencing, reversing, or parallel operation for up to 12 TAC System 8000 controlled devices in HVAC systems. The module sequences two non-positive positioning devices or three positive positioning devices. Sequencing, Paralleling, Reversing Module Specifications • Operation: Receives 1 to 15 Vdc output from a controller for parallell, sequencing, or reversing operation of up to 12 controlled devices.
Accessories and Tools AD-812x Application TAC System 8000 This signal adapter for dual output sequence control offers a one to two signal amplifier and a reversing module with one to two signal amplification. The adapter is usable with other TAC System 8000 controllers. Compact design permits mounting on the back of the TP-8101 thermostat. The color coding is compatible with Series 8000 devices. The output with adjustable span conforms with ASHRAE 90-75 Standards.
Accessories and Tools AD-8201 Application TAC System 8000 High/Low Signal Selector This signal selector offers selection of either the highest or lowest signal from up to six zones. One model can be used for either high or low signal selections. The selector has the capability to drive up to 12 TAC System 8000 controlled devices. It has TAC System 8000 compatible terminology. The AD-8201 offsets input to output adjustment. Standard trade mounting.
Accessories and Tools AD-8817 Application Position indication kit for MP-300, MP-400, MP-2000, MP-4000 and MP-9700 Series gear train actuators. Specifications Position Indication Kit 0 10 20 30 40 CLO SE D 50 60 7 0 8 0 9 0 OP 0 10 • Kit: - Converter: AC/DC. - Calibration potentiometer: 10K, 2W. - Indication meter: 0 to 100% (Open/Closed), 0 to 10 Vdc, 1000 Ω. EN • Operation: Meter shows position of actuator shaft rotation, closed % to open 100%. • Input: 100 Ω actuator potentiometer.
Accessories and Tools AD-8953 Application Vinyl mounting track for cabinet mounting of devices. Vinyl Mounting Track Specifications • Dimensions: 3-3/4 in. W x 4 ft. L (95 mm x 1.2 m). AD-8954 Application Panel mounting adaptor, adapts AD-8301 or AT-8xxx remote setpoint adjustors. Panel Mounting Adaptor Specifications • Mounting: Can snap into AD-8953 mounting track. • Dimensions: 3-3/4 H x 2-1/8 W x 1-1/4 D in. (95 x 54 x 32 mm).
Accessories and Tools AD-8969-202 Series Application AD-8969-202 Converting and interfacing a 4 to 20 mAdc external signal to 1 to 5 Vdc signal. Resistor Kit Specifications AD-8969-202 • 250 Ω, ±1% tolerance, 1/2 watt, temperature coefficient (TC) of 25 PPM/°C metal film resistor. • Number in kit: six. • Refer to F-21279 for complete applications. AD-8969-621 Application Used for electrical and magnetic noise by-passing to ground.
Accessories and Tools Acces sories and Tools AE-304, AE-314 Application This relay connects power to control equipment. The AE-3xx can be panel mounted or stand alone with AE-300 enclosure. One unit (DPDT) is universally adaptable to most applications. Power Relays Specifications • • • • • Electrical switch: DPDT clapper type. Connections: Screw terminals. Coil power requirements: 9.8 VA. UL Listed. Dimensions: 3-3/8 H x 2-17/32 W x 2-1/2 D in. (86 x 64 x 64 mm).
Accessories and Tools AM-123 Application Angle damper plated clip for attaching connector to damper blade. Angle Damper Clip Specifications • Use AM-122 or AM-132 connectors in 3/8 in. (10 mm) slot. Accessories AM-122 Straight linkage connector. AM-132 Ball joint linkage connector. AM-125, AM-125-048, AM-125-600 Application Damper rod. Damper Rod Specifications AM-125 • Plated 5/16 dia. x 20 in. (8 mm x 0.5 m). • Maximum load for damper rod 173 lbs. (769 N). AM-125-048 • Plated 5/16 dia x 48 in.
Accessories and Tools AM-161, AM-161-1, AM-161-3 Application Damper linkage kits eliminate the need to order all the necessary linkage parts separately. Damper Linkage Kits Specifications • Description: Kits consist of two to five pieces of prepackaged hardware. • Order AM-125-xxx damper rod separately. AM-161-3 AM-161 Hardware Supplied Damper Linkage Model No. 1/2 in. Dia.
Accessories and Tools AM-231 Application For connecting MM and MMR-400/500 Series modular actuators to 120, 208, or 240 Vac power sources. Transformer/Cover Kit (if power 120, 208, or 240 Vac) Specifications • Power supply: - Primary: 120/208/240 Vac (+10, -15%), 50/60 Hz. For maximum reliability and operating life, use at nominal primary voltage. - Secondary: 24 Vac. - VA: 40. • Ambient temperature limits: - Shipping and storage: -40 to 160°F (-40 to 71°C). - Operating: -40 to 130°F (-40 to 54°C).
Accessories and Tools AM-237 Application AM-237 kit is used to mount Honeywell Q607 auxiliary switch and Q181A auxiliary potentiometer kits to MM or MMR-400/500 modular actuators when AV-631 linkage is used. Bracket Kit Specifications • Refer to F-23503 for complete applications.
Accessories and Tools AM-332 Application Single potentiometer for use in position indicating applications or in paralleling actuators. For use with MP oil-submerged gear train actuator or AM-348 mounting bracket. Potentiometer Specifications • Construction: Spring-loaded friction-driven copper wiper arm with a contact that rides on a uniformly wound wire resistance card. • Resistance card: - Resistance: 100 Ω; use with a power supply not to exceed 25 Vac. - Electrical capacity: 3 watts.
Accessories and Tools AM-345 Application Time delay relay used with CP-8301-xxx and CP-8391-91x solid state drives to control MP-98xx and MP-99xx actuators. Actuator Mount Time Delay Relay Specifications • Electrical Switch: Two SPDT relays having separate electronic 3 to 5 second time delay circuits. - Coil power requirements: 5 VA at 24 Vac. - 120 Vac: 5. - 240 Vac: 2.5 AC AC TU A C E TO SS R OR IES • • • • • Connections: Color coded leads. Case: Metal Locations: NEMA Type 1.
Accessories and Tools AM-369 Application The NEMA 4 rated gasket cover kit is designed to provide the internal components MC and MP-9000 Series actuators with a degree of protection against wind-blown dust, rain and hose directed water. NEMA 4 Rated Gasket Cover Kit Specifications • Construction: Top and back gasketed aluminum covers. • Kit contains: - One top cover plate. - One back cover plate. - Four #6-32 top cover plate screws. - Five #8-32 back cover plate screws.
Accessories and Tools Acces sories and Tools AM-601 Application Required to modify Mx-5xxx and Mxx-5xxx hydraulic actuators for damper applications with 2 in. (51 mm) stroke. Damper Actuator Mounting Adaptor Specifications • Device includes: - Mounting bracket. - Damper linkage with spring. - AM-122 straight connector. - Spring loader fixture.
Accessories and Tools AM-672 Application TAC DuraDrive The AM-672 universal mounting bracket is designed to provide a mounting surface for an actuator when the actuator cannot be mounted directly to the damper shaft and no proper mounting surface is available. Universal Mounting Bracket Specifications • To be used with the following damper actuators: - MA40-704x. - MF40-704x. - MS40-704x. - MA4x-707x. - MF4x-707x. - MS4x-707x. - MA4x-715x. - MF4x-715x. - MS4x-715x. • Material: 12 gauge galvanized steel.
Accessories and Tools AM-674 Application TAC DuraDrive The AM-674 weather shield provides moderate weather protection for damper actuators which are mounted outdoors. While this weather shield provides effective, moderate, weather protection it is not designed as a water-tight enclosure. Weather Shield Specifications • Material: 16 gage galvanized steel. • Provides weather protection for the following actuators: - MX40-704x. - MX41-707x. - MX41-715x. - MX40-717x. - MF41-6043. - MS41-6043. - MF41-6083.
Accessories and Tools AM-676 Application Tac DuraDrive The AM-676 universal shaft extension extends the length of the damper shaft in applications where the damper shaft is too short to reach the damper actuator. Universal Shaft Extension Specifications • Length: Approximately 9-1/2 in. (13 mm). • Damper shaft sizes: - 3/8 to 11/16 in. (10 to 17 mm) diameter for round shafts. - 3/8 to 9/16 in. (10 to 14 mm) square for square shafts.
Accessories and Tools AM-689 Application TAC DuraDrive The AM-689 Rotation Limiter is used to limit the angle of rotation of a direct coupled damper actuator in applications where the damper does not have a proper end-stop. Rotation Limiter Specifications • Material: Plated steel. • Maximum angle allowed: 95°. • Setting Increments: 5°. • Actuators: Mx4x-707x and Mx4x-715x. • Refer to F-25098 for complete applications.
Accessories and Tools AM-693 Application TAC DuraDrive The AM-693 damper linkage kit provides a mechanical linkage between the damper actuator and the damper shaft when a direct coupling is not possible. Damper Linkage Kit Specifications • Actuators: Mx4x-707x and Mx4x-715x. • Parts included in kit: - Crank arm with wire clip. - “C” mounting brackets (2) - Self-tapping metal screws (4). - Ball joints (2). - Flat washers (4) • Refer to F-25098 for complete applications.
Accessories and Tools AM-704 Application TAC DuraDrive The AM-704 modulation interface converts signal input from a pulse-width modulated input signal to an analog 2 to 10 Vdc signal. Modulation Interface Specifications • Actuators: MS40-7043, MS4x-7073, MS4x-7153, MS40-717x, MS41-6083, MS41-6153, MS41-6343, and MS4D-xxxx-x00. • Four input pulse clock rates. • Optically isolated input signal. • Linear analog output has 256 steps of resolution. • Diagnostic LEDs. • Supply voltage: 24 Vac/Vdc ± 15%.
Accessories and Tools AM-705 and AM-706 Application TAC DuraDrive Positioners The AM-705 and AM-706 positioners are used for remotely controlling or setting minimum position of proportional actuators. The AM-705 is for surface mounting. The AM-706 is for flush mounting. Specifications • Actuators: MS40-7043, MS4x-7073, MS4x-7153, MS40-717x, MS41-6083, MS41-6153, MS41- 6343, and MS4D-xxxx-x00. • Control range is 0 to 100% of the actuator rotation angle.
Accessories and Tools AM-710 Application TAC DuraDrive The AM-710 universal clamp is used to clamp the actuator to 3/4” diameter round shafts, 3/8” to 5/8" hex shafts, or 1/2” square shafts. The AM-710 is required whenever the AM-676 shaft extension is used. Universal Clamp Specifications • Actuators: Mx40-704x. • Shaft sizes: - Up to 3/4" diameter round shafts. - 3/8” to 5/8” hex shafts. - Up to 1/2” square for square shafts. - Secured to actuator with retaining ring.
Accessories and Tools AM-713 Application TAC DuraDrive The AM-713 bracket is a mounting bracket for Honeywell Mod IV M6415-type actuators. Bracket Specifications • Actuators: Mx40-704x. • Refer to F-26896 for complete applications. AM-714 Application TAC DuraDrive The AM-714 weather shield provides moderate weather protection for damper actuators which are mounted outdoors. While these weather shields provide effective, moderate, weather protection, they are not designed as a water-tight enclosure.
Accessories and Tools AM-717 Application TAC DuraDrive The AM-717 replacement universal clamp is used to clamp the actuator up to 5/8 in. dia. or up to 1/2 in. sq. Available to replace lost standard clamps shipped with actuator. Universal Clamp Specifications • Refer to F-26896 for complete applications. AM-726 Application TAC DuraDrive The AM-726 accessory kit provides for changing the actuator rotary motion to linear motion for the MF41-6043, MF41-6083, MS41-6043, MS41-6083 series 35 in.-lb.
Accessories and Tools AM-728 Application TAC DuraDrive Accessory Kit The AM-728 accessory kit provides a conduit connection for the MF41-6043, MS41-6043, MF41-6083, and MS41-6083 series 35 in.-lb. non-spring return direct coupled damper actuators. Specifications • Contains: - Adaptor mounting bracket. - Conduit adaptor. - Mounting screws (2). • Actuators: - MF41-6043 - MS41-6043 - MF41-6083 - MS41-6083 • Refer to F-26802 for complete applications.
Accessories and Tools AM-753, AM-754 Application TAC DuraDrive The AM-753 and AM-754 shaft mounting clamps are used to clamp the actuator to the damper shaft. The AM-753 is used for a 5/8” (16 mm) square shaft, or 3/4” to 1” (19 mm to 25 mm) round shaft. Two clamps are in each package. The AM-754 is used for a 3/8” to 1/2” (10 to 13 mm) round and square shaft. Two clamps are in each package. Universal Mounting Clamps Specifications • Material: zinc dichromate plated steel.
Accessories and Tools AM-758 Application TAC DuraDrive The AM-758 universal mounting bracket is designed to provide a mounting surface for the Mx4x-707x and Mx4x-715x actuators when the actuators cannot be mounted directly to the damper shaft and no proper mounting surface is available. The bracket allows both vertical and horizontal mounting. The bracket requires the AM-690 or AM-691 crankarm kit be used. Universal Mounting Bracket Specifications • Material: 12-gauge galvanized steel.
Accessories and Tools AM-761, AM-762 Application TAC DuraDrive Anti-Rotation Bracket The AM-761 and AM-762 anti-rotation brackets are used to secure the Mx4x-707x and Mx41-715x actuators and prevent them from rotating around the shaft. Available to replace lost anti-rotation brackets shipped with actuator. Specifications • AM-761: 7 inch length. • AM-762: 9 inch length. • Refer to F-25098 for complete applications.
Accessories and Tools AM-771 Application TAC DuraDrive The AM-771 is a mounting bracket designed to provide a mounting surface for an actuator when the actuator cannot be mounted directly to a damper shaft. Mounting Bracket Kit Specifications • For use with the following actuators: - Mx4D-60x3-xxx - Mx4D-7033-xxx. - Mx4D-8033-xxx. • Kit contains: - Bracket. - Shaft. - Crank arm. - Mounting screw. - Linkage kit. AP-302 Application Duct status pressure sensing tips.
Accessories and Tools AP-305 Application Duct status pressure sensing tips. Static Pressure Probe Specifications • • • • • • Mounting hardware provided. 1/8 in. pipe thread end fitting. Construction: Brass with S.S. tee end. Mounting location: Very low actuating pressure. Dimensions: 8-3/4 L x 2-1/2 W in. (222 x 64 mm). For use with: - P323 Series. - PC-301. - PF-300 Series. - PP-1012. - PP-3013. - PP-3113. - PKS-323. - R435. - R436. F-27382-1 © Copyright 2006 TAC. All Rights Reserved.
Accessories and Tools ASP-81xx Application This indicator is a self-contained unit, designed for panel mounting. The unit has a 1/2 in. (13 mm) high, seven segment, light emitting diode (LED) display for temperature, 0 to 100 or 0 to 1000 range digital readouts. Digital Indicator Specifications • Refer to F-21292 for complete applications. Power Requirements Input Model No. Range ASP-8111 -40 to 260 °F or (-40 to 126°C) Any TS-8000 Series (without internal setpoints & TS-8204) 1KΩ Balco sensor.
Accessories and Tools AT-81xx, AT-82xx, AT-8435, AT-8522, AT-8901 Application TAC System 8000 Use these adjusters when setpoint is to be remote from the controller or to obtain setpoint range required for the application. Setpoint Adjusters Specifications 30 40 50 60 20 • Universal mounting capability with selected hardware. • Matches all TAC System 8000 AB1 or AB2 input requirements. • Universal adaptation of specific applications and/or alternate non-TAC System 8000 devices.
Accessories and Tools AT-8122-420, AT-8222-xxx Application TAC System 8000 Remote Setpoint Adjusters The AT-8122-420 remote setpoint adjuster and AT-8222-xxx series dial scales are required when using the TSP-8xxx, VER-HDxx-MSx, VER-HOxx-MSx, VER-HxWx-MA 4 to 20 mA transmitters in association with TAC System 8000 controllers. 30 40 50 60 20 Specifications 70 10 80 • Adapts new 4 to 20 mA transmitters to TAC System 8000 controllers. • Universal mounting capability with appropriate hardware.
Accessories and Tools Acces sories and Tools AT-1x Series, AT-2x Series, AT-61, AT-11 through AT-70 Application Thermostat covers and inserts. Thermostat Covers and Inserts Specifications -398 (oC) -399 (oF) -400 -401 -402 AT-61-400-0-24 AT-61-401-0-24 AT-61-402-0-24 AT-61-403-0-24 AT-61-404-0-24 Typical of: AT-61 cover plates (in packages of 24) brushed bronze. Cover plates are typically used to convert a “standard” cover to -4xx cover.
AT-1x Series, AT-2x Series, AT-61, AT-11 through AT-70 Thermostat Covers and Inserts (Continued) Standard Part Number -400 Plastic Metal Cover Cover Plastic Cover Metal Cover -401 Cover Platea Plastic Cover Metal Cover -402 Cover Plate a Plastic Cover Metal Cover -403 Cover Plate a Plastic Cover Metal Cover HC-101-404, HS-8101, HS-8201, HSP-82xx, -404 Cover Plate a Plastic Cover Metal Cover -600 Cover Plate a Aspirated Metal Cover AT-11-404 TKS-5001 AT-14 AT-24 AT-14-400 AT-24-40
Accessories and Tools AT-80 Application Replacement cover kits. Cover Kits Specifications • Kit includes: - One shadow white plastic cover. - Five cover inserts. Thermometer Setpoint Indicator Setpoint Knob • Where used: - TS-57011 - TS-57011-850 - TS-58011 - TS-81011 AT-101 Application Lock cover screw kit modifies room thermostats to prevent unauthorized tampering of either the dial setting or the internal mechanism. Lock Cover Screw Kit Specifications • Electric. - All except TA-121, TC-114.
Accessories and Tools AT-104 Application Package of 100 dial stop pins to insert in dial ends to limit the high or low setting of room thermostats. Dial Stop Pins Specifications • Electric. - All except TA-121, TC-114. • Electronic. - TP-810x. - TP-8232. - TS-5191. - TS-5711. - TS-811x. • Pneumatic. - All TK-1xxx and TK-5xxx except TK-17xx, TK-18XX. AT-201, AT-203, AT-206 Application Immersion well for use with 3/8 in. (10 mm) temperature bulbs.
Accessories and Tools AT - 208 Application Duct mounting kit for pneumatic and electric temperature bulbs. TS-8201-105, TS-8204 temperature sensors typical. Duct Mounting Kit Specifications • Refer to F-18895 for complete applications. AT-209 Application 3/4 in. MNPT liquid line or tank mounting kit for TC-4x1x, TC-4x2x, TC-4x5x, TK-6024 or TK-6124 Series bulb thermostats. Bulb well is recommended. Liquid Line or Tank Mounting Kit Specifications • Refer to F-18895 for complete applications.
Accessories and Tools AT-219 Application Bulb well for use with TS-290 Series dial thermostats for insertion into ducts, pipes, and tanks. Bulb Well Specifications • Construction: Brass • Connection: 1/2 in. MNPT, external, 5/8-18 UNF internal. • Dimensions: 9/16 Dia. O.D. 4.6 in. insertion length (116.8 mm) nominal. 6.25 in. overall length (158.8 mm) nominal. • Will accept a 7/16 in. Dia. bulb element.
Accessories and Tools AT-504 Application Single room type electric or pneumatic thermostats, sensing elements and electronic controllers or sensing elements. Used to cover a rough plaster hole in the wall. Use with AT-505 sub-base for surface mounting applications. Mounting Base Single Specifications • Color: Beige. • Dimensions: 5-7/16 H x 3-7/8 W x 3/8 D in. (138 x 98 x 16 mm).
Accessories and Tools AT-602, AT-603 Application Selector switch sub-bases for use with electric room thermostats to provide switching functions such as heating to cooling, day to night control, etc. Single Unit Sub-Base Specifications • Legend plates: Blank plate on left side is factory installed. • Connections: Coded screw terminals. • Mounting: On flush or surface with box. Directly to the wall for 24V applications. • Switch positions: - AT-602: Lower right DP4T. - AT-603: Upper right: DPDT.
Accessories and Tools AT-607, AT-608 Application Selector switch sub-bases for use with electric room thermostats to provide switching functions such as heating to cooling, day to night control, etc. Duplex Unit Sub-Base Specifications • Connections: Coded screw terminals. • Mounting: On flush or surface with box. Directly to the wall for 24V applications. • Switch positions: - AT-607: Lower right: DP4T. - AT-608: Upper right: DPDT. Lower right: DP4T.
Accessories and Tools Application AT-609 Series Legend plates for use with AT-600 Series selector switch sub-base. Legend Plates Specifications • Construction: Brown simulated leather finish with bright letters and self-adhesive backing.
Accessories and Tools AT-1103, AT-1163 Application Room thermostat guards protect thermostats from damage and vandalism. Thermostat Guard Specifications • Construction: - AT-1103: Wire guard with steel base plate, zinc plated. - AT-1163: Guard, zinc plated, with beige steel base. H • Mounting: To standard outlet or directly to the wall. • Dimensions: - AT-1103: 4-1/4 H x 2-7/8 W x 1-5/8 D in. (108 x 67 x 41 mm). - AT-1163: 6-1/2 H x 6-5/8 W x 3-1/4 D in. (165 x 168 x 83 mm).
Accessories and Tools AT-1104 Application Room thermostat guards protect thermostats from damage and vandalism. Thermostat Guard Specifications • • • • Construction: Cast aluminum guard with steel base plate. Mounting: To standard outlet or directly to the wall. Dimensions: 4-1/4 H x 3-1/8 W x 1-5/8 D in. (108 x 79 x 41 mm). Refer to F-07930 for complete applications.
Accessories and Tools AT-1165 Application Room thermostat guard protects thermostats from damage and vandalism. Thermostat Guard Specifications • Construction: Clear plastic guard with solid and ring base, tumbler type key lock. • Mounting: To standard outlet or directly to the wall. • Included: Mounting ring for installation over installed thermostats without their removal from the wall. • Dimensions: 8 H x 5-1/2 W x 3-1/2 D in. (203 x 140 x 89 mm). • Refer to F-07930 for complete applications.
Accessories and Tools BYZP-xxx Application Electrical component for AE-629 to AE-662 control cabinets. Terminal Block Specifications BYZP-145 • 12 circuit terminal block. BYZP-146 • Marker strip #1 to 12. BYZP-252 • Marker strip #13 to 24. BYZP-253 • Marker strip #25 to 36. BYZP-269-2 Application Mounting bracket for circuit breaker and switch. 366 © Copyright 2006 TAC. All Rights Reserved.
Accessories and Tools CYZP-11 throughCYZP-427 Application Switches, mounting and position indicating plates for AE-629 to AE-662 control cabinets and standard switch boxes. SYZE-52 through SYZE-300 Toggle Switch Switch Part No. CYZP-11 Switch Action DPDT AC Rating Amp 10 Volt Switch Type 250 Toggle 2 position CYZP-105 4PDT 5 24 CYZP-268 DPDT (Center Off) 10 CYZP-427 4PDT (Center Off) 5 24 CYZP-346 SPST N.O. 5 125 CYZP-347 SPST N.C.
Accessories and Tools EYZP-xxx Application Electrical component for AE-629 to AE-662 control cabinets. Pilot Light Assembly Specifications EYZP-504-1. • Lamp, 24V, 0.073 amp, 1.7 W. EYZP-504-2. • Lamp, 120V, 0.025 amp, 3.0 W. EYZP-504-3. • Lamp, 48V, 0.053 amp, 2.5 W. EYZP-721. • Lamp socket with clip. EYZP-722-1. • Lens, red. EYZP-722-2. • Lens, green. EYZP-722-3. • Lens, amber. EYZP-722-4. • Lens, blue. EYZP-722-5. • Lens, white.
Accessories and Tools N5-52 (21-068) Application 2 X 2 Sensor Installation Mounting Plate. Description Mounting Bracket Mounting bracket (for use in mounting sensors). For installation on dry wall construction. Used with 10-58 for drywall mounting. Specifications • For use with: - TS-57011. - TS-58011. - TS-81031. N5-53 (21-069) Application 2 X 2 Sensor Installation Mounting Plate. Description Mounting Plate Mounting plate for sensors. Use for dry wall construction.
Accessories and Tools cces ories Application TAC System 8000 nd series electronic temperature transmitters are used ools TSP-8101 for providing signals to 8000 controllers and temperature TSP-8101 Series, TSP-8111 Series Temperature Transmitters indication readouts. TSP-8111 series electronic temperature transmitters are used for providing signals for temperature indication readouts. M- Specifications 50 Refer to F-15496 for complete applications. 5 TSP-8101 Series TSP-8111 Series Description.
Accessories and Tools TOOL-11 Application Calibration wrench for 2-position electric room thermostats, electric MU actuators and pneumatic receiver controller. Calibration Wrench Specifications Also included in AL-95. TOOL-12 Application 5/32 hex auxiliary switch adjustment for MA and MP-5000 Series actuators. TOOL-13 Application For contact preparation. Contact Burnishing Tool TOOL-14 Application Spanner head bit for #6 spanner head screws.
Accessories and Tools TOOL-16 Application Cam adjustment wrench fo ME-12313 and ME-12313-102 actuators. Cam Adjustment Wrench TOOL-23 Application Bellows compressor for remote bulb thermostats. Bellows Compressor TOOL-95-1 Application Pneumatic calibration tool kit. Calibrates all pneumatic equipment. Pneumatic Thermostat Calibration Kit Specifications Kit includes: • MCS-GA, gauge adaptor. • N2-4, 2 x 2, 1/16 in. hexhead thermostat calibration cover screw wrench.
Accessories and Tools TOOL-11x Application Wrench for removing thermostat backplates and covers. Wrench Specifications TOOL-110 • 3/32 in. hex wrench. TOOL-111 • 5/64 in. Allen wrench. Also included in TOOL-96. See also TOOL-82. TOOL-112 • 7/64 in. Allen wrench. Also included inTOOL-96. TOOL-113 • 0.035 in. Allen wrench. TOOL-115 • TORX T-8 offset driver for removing back plates of pneumatic room thermostats (TK-1xxx and TK-1xxxx) manufactured after 1-1-81.
Accessories and Tools TOOL-203, TOOL-204, TOOL-205 Application TAC System 8000 Substitute for temperature element equivalent to 70°F for TAC System 8000 controllers. Precision Resistor Specifications TOOL-203 • 1000 Ω ±0.1% temperature coefficient 20 ppm/°C precision resistor. TOOL-204 • 22K Ω ±1% resistor (substitute for HS-8xxx humidity element equivalent to mid-point of element) for TAC System 8000 controllers. TOOL-205 • 1 meg. Ω resistor for calibration of TP-8124.
Enclosure Selection Chart nclosure election hart Enclosure ratings in NEMA and IP terms are similar. Use the following tables to convert from one rating to the other. NEMA Rating Definitions (Ref. NEMA 250, UL 50, and ANS/UL 50). NEMA Type 1 2 3 3R 3S 4 4X Intended Use and Description UL Standard UL50 Requirements Indoor use primarily to provide a degree of protection against limited amounts of falling dirt.
Low Pressure Conversion Chart Low Pressure Conversion Chart in/H2O .1 .2 .4 .6 .8 1.0 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 376 P.S.I. .0036 .0072 .0144 .0216 .0289 .0361 .0722 .1083 .1444 .1804 .2165 .2526 .2887 .3248 .3609 .3970 .4331 .4692 .5053 .5414 .5774 .6136 .6496 .6857 .7218 .7579 .7940 .8301 .8662 .9023 .9384 .9745 1.010 in/Hg .0073 .0146 .0293 .0440 .0588 .0735 .1470 .2205 .2940 .3673 .4408 .5143 .5878 .6613 .7348 .8083 .8818 .9553 1.029 1.102 1.176 1.249 1.
High Pressure Conversion Chart igh ressure onversi n Chart High Pressure Conversion Chart P.S.I. 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.2 6.3 F-27382-1 in/H2O 27.71 30.45 33.22 35.98 38.75 41.52 44.29 47.06 49.82 52.59 55.36 58.13 60.90 63.67 66.43 69.20 71.97 74.74 77.51 80.27 83.04 85.81 88.58 91.35 94.11 96.88 99.65 102.4 105.2 108.
High Pressure Conversion Chart P.S.I. 6.4 6.5 6.6 6.7 6.8 6.9 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.8 8.0 8.2 8.4 8.6 8.8 9.0 9.2 9.4 9.6 9.8 10.0 11.0 12.0 13.0 14.0 14.7 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 25.0 378 in/H2O 177.2 179.9 182.7 185.5 188.2 191.0 193.8 196.5 199.3 202.1 204.8 207.6 210.4 215.9 221.4 227.0 232.5 238.0 243.6 249.1 254.7 260.2 265.7 271.3 276.8 304.5 332.2 359.8 387.5 406.9 415.2 442.9 470.6 498.2 525.9 553.6 581.3 609.0 636.7 664.3 692.0 in/Hg 13.03 13.23 13.44 13.
Conversion Factors Conversion Factors Multiply By To Obtain Note: Conversion factors rounded. Centimeters of mercury 27.85 lbs/sq ft PSI x 27.71 = in. H2O PSI x .0689 = bar Centimeters of mercury 0.1934 lbs/sq inch PSI 2.036 = in. Hg PSI x 68.95 = mbar Centipoise, dynamic viscosity, μ 1.00 Centistokes, kinematic viscosity, ν 1.00 PSI x 703.1 = mm/H20 PSI x 6895 = pa CFM 0.000471947 PSI x 51.75 = mm/Hg PSI x 6.895 = kPa Clo 0.155 PSI x .
Conversion Factors Multiply By To Obtain Gallons 231 cubic inches Liters 2.113 pints (liquid) Gallons 128 fluid ounces Liters 1,057 quarts (liquid) Gallons 3.785 liters Meters 100 centimeters Gallons water 8.35 lbs water at 60°F Meters 3.281 feet Gph 1.05 mL/s Meters 39.37 inches Gpm 0.000063092 m3/s Meters 1000 millimeters Gpm 0.0631 L/s Meters 1.094 yards Gpm/ft2 0.6791 Micron (μm) of mercury (60°F) 133 mPa Gpm/ton refrigeration 0.0179 mL/J Mile 1.
Electronic/Pneumatic Transducer Conversion Chart Multiply Pounds/sq inch onversio Factors nd esistor oding By To Obtain Multiply By To Obtain 6.8948 kPa Watt-hours 3.415 btu-hr. Quart (liquid, US) 0.946 L Watt-hours 2655 foot-pounds Square (100 ft2) 9.29 m2 Watt-hours 0.001341 horsepower hrs. Tablespoon (approx.) 15 mL Watt-hours 0.001 kilowatt-hours Teaspoon (approx.) 5 mL Watt per square foot 10.8 W/m2 100,000 btu Yd 0.9144 M 2240 pounds Yd 2 0.
Useful Formulas TAC SYSTEM 8000 Ratio (Reset applications only) Action A (T1 max - min) = __________________ Balco between 6.2 and ISA = 1K resistor between ISA and COM Direct Action B (T2 max - min) = __________________ 1K resistor between ISA and 6.2 = Balco between ISA and COM Reverse Action B --- = Ratio A Useful Formulas Reset Truth Table Typical S.T.R. If You Need the Reset To Be: Make the “B” Bridge Reverse The same as the “A” Bridge Direct Different than the “A” Bridge S.T.R.
Glossary Abbreviations R: Ratio R.A.: Return Air, Reverse Action, Reverse Acting ACU: Air Conditioning Unit RC: Receiver-Controller AHU: Air Handling Unit RH: Relative Humidity ASHRAE: American Society of Heating, Refrigerating, and Air-Conditioning Engineers; 1791 Tullie Circle N.E.; Atlanta, GA 30329. RSES: Refrigeration Service Engineer Society, 960 Rand Rd.
Glossary Auxiliary Device (Pneumatic): A control module which is generally placed between the controller and actuator that modifies the controller signal in some manner before the signal reaches the actuator. Example: Relays and switches. Averaging Element: A sensing device that can extend across the entire duct and sense the average temperature. Axial Fan: A fan with multiple impeller blades that move air along the length of the fan’s axle.
Glossary Degree Day, Heating: A unit, based upon temperature and time, used in estimating fuel consumption and specifying nominal heating load of a building in winter. For any one day, when the mean temperature is less than 65°F (18°C), there exist as many degree days as there are Fahrenheit (Celsius) degrees difference in temperature between the mean temperature for the day and 65°F (18°C). Dew Point: The point at which a given mixture of air and water vapor is saturated.
Glossary Humidity Controller: A device which senses and controls the moisture content of air. Humidistat: An instrument which measures humidity and controls a device(s) for maintaining a desired humidity. Hunting: The action of a controller which causes the controlled device to continuously travel from one end of its stroke to the other. Normally associated with proportional control. Hunting is an undesirable condition. HVAC: Heating, ventilating, and air conditioning.
Glossary Offset: The amount of difference between control point and setpoint in a proportional control system. Recovered Energy: Energy utilized which would otherwise be wasted from an energy utilization system. Packaged Equipment: Reheat: The process by which heat is added to preconditioned (cooled, humidified, etc.) primary air or recirculated room air. Off-the-shelf HVAC equipment.
Glossary Sequencing: A control arrangement in which several actuators move through their stroke in succession as the signal from the controller changes. Example: Electric; This arrangement is derived by using actuators with different voltage ranges (such as 3 to 6 Vdc and 6 to 9 Vdc) or by the use of a sequencing adaptor. Pneumatic; This arrangement is derived by using actuators with different spring ranges (such as 3 to 8 psi and 8 to 13 psi) or by the use of a pneumatic relay.
Glossary Variable Frequency Drive: A device that varies the voltage to an electric motor to vary the speed of the motor (also called a speed drive.) VDC: Volts direct current. Velocity Pressure: The pressure caused by the air being in motion and has a direct relation to the velocity of the air. Wet-Bulb Temperature: Air temperature as measured by a wet-bulb thermometer and which is lower than dry-bulb temperature (for all cases except when the air is saturated) in inverse proportion to the humidity.
Glossary 390 © Copyright 2006 TAC. All Rights Reserved.