User Guide

INSTALLATION PJB2175 & PJB4175
TROUBLESHOOTING
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
1. On light is OFF a. Burned - out bulb a. Replace bulb
b. Bad connection b. Correct defect
2. All lights are OFF a. Tripped breaker a. Reset breaker
b. Open GFCI b. Call Electrician
A wiring layout should be prepared ahead
of the installation of this Junction Box with
considerations given to the following details:
1. Installation shall be according to Article 680 of
the National Electric Code and all applicable
local Codes. This Junction Box is suitable for
either line or low voltage luminaires.
2. Use copper conductors only.
3. This Junction Box will accommodate water
resistant flexible cord, #16/3 or #14/3 Extra-
hard usage (Type SOW, STW or STOW) or,
#12/3 or #10/2 Hard usage (Type SJW, SJTW
or SJTWO).
Torque wire to terminal 15-20 lbf-in.
4. The Junction box must be rigidly supported
and unused conduit openings permanently
plugged with the plugs provided.
Installation
1. Determine best location for the Junction Box and run
properly sized conduits as per the wiring layout. The
Junction Box shall be located not less than 4 feet from
the inside wall of the pool. It must also be at least 8
inches above the maximum water level and not less
than 4 inches above deck or grade. (See Illustration)
Make sure the Junction Box can be rigidly supported. The
optional mounting bracket (Model PA114) is designed to
accommodate either wall or stake mounting.
2. Cut off all conduits at the same level. Use reducer
bushings furnished as needed for installation. For 1/2 inch
conduit, apply PVC Solvent Cement 1 inch down conduit
and to small inside diameter of reducer bushing. Slide
small end of reducer bushing over conduit to the stop
tab. For 3/4 inch conduit, break the stop tab off of reducer
bushing and PVC Solvent Cement large inside diameter
of reducer bushing to conduit. PVC Solvent Cement large
outside diameter of reducer bushings or 1 inch conduit
to Junction Box base. Permanently close all unused
conduit openings with the plugs provided.
3. An optional external bonding lug is provided. Connect to
Equipotential Bonding Grid, if your installation requires it.
4. Pull supply conductors from source and flexible cord
from luminaires into Junction Box. Use twist on wire
connectors or other approved termination method for
power connections. Connect ground conductors and
bonding conductors, if required, to ground bar. Tighten
terminal screws 35 in-lbs minimum.
5. Install strain reliefs. The direction that the clamps go on
depends on the diameter of cable. For cables smaller than
1/2 inch (#16/3 or #12/3), install clamps with the arrow
pointing down. For cables larger than 1/2 inch (#14/3 or
#10/2) install clamps with the arrow pointing up. Tighten
screws evenly until clamp bottoms out. If required, make
bonding connections to the grounding bar and to external
bonding lug.
6. Check tightness of connections, make sure gasket is
properly seated and close the Junction Box with the
screws provided.
NOT LESS THAN 4FT.
TOP FACE OF JUNCTION BOX BASE
JUNCTION BOX
PLUGS
NOT LESS THAN 4”
NOT LESS THAN 8”
DECK
LIMITED ONE-YEAR WARRANTY
If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, free of charge. This warranty
is extended to the original household purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused by accident, dropping or abuse in handling, acts of God or
any negligent use; (b) units which have been subject to unauthorized repair, opened, taken apart or otherwise modified; (c) units not used in accordance with instructions; (d) damages exceeding
the cost of the product; (e) sealed lamps and/or lamp bulbs, LED’s and batteries; (f) the finish on any portion of the product, such as surface and/or weathering, as this is considered normal wear
and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.
INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR
CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL
IMPLIED WARRANTIES, INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST ONLY
AS CONTAINED IN THIS LIMITED WARRANTY, AND SHALL BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. SOME STATES DO NOT ALLOW LIMITATIONS ON THE
DURATION OF AN IMPLIED WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.intermatic.com.
This warranty is made by: Intermatic Incorporated, Customer Service 7777 Winn Rd., Spring Grove, Illinois 60081-9698. For warranty service go to: http://www.Intermatic.com or call 815-675-
7000.
Because of our commitment to continuing research and improvements, Intermatic Incorporated reserves the right to make changes, without notice, in the specifications and material contained herein
and shall not be responsible for any damages, direct or consequential, caused by reliance on the material presented.
INTERMATIC INCORPORATED, SPRING GROVE, IL 60081-9698
http://www.intermatic.com
158--02085