Appendix-2 Instructions for UL
Recommended Input Fuse Selection
Motor Overtemperature Protection
Motor overtemperature protection shall be provided in the end use application.
Field Wiring Terminals
All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to
be made to each terminal and indicate that copper conductors, rated 75°C are to be used.
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise
above value. Please see electrical ratings for maximum voltage and table below for current.
The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit tolerance of
the power supply being used.
Suitable for use on a circuit capable of delivering not more than ( A ) RMS symmetrical amperes for ( Hp ) Hp in 240 / 480 V class drives
motor
overload protection.
Horse Power ( Hp ) Current ( A ) Voltage ( V )
1- 50 5,000 240 / 480
51- 200 10,000 240 / 480
201 - 400 18,000 240 / 480
401 - 600 30,000 240 / 480
Fuse Type
Drive Model FUS ... Manufacturer: Bussmann
Model Fuse Ampere Rating (A)
200 V Class Single-Phase Drives
020/L5 Bussmann 10CT 690 V, 10 A
037/L5 Bussmann 10CT/16CT 690 V, 10 A / 690 V, 16 A
075/L5 Bussmann 16CT/20CT 690 V, 16 A / 690 V, 20 A
150/L5 Bussmann 30FE 690 V, 30 A
220/L5 Bussmann 50FE 690 V, 50 A
Fuse Type
Drive Model FUS ... Manufacturer: Bussmann
Model Fuse Ampere Rating (A) [A]
400 V Class Three-Phase Drives
075/3L5
Bussmann 10CT 690 V, 10 A
150/3L5
Bussmann 16CT 690 V, 16 A
220/3L5
Bussmann 20CT 690 V, 20 A