User manual

4-51
09- Communication function group
09- 00 Assigned Communication Station Number
Range
1 ~ 32
09-00 sets the communication station number when there are more that one unit on the
communication network. Up to 32 Slave units can be controlled from one master controller such
as a PLC.
09- 01 RTU code /ASCII code Selection
Range
0:RTU
1:ASCII
09- 02 Baud Rate Setting (bps)
Range
0:4800
1:9600
2:19200
3:38400
09- 03 Stop Bit Selection
Range
0:1 stop bit
1:2 stop bit
09- 04 Parity Selection
Range
0:no parity
1:even parity
2:odd parity
09- 05 Data Format Selection
Range
0:8 bit data
1:7 bit data
Set 09-01~09-05 to configure communication format before starting communication.
09- 06 Communication time-out detection time
Range
0.0~25.5Sec
09- 07 Communication time-out operation selection
Range
0:Stop in deceleration time 1 and show COT after communication timeout
1:Stop in free run mode and show COT after communication timeout
2:Stop in deceleration time 2 and show COT after communication timeout
3:Keep running and show COT after Communication timeout
Time-out detection time: 00.0~25.5 seconds; setting 00.0 seconds: disables time-out function.
09- 08 Err6 fault tolerance times
Range
1~20
When communication error time 09-08 settingkeypad display shows ERR6.
09- 09 Drive Transmit Wait Time
Range
5~65m s
This parameter is used to set the converter to receive data from the sending date to the
beginning of the time.