Install Instructions
© Copyright 2005 PECO, Inc. All Rights Reserved P/N 70324 3220-2250 Rev0 Page 1
TA156/TB156/TE156
Installation Instructions
•UseCopperwireonly,insulateorwire
nutallunusedleads.
•Anywiring,includingtheremoteprobe,
maycarrythefulloperatingvoltageof
thethermostat.
Voltage
Rating
Inductive
FLA LRA
Resistive
Amps
Pilot
Duty
Thermostatic
Switching
24 VAC
120VAC
240VAC
277VAC
N.A. N.A. N.A. 24 VA 10 VA
5.8 34.8 6.0 125 VA 20VA
20VA
20VA
125 VA
125 VA
2.9 17.4 5.0
2.4 14.4 4.2
FAN AND SYSTEM SWITCHES
1.TheT156controlfeaturesasnapinplacepanelmountingcover.The
coverwillfacilitatearangeofpanelthicknessfrom.020”to.065”.
ThepanelopeningfortheT156installationshouldbe4.52±.015”by
2.770±.015”.
2.Dependantuponspecicinstallationcongurationthewiringmaybe
donepriortoorafterinstallationoftheT156intotheenclosure.The
installershoulddeterminethispriortoinstallation.
3.Checkout:Afterwiringandinstallationarecomplete,energizethe
systemandchecktheoperation.Adjustthethermostatasnecessary
tocompleteatleastonecycle.Besurethethermostatandallother
equipmentarefunctioningcorrectly.
WIRE COLOR FUNCTION
WHITEWITHORANGESTRIPE FANSPEED,HIGH
WHITEWITHREDSTRIPE FANSPEED,MEDIUM
WHITEWITHBROWNSTRIPE FANSPEED,LOW
RED HEATOUTPUT
BLUE COOLOUTPUT
BLACK L1(HOT)
YELLOW L2orNEUTRAL
BROWN REMOTEPROBE(2
LEADS,NOPOLARITY)
PURPLE FANSUPPLY
ORANGE SWITCHEDPOWER
TemperatureRange:50°F-90°F
TA156:AHEAT-OFF-COOLsystemswitchmanuallyselectsheating
orcoolingmode.IntheHEATposition,onlytheheatoutputcycles
withdemand.IntheCOOLposition,onlythecooloutputcycleswith
demand.IntheOFFpositionheatingandcoolingoutputsareoff.Units
withatwopositionsystemswitchorwithoutasystemswitchmustusea
loadtransferswitchwhenbothheatingandcoolingoutputsareusedto
preventcontrolfailureandequipmentdamagecausedbydirectcycling
betweenloads.
TB156:AnON-OFFsystemswitchenablesauto-changeoverofheating
andcoolingmode.IntheONpositionthethermostatactivatesheating
orcoolingoutputsdependantupontherelationshipbetweentheset
pointandtheambienttemperature.Heatontocoolondeadbandis
4°F.IntheOFFposition,heatingandcoolingoutputsareoff.Units
withoutasystemswitchcycledirectlybetweenheatingandcoolingwith
a4°Fdeadband.
TE156:TheTE156actasaswitchingdeviceandhasnothermostat
function.Byuserswitchselection,inputpowerisswitchedto
correspondingoutputs.StandardswitchcongurationsisON-OFF.Inthe
OFFpositionalloutputsareOFF.IntheONpositionpowerisswitched
totheswitchedpoweroutput.
Onunitsthathavefanswitchingtheswitchedpoweroutputmaybe
internallywiredtothefansupply.Dependinguponcongurationthe
usermayneedtomakethisconnection.
FAN:Someunitshaveaswitchformanualselectionoffanspeed.Fan
operationmaybeinternallywiredforfancontinuousoperationora
fansupplyconnectionmaybeavailable.Wheninternallywiredforfan
continuousoperation,thefanwillbeoffwhenthesystemswitchisoff.
Onunitswithafansupplylead,thefanoperationisdependantupon
externalconnections.Dependantupontheseconnectionsthefanmay
notbeoffwiththesystemswitchintheoffposition.
dEsCRIpTION
WIRINg CONNECTIONs
FaN & sysTEm sWITChEs
ThERmOsTaT OpERaTION
•READTHESEINSTRUCTIONSCAREFULLYBEFOREATTEMPTINGTO
INSTALL,OPERATEORSERVICETHISTHERMOSTAT.
•Failuretoobservesafetyinformationandcomplywithinstructionscould
resultinPERSONALINJURY,DEATHAND/ORPROPERTYDAMAGE.
•Toavoidelectricalshockordamagetoequipment,disconnectpowerbefore
installingorservicing.
•Toavoidelectricshockordamagetoequipment,useonlywiringwithinsula-
tionratedforfullthermostatoperatingvoltage.
•Toavoidpotentialfireand/orexplosiondonotuseinpotentiallyflammableor
explosiveatmospheres.
•Retaintheseinstructionsforfuturereference.Thisproduct,wheninstalled,
willbepartofanengineeredsystemwhosespecificationsandperformance
characteristicsarenotdesignedorcontrolledbyPECO,Inc.Youmust
reviewyourapplicationandnationalandlocalcodestoassurethatyour
installationwillbefunctionalandsafe.
WaRNINg
▲
!
CaUTION
▲
!