Use And Care Manual

Page 13
No .
High
(left)
Low (right) Remarks
/ 0 1. by panel control 0. by dip switches
S1 1 1. electric heat only 0. electric heat and pump heat
For Heat Pump
unit only
S2 2 1. temperature display in °F 0. temperature display in °C
S3*S9 3
2. use some types of wall thermostat;
1. use PTAC other wall thermostat;
0. control panel enable.
You can consult with
the sales agency or
manufacturer for
details
S4*S5 4
4. 62°F~86°F (17°C~30°C) 1. 63°F~80°F (17°C~27°C)
3. 61°F~86°F (16°C~30°C) 0. 68°F~75°F (20°C~24°C)
2. 65°F~78°F (18°C~26°C)
S6 6 1. fan continuous run for heating 0. fan cycle for heating
S7 7 1. fan continuous run for cooling 0. fan cycle for cooling
S8 8 1. low temp. protection enable 0. low temp. protection disable Optional
SW7 A 1. front desk control disable 0. front desk control enable Optional
NOTE
1. The LED display window will show 00 when you first enter the setting mode, only when you set
01, can you start the next settings.
2. To activate front desk control function, you need to pull the dip switch SW7 to DOWN (OFF),
and then set the panel control to “A0”.
3. After all switches have been set, press up (+) and down (-) buttons together for 3 seconds to exit
the operation interface and cut off the power. When re-power on, the settings are activated.
4
DIP SWITCHES CONFIGURATIONS
by PANEL CONTROL
Turn off the unit.
Press the up (
+
) and down (
-
) buttons
together for 3 seconds to activate the
dip switches configurations by panel
control (see Fig. 5).
Table 2 - Dip Switches Configurations by Panel Control
NOTE
Press the up (+) and down (-) together
for 3 seconds again or no operation
within 30 seconds to exit the dip switches
configurations by panel control and the
unit will save the last settings
See Table 2 for Dip Switches configurations
and functions by panel control.
Display function settings with 2 digitals
in LED display window, high (left) for dip
switches, low (right) for functions (see
Fig. 5).
Press up (
+
) button to set the dip swithces,
press down (
-
) button to set the functons.
Dip Switches
Configurations
by Panel Control
Fig. 5
°
C
temperature
°
F
LED
display
window
High (left) Low (right)
01
If you follow the panel control dip switch configuration procedure, then the manual dip switch
configuration process (starting on
page 11) will no longer function.
NOTE