Install Instructions

Table Of Contents
69
Table 12.5: Electrical Ratings
SERIES PEERLESS
®
PUREFIRE
®
ELECTRICAL RATINGS
Boiler
Model
Supply
Voltage
(-15%, +10%)
Frequency
(±1.2 hz)
Blower Gas Valve Pumps
Max Total
Service
Current to
Boiler
Voltage
(VAC)
Current
(Amps)
Voltage
(VAC)
Current
(Amps)
Voltage
(VAC)
Max.
Current
(Amps)
PF-50 120 VAC 60 hz 120 0.53 120 0.09 120 2.48 3.15
PF-80 120 VAC 60 hz 120 0.53 120 0.09 120 2.48 3.15
PF-110 120 VAC 60 hz 120 0.78 120 0.09 120 2.23 3.15
PF-140 120 VAC 60 hz 120 0.71 120 0.09 120 2.30 3.15
PF-210 120 VAC 60 hz 120 2.58 120 0.09 120 20.00 22.67
PF-399 120 VAC 60 hz 120 2.58 120 0.21 120 20.00 22.79
BOILER DIMENSIONS & RATINGS