Cut Sheet

13
229 Waterford Street • Edinboro, PA 16412-2398
Phone 814.734.1631 • Fax 814.734.4946
13
PENN-STEMS • TYPES PSKS AND PSS
For terminating aluminum and ACSR conductors
Stem No. of
Cable
Crimps
Length
Con-
Maximum Conductor Wire Dia.
Range Hy- TDY-U
Catalog
(Approx.)
ductor
Diameter Range Range‡
Color Hand draulic Die Pressure
Number in. mm Range in. mm Aluminum ACSR in Code Tool Tool Size Setting
PSKS-44-2
1
/4 6 Str., 4 Sol. 6-6/1 .184-.204 Blue
PSKS-24-2
1
/4
2
1
/2 64 4 Sol. .204 5.15
4 Str., 2 Sol. 4-6/1, 7/1 .232-.258 Orange
PSKS-14-2
1
/4 2 Str., 1/0 Sol. 2-6/1, 7/1 .292-.325 Red
PSKS-04-2
1
/4 1/0 Str. 1/0-6/1 .373-.398 Yellow 3 1 BG,
5
/8 2
PSKS-22-3
1
/4 4 Str. 2 Sol. 4-6/1, 7/1 .232-.258 Orange
PSKS-12-3
1
/4 3
1
/4 83 2 Sol. .258 6.50 2 Str. 1/0 Sol. 2-6/1, 7/1 .292-.325 Red
PSKS-02-3
1
/4 1/0 Str. 1/0-6/1 .373-.398 Yellow
PSS-22-6
1
/2
6
1
/2 165 2 Sol. .258 6.50
4 Str. 2 Sol. 4 .232-.258 Orange
PSS-12-6
1
/2 2 Str. 1/0 Sol. 2 .292-.325 Red
.840
PSS-01-6
1
/2 1/0 Str. 1/0 .373-.398 Yellow 7 4 or 4
PSS-201-6
1
/2 6
1
/2 165 1/0 Sol. .325 8.33 2/0 Str. 2/0 .418-.447 Gray
B-249
PSS-301-6
1
/2 3/0 Str. 3/0 .470-.502 Black
PSS-401-6
1
/2 4/0 Str. 4/0 .528-.563 Pink
250 MCM
.575-.594PSS-2630-5
1
/2
266.8 MCM
300 MCM
266.8-18/1, 26/7 .609-.669PSS-3330-5
1
/2
5
1
/2 140 4/0 Sol. .460 11.70
336.4 MCM
Clear 4 1
1
/8-2 5
PSS-3930-5
1
/2
350 MCM 300-26/7
.681-.721
397.5 MCM 336.4-18/1,26/7
477 MCM 397.5-26/7, 30/7
PSS-4730-5
1
/2
500 MCM 477-18/1, 24/7 .793-.846
‡For conversion to metric range, see page 175.
Designed to be used in places where a terminal that was intended
to hold a copper wire is too small or unsuitable for an aluminum
wire, such as secondaries on transformers and meter entrances.
TIN PLATED SOFT
DRAWN COPPER STEM
LENGTH
CUAL-AID
®
FILLED
CABLE GROOVE
COLOR CODED
PLASTIC CAP
FACTORY BONDED
JOINT
pu_2399_cat.p65 1/14/09, 1:31 PM13
ALUMINUM TERMINAL PLUG • TYPES TP & TPO
For terminating copper or aluminum wire
Aluminum
Wire Diameter
Approximate Dimensions Crimping Tool Reference
Catalog Conductor
Range‡ A O.D. L
1
L
2
C
Die Color Burndy TPU TDY-1
Number Size in in in in in in Code Die Die Pressure Setting
TP-6 6 Str. .184
TP-4 4 Str. .232 .23 1.85 .68
TP-2 2 Str. .292 .60 1.75 Tan B-296 T-296 2
TP-1 1 Str. .332 .26 2.01
TP-1/0 1/0 Str. .373 .29 .84
TP-2/0 2/0 Str. .418 .33 2.21
TP-3/0 3/0 Str. .470 .37 .85 2.25 White B-298 T-298
TP-4/0 4/0 Str. .528 .42 2.59 1.22 5
TP-250 250 MCM .575 .47 2.63
TP-300 300 MCM .630 .53 1.10 2.50 Brown B-299 T-299
TP-350 350 MCM .681 .57 2.75 1.34
TP-400 400 MCM .728 .63
1.31 3.08 1.60 2.87 Pink B-300 T-300 7
TP-500 500 MCM .813 .68
TP-600 600 MCM .893 .73
1.46
3.67 1.64
3.75 Yellow B-936 9
TP-750 750 MCM .998 .81 3.79 1.76
OFFSET STYLE
TPO-2/0 2/0 Str. .418 .33 2.7 1.13
TPO-3/0 3/0 Str. .470 .37 .85 2.8 1.25 2.25 White B-298 T-298
TPO-4/0 4/0 Str. .528 .42 1.28
5
TPO-250 250 MCM .575 .47 3.0 1.28
TPO-300 300 MCM .630 .53 1.10
3.1 1.47
2.50 Brown B-299 T-299
TPO-350 350 MCM .681 .57
TPO-400 400 MCM .728 .63
1.32 3.4 1.69 2.87 Pink B-300 T-300 7
TPO-500 500 MCM .813 .68
TPO-600 600 MCM .893 .73
1.46
4.0
1.73 3.75 Yellow B-936 9
TPO-750 750 MCM .998 .81 4.2
‡For conversion to metric range, see page 175.
486B
LISTED
AL9CU
Optimum design to permit use of stranded copper or aluminum
conductor in equipment boards and boxes with mechanical con-
nectors.
Type TPO offset pin designed for use in limited spaces in equip-
ment boards and meter boxes.
Simply crimp onto the copper or wire brushed aluminum conduc-
tor and install into the mechanical connector supplied with the
equipment. No worry about cutting strands. No bulky in-line splice
boxes required.
The plug is made of aluminum, tin-plated and filled with Cual-
Aid
®
for a cool running compression connection. A cover is pro-
vided for quick insulation of the compression barrel. All required
information is marked on the plug.
C
L1
L2
A
O.D.
TPO SERIES
A
TP SERIES
L
1
L2
O.D.
12
pu_2399_cat.p65 1/14/09, 1:31 PM12
pu_24970_catA.indd 13 10/14/11 3:21 PM

Summary of content (1 pages)