06- 37 Auto_ Run Mode Running Direction5
06- 38 Auto_ Run Mode Running Direction6
06- 39 Auto_ Run Mode Running Direction7
Range
【0】: STOP 【1】: Forward 【2】: Reverse
Auto Run sequencer mode has to be enabled by using one of the multifunctional inputs S1 to S5
and setting the relevant parameter 03-00 to 03-04 to selection【18】.
Various Auto Run (sequencer) modes can be selected by parameter (06-00) as listed above.
7 Auto Run (sequencer) modes can be selected by parameters (06-01~06-39)
Auto Run frequency commands1 to 7 are set with Parameters (06-01 ~ 06-07),
Sequence run times are set with parameters (06-17 ~ 06-23)
FWD/REV Direction for each sequence can be set with parameters (06-33 ~ 06-39).
Auto sequence 0, frequency is set from keypad by parameter 05-01, sequence run time and
direction are set by parameters 06-16 and 06-32.
Auto RUN (Auto Sequencer) examples are shown in the following pages:-
Example 1. Single Cycle (06- 00=1,4)
The inverter will run for a single full cycle based on the specified number of sequences, then it
will stop. In this example 4 sequences are set, three in forward direction and one in Reverse.
Auto Run Mode. 06- 00=【1】or【4】,
Frequency 05- 01=【15】Hz, 06- 01=【30】Hz, 06- 02=【50】Hz, 06- 03=【20】Hz
Sequence Run Time 06-16=【20】s, 06-17 =【25】s, 06-18=【30】s, 06-19=【40】s,
Direction 06-32=【1】FWD, 06-33 =【1】FWD, 06-34=【1】(FWD), 06-35=【2】(REV)
Unused Sequence Parameters 06-04~ 06-07=【0】Hz , 06-20~06-23=【0】s , 06-36~06-39=【0】
05-01
06-01
06-02
06-03
06-16
06-17
06-18
06-19
T
Hz
RUN command
RUN
ON
S1 to S5 auto
run enable