BMF Series Media Filter Operating & Maintenance Manual PEP Filters • 322 Rolling Hill Road • Mooresville, NC 28117 • 800-243-4583 • www.pepfilters.com 704-662-3133 (Outside USA) Page 1 of 14 Fax 704-662-3155 rev.
BMF Series Media Filter Operating & Maintenance Manual Process Efficiency Products (“PEP Filters”) filtration equipment has been designed to give long, trouble-free service when properly installed, operated and maintained. This manual contains important installation procedures and should be read prior to installing. This manual is also a guide for proper filter operation, maintenance and winterizing.
BMF Series Media Filter Operating & Maintenance Manual General Description The BMF Series Industrial Water Filters are permanent media type units specifically designed to clean cooling tower and other industrial process water. The filters may be used for both side-stream and full stream applications in pressurized and nonpressurized systems. Standard BMF series filter vessels are rated for 50 psig (345 kpa). Optional higher pressure ratings of 100 psig (689 kpa) and 150 psig (1034 kpa) are also available.
BMF Series Media Filter Operating & Maintenance Manual Connect a backwash waste line to the connection labeled "Waste". This line carries the backwash wastewater to drain. Do not install a valve in the waste line. Refer to Table 3 for the minimum and maximum backwash flow rates. Note: If the drain is not large enough to handle the volume of water during backwash, it may be necessary to use a backwash water holding tank to buffer the backwash flow rate from the filter to the waste drain.
BMF Series Media Filter Operating & Maintenance Manual motor nameplate rating. 9. Check the unit for any unusual noise or vibration. 10. Check the unit for any air or water leaks. Any air leaks in the pump suction piping must be found and repaired. Failure to do so could result in poor performance and/or personal injury. 11. Backwash the filter. After backwashing the filter, check the pressure gauge on top of the filter tank and record the clean media operating pressure gauge (inlet gauge).
BMF Series Media Filter Operating & Maintenance Manual Maintenance Procedures Pump Pre-strainer (if equipped) Warning: Disconnect all electrical power prior to performing pump maintenance. The filter pre-strainer basket on the pump inlet must be checked regularly and kept free of debris. Failure to do so may damage the pump and/or motor. Shut off the power, close the valves, open the manual air relief valve, remove bolts and the pre-strainer cover.
BMF Series Media Filter Operating & Maintenance Manual Water Treatment Filtration is an effective way of reducing and managing the level of contamination in a fluid system. Still, there are other components of equal importance in a water treatment program. For cooling tower water and closed loop systems, often the water must be further treated to inhibit or prevent the deposition of dissolved solids on heat transfer surfaces.
BMF Series Media Filter Operating & Maintenance Manual Table 1 Type of Service General Condition of Unit Operation and Maintenance Schedule Start Up Monthly X X Semiannually Drain condensate from air line to pneumatic actuator (if applicable) As Required Clean pre-strainer basket As Required Inspect gaskets X X Check pump shaft for free rotation X X Check operation of valves X X X Check pump motor for proper rotation X Check motor voltage & current X Prime pump X Check pressure g
BMF Series Media Filter Operating & Maintenance Manual Table 2 Connection Sizes System (‘tower”) Water Backwash Filter Model Filter Inlet Filter Outlet Waste Outlet Inches / mm Inches / mm Inches / mm Optional Pump Inlet Inches / mm 4 / 100 4 / 100 4 / 100 6 / 150 6 / 150 6 / 150 6 / 150 8 / 200 4 / 100 4 / 100 4 / 100 6 / 150 6 / 150 6 / 150 6 / 150 8 / 200 4 / 100 4 / 100 4 / 100 6 / 150 6 / 150 6 / 150 6 / 150 8 / 200 3 / 76 3 / 76 4 / 100 4 / 100 4 / 100 6 / 150 6 / 150 6 / 150 BMF 54 BMF
BMF Series Media Filter Operating & Maintenance Manual Table 4A Table 5 Electrical Requirements – Three Phase, 50 Hz Pump Voltage (three phase) Full Load Current HP / KW 50 Hz Amps 7.5 / 5.6 380, 415 11.5, 10.6 10 / 7.5 380, 415 15.1, 13.5 15 / 11.2 380, 415 23.7, 22.4 20 / 15 380, 415 31.1, 29.
BMF Series Media Filter Operating & Maintenance Manual Table 5A Media Quantities for ASME Code BMF Filter Vessels Filter Model Under-drain Support Gravel Unigran 475 Standard 10 Micron Filtration Unigran 85 Optional 5 Micron Filtration Unigran 55 ft ft ft3 BMF 54 25 34 17 17 BMF 60 33 42 21 21 BMF 66 41 51 26 26 BMF 72 53 64 32 32 BMF 78 64 75 38 38 BMF 84 80 87 44 44 BMF 90 88 100 50 50 BMF 96 116 136 68 68 3 3 Unigran 85 ft 3 Note: To assure correct re
BMF Series Media Filter Operating & Maintenance Manual Refer to Table 6 for description and part numbers Table 6 Filter Parts Description Key Filter Model Part Number Item 1 BMF 54 Over-drain Schedule 80 PVC O-PVC80-BM-54 1 BMF 60 Over-drain Schedule 80 PVC O-PVC80-BM-60 1 BMF 66 Over-drain Schedule 80 PVC O-PVC80-BM-66 1 BMF 72 Over-drain Schedule 80 PVC O-PVC80-BM-72 1 BMF 78 Over-drain Schedule 80 PVC O-PVC80-BM-78 1 BMF 84 Over-drain Schedule 80 PVC O-PVC80-BM-84 1 BM
BMF Series Media Filter Operating & Maintenance Manual Description Key Filter Model 1 BMF 96 Part Number Item Over-drain Schedule 80 PVC O-PVC80-BM-96 Note: Refer to factory shop drawing to confirm over-drain materials of construction 2 All Filter Vessel 3 All Control Panel 4 All DP Switch 5 BMF 54 Under-drain Header & Laterals U-PVC80-BM-54 5 BMF 60 Under-drain Header & Laterals U-PVC80-BM-60 5 BMF 66 Under-drain Header & Laterals U-PVC80-BM-66 5 BMF 72 Under-drain Header
BMF Series Media Filter Operating & Maintenance Manual Description Key Filter Model Part Number Item 9 BMF 78 Manual City or Tower L-LA-BM-072-M- C or T 9 BMF 84 Automatic City or Tower L-LA-BM-084-A- C or T 9 BMF 84 Manual City or Tower L-LA-BM-084-M- C or T 9 BMF 90 Automatic City or Tower L-LA-BM-090-A- C or T 9 BMF 90 Manual City or Tower L-LA-BM-090-M- C or T 9 BMF 96 Automatic City or Tower L-LA-BM-096-A- C or T 9 BMF 96 Manual City or Tower L-LA-BM-096-M- C or T