VersiDrive i E3 User Guide Revision 1.03 AC-Drive VersiDrive i ...
VersiDrive i E3 User Guide Revision 1.03 Quick Start Up 1 1. Quick Start Up...................................................................................................................................................................... 4 1.1. Important Safety Information 4 1.2. Quick Start Process 5 2. General Information and Ratings ......................................................................................................................................... 7 2.1.
VersiDrive i E3 User Guide Revision 1.03 Declaration of Conformity 1 Quick Start Up PETER electronic GmbH & Co. KG hereby states that the VersiDrive i E3 product range conforms to the relevant safety provisions of the following council directives: 2004/108/EC (EMC) and 2006/95/EC (LVD) (Valid until 20.04.2016) 2014/30/EU (EMC) and 2014/35/EU (LVD) (Valid from 20.04.
Quick Start Up 1 VersiDrive i E3 User Guide Revision 1.03 1. Quick Start Up 1.1. Important Safety Information Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and Caution information elsewhere. Danger : Indicates a risk of electric shock, which, if not Danger : Indicates a potentially hazardous situation avoided, could result in damage to the equipment and other than electrical, which if not avoided, could possible injury or death. result in damage to property.
VersiDrive i E3 User Guide Revision 1.03 1.2. Quick Start Process 3 4 5 6 7 8 9 10 11 12 Select the correct power and motor cables according to local wiring regulations or code, noting the maximum permissible sizes If the supply type is IT or corner grounded, disconnect the EMC filter before connecting the supply. Check the supply cable and motor cable for faults or short circuits.
Quick Start Up 1 VersiDrive i E3 User Guide Revision 1.03 Quick Start – IP20 & IP66 Non Switched Connect a Start / Stop switch between control terminals 1 & 2 5k – 10k Close the Switch to Start Open to Stop Connect a potentiometer (5k – 10kΩ) between terminals as shown to vary the speed from P-2 (0Hz default) to P-01 (50 / 60 Hz default) 0....10V 0.......50/60Hz Quick Start – IP66 Switched Switch the unit on using the isolator switch on the panel.
VersiDrive i E3 User Guide Revision 1.03 2 2. General Information and Ratings This chapter contains information about the VersiDrive i E3 including how to identify the drive General Information and Ratings 2.1. Identifying the Drive by Model Number Each drive can be identified by its model number, as shown in the table below. The model number is on the shipping label and the drive nameplate. The model number includes the drive and any options. 2.2.
Mechanical Installation 3 VersiDrive i E3 User Guide Revision 1.03 3. Mechanical Installation 3.1. General • • • • • • The VersiDrive i E3 should be mounted in a vertical position only, on a flat, flame resistant, vibration free mounting using the integral mounting holes or DIN Rail clip (Frame Sizes 1 and 2 only). IP20 VersiDrive i E3s must be installed in a pollution degree 1 or 2 environment only.
VersiDrive i E3 User Guide Revision 1.03 3.5. Mechanical Dimensions – IP66 (Nema 4X) Enclosed Units 3 Mechanical Installation Drive Size A B mm in mm in 1 232.0 9.13 207.0 8.15 2 257.0 10.12 220.0 8.67 3 310.0 12.20 276.5 10.89 Mounting Bolts All Frame Sizes Tightening Torques All Frame Sizes D E mm in mm 189.0 7.44 25.0 200.0 7.87 28.5 251.5 9.90 33.4 4 x M4 (#8) Control Terminals Power Terminals F in 0.98 1.12 1.31 mm 179.0 187.0 252 In 7.05 7.36 9.92 G mm in 161.0 6.34 188.0 7.40 211.0 8.
VersiDrive i E3 User Guide Revision 1.03 Mechanical Installation 3 3.7. Gland Plate and Lock Off The use of a suitable gland system is required to maintain the appropriate IP / Nema rating. The gland plate has pre moulded cable entry holes for power and motor connections suitable for use with glands as shown in the following table. Where additional holes are required, these can be drilled to suitable size. Please take care when drilling to avoid leaving any particles within the product.
VersiDrive i E3 User Guide Revision 1.03 4 4. Power Wiring This manual is intended as a guide for proper installation. PETER electronic GmbH & Co. KG cannot assume responsibility for the compliance or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
VersiDrive i E3 User Guide Revision 1.03 Power Wiring 4 4.4. Incoming Power Connection • • • • • • • • • • • For 1 phase supply, power should be connected to L1/L, L2/N. For 3 phase supplies, power should be connected to L1, L2, and L3. Phase sequence is not important. For compliance with CE and C Tick EMC requirements, a symmetrical shielded cable is recommended.
VersiDrive i E3 User Guide Revision 1.03 4.7. Motor Thermal overload Protection 4 4.7.1. Internal Thermal Overload Protection 4.7.2. Motor Thermistor Connection Where a motor thermistor is to be used, it should be connected as follows:Control Terminal Strip 1 2 3 4 Additional Information • Compatible Thermistor : PTC Type, 2.5kΩ trip level • Use a setting of P-15 that has Input 3 function as External Trip, e.g. P-15 = 3. Refer to section 7 for further details. • Set P-47 = “ptc-th ptc-th" ptc-th 4.8.
VersiDrive i E3 User Guide Revision 1.03 Power Wiring 4 4.10. Using the REV/0/FWD Selector Switch (Switched Version Only) By adjusting the parameter settings the VersiDrive i E3 can be configured for multiple applications and not just for Forward or Reverse. This could typically be for Hand/Off/Auto applications (also known and Local/Remote) for HVAC and pumping industries.
VersiDrive i E3 User Guide Revision 1.03 5 5. Operation Operation 5.1. Managing the Keypad The drive is configured and its operation monitored via the keypad and display.
Parameters 6 VersiDrive i E3 User Guide Revision 1.03 6. Parameters 6.1. Standard Parameters Par. P-01 P-02 P-03 P-04 P-05 P-06 P-07 P-08 P-09 P-10 P-11 Description Minimum Maximum Default Units Maximum Frequency / Speed Limit P-02 500.0 50.0 (60.0) Hz / RPM Maximum output frequency or motor speed limit – Hz or RPM. If P-10 >0, the value entered / displayed is in RPM Minimum Frequency / Speed Limit 0.0 P-01 0.0 Hz / RPM Minimum speed limit – Hz or RPM.
VersiDrive i E3 User Guide Revision 1.03 P-13 Par. P-15 P-16 P-17 Description Minimum Maximum Default Units Digital Input Function Select 0 17 0 Defines the function of the digital inputs depending on the control mode setting in P-12. See section 7 Analog and Digital Input Macro Configurations for more information. Analog Input 1 Signal Format See Below U0-10 U 0-10 = Uni-polar 0 to 10 Volt Signal.
Par. P-25 Parameters 6 VersiDrive i E3 User Guide Revision 1.03 P-26 P-27 P-28 P-29 P-30 P-31 P-32 18 Description Minimum Maximum Default Units Analog Output Function Select 0 10 8 Digital Output Mode. Logic 1 = +24V DC 0 : Drive Enabled (Running). Logic 1 when the VersiDrive i E3 is enabled (Running) 1 : Drive Healthy. Logic 1 When no Fault condition exists on the drive 2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency 3: Drive Tripped.
VersiDrive i E3 User Guide Revision 1.03 P-35 P-36 P-37 P-38 P-39 P-40 P-41 P-42 P-43 P-44 P-45 www.peter-electronic.com 19 Parameters P-34 Description Minimum Maximum Default Units Spin Start 0 2 0 0 : Disabled 1 : Enabled. When enabled, on start up the drive will attempt to determine if the motor is already rotating, and will begin to control the motor from its current speed. A short delay may be observed when starting motors which are not turning.
Par. P-46 Parameters 6 VersiDrive i E3 User Guide Revision 1.03 P-47 P-48 P-49 P-50 Description Minimum Maximum Default Units PI Feedback Source Select 0 5 0 Selects the source of the feedback signal to be used by the PI controller. 0 : Analog Input 2 (Terminal 4) Signal level readable in P00-02. 1 : Analog Input 1 (Terminal 6) Signal level readable in P00-01 2 : Motor Current. Scaled as % of P-08. 3 : DC Bus Voltage Scaled 0 – 1000 Volts = 0 – 100% 4 : Analog 1 – Analog 2.
VersiDrive i E3 User Guide Revision 1.03 6.4.
Analog and Digital Input Macro Configurations 7 VersiDrive i E3 User Guide Revision 1.03 7. Analog and Digital Input Macro Configurations 7.1. Overview VersiDrive i E3 uses a Macro approach to simplify the configuration of the Analog and Digital Inputs. There are two key parameters which determine the input functions and drive behaviour:• P-12 – Selects the main drive control source and determines how the output frequency of the drive is primarily controlled.
VersiDrive i E3 User Guide Revision 1.03 14 STOP 15 16 17 STOP STOP STOP DI1 DI2 DI3 / AI2 START FWD STOP (NC) (NO) START REV ˄-----------------------------FAST STOP (P-24)---------------------------------------------˄ RUN DI2 E-TRIP OK RUN RUN RUN P-23 REF P-23 REF AI1 P-21 REF Fire Mode Fire Mode Fire Mode DI2 DI4 / AI1 KPD REF P-20 REF DI2 0 1 0 1 DI4 PR 0 P-20 0 P-21 1 P-22 1 P-23 Analog Input AI1 FWD REV DI2 DI4 PR 0 0 P-20 1 0 P-21 0 1 P-22 1 1 P-23 7.4.
VersiDrive i E3 User Guide Revision 1.03 Analog and Digital Input Macro Configurations 7 7.7. Fire Mode The Fire Mode function is designed to ensure continuous operation of the drive in emergency conditions until the drive is no longer capable of sustaining operation. The Fire Mode input may be a normally open (Close to Activate Fire Mode) or Normally Closed (Open to Activate Fire Mode) according to the setting of P-30 Index 2.
VersiDrive i E3 User Guide Revision 1.03 8 8. Modbus RTU Communications Modbus RTU Communications 8.1. Introduction The VersiDrive i E3 can be connected to a Modbus RTU network via the RJ45 connector on the front of the drive. 8.2. Modbus RTU Specification Protocol Error check Baud rate Data format Physical signal User interface Modbus RTU CRC 9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default) 1 start bit, 8 data bits, 1 stop bits, no parity. RS 485 (2-wire) RJ45 8.3.
Technical Data 9 VersiDrive i E3 User Guide Revision 1.03 9. Technical Data 9.1. Environmental Operational ambient temperature range Storage ambient temperature range Maximum altitude Maximum humidity NOTE Open Drives Enclosed Drives : : : : : -10 … 50°C (frost and condensation free) -10 ... 40°C (frost and condensation free) -40 … 60°C 2000m. Derate above 1000m : 1% / 100m 95%, non-condensing For UL compliance: the average ambient temperature over a 24 hour period for 200-240V, 2.
VersiDrive i E3 User Guide Revision 1.03 9.4. Additional Information for UL Compliance 9 Input Power Supply Requirements Supply Voltage Imbalance Frequency Short Circuit Capacity 200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum 380 – 480 Volts for 400 Volt rated units, + / - 10% variation allowed, Maximum 500 Volts RMS Maximum 3% voltage variation between phase – phase voltages allowed All VersiDrive i E3 units have phase imbalance monitoring.
Trouble Shooting 10 VersiDrive i E3 User Guide Revision 1.03 10. Trouble Shooting 10.1. Fault Code Messages Fault Code No. Description Suggested Remedy no-Flt OI-b OL-br O-I I.t-trp I.