User manual
4-51
09- Communication function group
09- 00 Assigned Communication Station Number
Range
【1 ~ 32】
09-00 sets the communication station number when there are more that one unit on the
communication network. Up to 32 Slave units can be controlled from one master controller such
as a PLC.
09- 01 RTU code /ASCII code Selection
Range
【0】:RTU
【1】:ASCII
09- 02 Baud Rate Setting (bps)
Range
【0】:4800
【1】:9600
【2】:19200
【3】:38400
09- 03 Stop Bit Selection
Range
【0】:1 stop bit
【1】:2 stop bit
09- 04 Parity Selection
Range
【0】:no parity
【1】:even parity
【2】:odd parity
09- 05 Data Format Selection
Range
【0】:8 bit data
【1】:7 bit data
Set 09-01~09-05 to configure communication format before starting communication.
09- 06 Communication time-out detection time
Range
【0.0~25.5】Sec
09- 07 Communication time-out operation selection
Range
【0】:Stop in deceleration time 1 and show COT after communication timeout
【1】:Stop in free run mode and show COT after communication timeout
【2】:Stop in deceleration time 2 and show COT after communication timeout
【3】:Keep running and show COT after Communication timeout
Time-out detection time: 00.0~25.5 seconds; setting 00.0 seconds: disables time-out function.
09- 08 Err6 fault tolerance times
Range
【1~20】
When communication error time ≥ 09-08 setting,keypad display shows ERR6.
09- 09 Drive Transmit Wait Time
Range
【5~65】m s
This parameter is used to set the converter to receive data from the sending date to the
beginning of the time.