Datasheet
Subject to change without notice.
A
C
B
Techni
cal data
FUS ... /L5
FUS .../3L5
020
037
075
150
220
075
150
220
m
otor
shaft power
/ kW
0,2
0,37
0,75
1,5
2,2
0,75
1,5
2,2
mains voltage
according to DIN EN 50160 (IEC 38)
single
-
phase
200-240V ,+10%, -15%
50/60Hz
±
5%
three
-
phase
380-460V,+10%,-15%
50/60Hz
±
5%
output current
/ A
1,8A
2,6A
4,3A
7,5A
10,5A
2,3A
3,8A
5,2A
control functions
frequency setting range
0
—
650Hz
torque boost
6
fixed
U/
f
-
characteristic
, fre
e
configurable
U/
f
-
characteristic
r
amp
-
up and ramp
-
down time
0 …
3
600s
frequency setpoint
p
otentiometer >= 1kΩ, 0
-
10V, 0/4
-
20mA,
keypad
,
keypad p
ot
entiometer
,
fixed frequencies
,
m
otor
pot
entiometer
, Modbus
ambient
/
storage
temperatur
e
-
10 … 40°C (
-
10 … 50°C für BG 2),
-
2
0 … 60°C
design size
1
2
2
weight
/ kg
0,7
0,9
1,6
1,7
Dimensions:
Connection Diagram:
size
A
B
C
1
72
141
14
1
2
118
144
1
50
All dimensions indicated in mm
AC drive FUS … /L5/3L5
up to
2,2kW
4.18
S5
Analog output
0-10V
Ext. analog-signal 0-10V
FM
AO
AGND
10V
AVI
AGND
24V
L3 (N)
S1
S2
S3
S4
L1 (L)
L2
CON 2
Interface for
communication expansion units
RS 485
PE
Earthing
Motor
T3
T1
T2
Braking
resistor
BR
+
-
RB
RA
Relay output
Multi-functional inputs
L1
L2
L3
L1
N
L1 (L)
L3 (N)
additional Mains filter
(for class B)
single-phase three-phase
P
E
ACI
0-20mA
4-20mA