PureFire Installation, Operation, and Maintenance Manual

Series Peerless
®
PUREFIRE
®
Installation, Operation and Maintenance Manual Supplement
Scope:
These instructions are intended to:
1. Notify installing contractors about the temperature reset requirements required by the Federal government
under the Energy Policy and Conservation Act.
2. Provide information about a new internal reset feature designed to enhance the effi ciency of Peerless
®
PUREFIRE
®
boilers.
Compliance with the Energy Policy and Conservation Act:
The Federal Regulations affect only the Central Heating (CH) Mode settings of Peerless
®
PUREFIRE
®
boilers.
The following chart lists the CH modes and indicates which modes can only be used under the conditions listed
above.
NOTICE
These instructions are intended as a supplement to the Peerless
®
PUREFIRE
®
Installation, Operation
and Maintenance Instructions and are intended for use by a qualifi ed boiler repair technician.
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is
equipped with a feature that saves energy by reducing the boiler water temperature as the heating
load decreases. This feature is equipped with an override which is provided primarily to permit the
use of an external energy management system that serves the same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS
TRUE:
An external energy management system is installed that reduces the boiler water temperature
as the heating load decreases.
This boiler is not used for any space heating
This boiler is part of a modular or multiple boiler system having a total input of 300,000
BTU/hr or greater.
This boiler is equipped with a tankless coil.
Central Heating (CH) Mode Description Restrictions
0 (Indoor Thermostat) Fixed Setpoint Not for space heating
1 (Thermostat and Outdoor Reset) Outdoor Reset No restrictions
2 (Permanent Demand and Outdoor Reset) Outdoor Reset No restrictions
3 (Permanent Demand and Setpoint) Fixed Setpoint Not for space heating
4 (Analog 0-10 VDC Input – Setpoint) Analog Input
External Energy
Management System
5 (Analog 0-10 VDC Input – Modulation Rate) Analog Input
6 (Hydro-Air Unit) Fixed Setpoint Not for space heating
7* (Internal Reset) Default Internal Reset No Restrictions
* New default CH mode which adjusts boiler water temperature based on thermostat call duration.
Outdoor Sensor Open Warning:
1. In accordance with Federal Regulations, a warning error has been added to alert the installing contractor or
homeowner if the outdoor sensor circuit is open.
a. Warning errors on P
UREFIRE
®
boilers result in a blinking display screen.
The error message is accessed by pressing the “RESET” key on the display module.
This warning only affects CH mode #1 & #2 which use outdoor reset.
b. Pressing the “RESET” key on the display module will reveal the following text: “Warning Number #W00,
Outdoor Sensor Open”.
c. In this condition, the control will target a fi xed value which is the Boiler Design Temperature.
d. To operate at the maximum effi ciency while the sensor circuit is being repaired or replaced, use CH Mode 7.