User manual

App 3-11
4.5 Write holding register [06H]
Specified data are written into the several specified holding registers from the Specified
respectively.
(Example)Set SLAVE station No:01, write L510 drive frequency reference 60.0HZ.
ASCII Mode
Instruction Message Response Message (Normal) Response(Fault)
3AH STX 3AH STX 3AH STX
30H 30H 30H
31H
SLAVE
Address
31H
SLAVE
Address
31H
SLAVE
Address
30H 30H 38H
36H
Function
Code
36H
Function Code
36H
Function Code
41H 41H 35H
30H 30H 32H
Error Code
30H 30H ?
32H
Start
Address
32H
Start
Address
?
LRC CHECK
0DH
31H 31H
0AH
END
37H 37H
37H 37H
30H
DATA
30H
DATA
? ?
?
LRC CHECK
?
LRC CHECK
0DH 0DH
0AH
END
0AH
END
RTU Mode
Instruction Message Response Message (Normal) Response(Fault)
SLAVE Address 01H SLAVE Address 01H SLAVE Address 01H
Function Code 06H Function Code 06H Function Code 86H
High
A0H
High
A0H
Error Code
52H Start
Address
Low
02H
Start
Address
Low
02H
High
C3H
High
17H
High
17H
CRC-16
Low
9DH
DATA
Low
70H
DATA
Low
70H
High
04H
High
04H
CRC-16
Low
1EH
CRC-16
Low
1EH