User Manual

P2P1
P1 P2 L N GND
L N
M
A1
N/O
N/C
A2
IMMERSION AND STARTING THE HP AT THE BEGINNING OF THE SEASON:
USE
Heating priority:
The ltration pump can be connected to the HP to force the ltration to operate if the water is not at the desired temperature.
Prior to this connection, a “dry contact” (normally open relay or connector) with a 230V AC coil should be provided.
Electrical connections:
Connect the coil of this relay (A1 and A2) on the P1 and P2 terminals of the HP.
Connect the input and the output of the dry contact (normally open) in parallel with the dry contact of the ltration clock of the swimming pool.
Cover the pool with a cover (bubble cover, shutter...) to reduce heat losses.
Once the HP is connected to the water circuit with the bypass, and is connected to the power supply by a professional, ensure that:
The HP is horizontal (level).
The HP is secured and stable.
The water circuit has been purged of air that has been trapped in the piping of the HP.
The pressure gauge, at the back of the HP, shows a temperature that is equal to the ambient outdoor temperature.
The water circuit is properly connected (no leaks or damage to the hydraulic connections, the connections are properly tightened).
The electric circuit is properly connected (the cables are tightly secured to the terminals and intermediate circuit-breaker), properly insulated, and connected to
the earthing connection.
The conditions of installation and use described above have all been met.
The outdoor temperature is between 0 and +35°C.
The water temperature is of 15°C minimum.
The evaporator at the rear/on the sides of the HP is clean (leaves, dust, pollen, cobwebs...)
You can now start your device by following, in the given order, the following steps:
Open the 3 valves of the bypass (refer to the hydraulic diagram).
Half-close the bypass valve.
Remove all unused items or tools from the area surrounding the HP.
Start the pump of the ltration system.
Power up the HP by engaging the circuit-breaker and using the ON/OFF button of the display.
Check that the HP starts and stops in sync with the ltration circuit: if no water is detected in the HP, the display shows “FLO”
The HP starts after a delay of a few minutes.
Adjust the temperature (“Regulation” chapter).
Adjust the water ow (“Water ow setting” chapter).
After a few minutes, you can adjust the bypass valve as indicated in the “Water ow setting” chapter. Having completed the above steps, cover the pool and let
the HP operate for a few days with the ltration pump in “forced mode” until the water of the pool reaches the desired bathing temperature.
Parameter for taking the connection into account:
Check that the setting of the ltration pump parameter
(parameter #9) is set to “1”. If this is not the case, please
contact us to change the setting.
ELECTRICAL CONNECTIONS:
8