User Guide

MASTERTEMP
®
Pool and Spa Heater Installation and User’s Guide Rev. M 1-8-15
22
2. Install the metal Flue Collar in the Vent Body
of the heater (located under the outside vent
cover). Fasten the metal Flue Collar to the Vent
Body with two #10 sheet metal screws. Use
high temperature silicone RTV to seal the Flue
Collar to the Vent Body. Before connecting
the metal Flue Collar to the Vent Body, wet a
clean cloth or paper towel with isopropyl alcohol
(rubbing alcohol) and vigorously wipe the socket
of the Vent Body. Immediately wipe the
cleaned surfaces dry with a clean cloth or
paper towel. Repeat for the exterior of the 4"
end of the metal Flue Collar. Attach the metal
Flue Collar to the Vent Body using the RTV
supplied with the kit, following the vent
manufacturers instructions (included with kit).
3. Attach the vent pipe to the metal Flue Collar
with sheet-metal screws.
WARNING
Risk of fire or asphyxiation if vent is not
assembled according to manufacturers
instructions or if vent parts from different
manufacturers are mixed. Vent parts from different
manufacturers ARE NOT interchangeable. Mixing
parts from more than one manufacturer may cause
leaks or damage to vent. When assembling a vent,
pick one manufacturer and be sure that all vent parts
come from that manufacturer and are specified by
the manufacturer for your system. Follow
manufacturer’s instructions, local code requirements,
National Fuel Gas Code requirements (U.S.) or
standards CSA B149.1 and B149.2 (Canada)
carefully during assembly and installation.
Section 3. Installation Instructions
6" (15 cm) Minimum
Clearance to Combustible
Materials
Listed
Termination
Cap
Storm Collar
Flashing
Firestop
Vent
Body
Metal Flue
Collar
Type B Double Wall
Metal Vent Pipe
Min. 10 Ft. (3.3 M)
Support Vertical
Vent Pipe so
adapter does not
take weight of
pipe. Dispose
of condensate
according to
local codes.
Type B Double Wall
Metal Vent Tee
Condensate
Drain w/trap
Min. 2 Ft.
(.7 M)
6" Minimum
Clearance to
Combustible
Materials
Listed
Termination
Cap
Storm Collar
Flashing
Firestop
Vent
Body
Metal Flue
Collar
Class B Double Wall
Metal Vent Pipe
Min. 10 Ft.
Support Vertical
Vent Pipe so
adapter does not
take weight of
pipe.
Figure 13. – Typical Metal Vent Pipe Installation - Canada
(Vertical – Negative Pressure)
Figure 12. – Typical Metal Vent Pipe Installation - U.S.
(Vertical – Negative Pressure)
NOTE
The allowable vent runs for each vent pipe diameter are different and can not be exceeded.
Each 90-degree elbow reduces the maximum horizontal vent run by 12 feet and each 45-degree elbow in
the vent run reduces the maximum vent run by 6 feet. See Table 7 on page 21 for the maximum vent lengths
using 90-degree and 45-degree elbows.