User's Manual

10 36ARB2 050505-36
VENTING
Before installing venting for this unit, the installer should read
these instructions to insure that the proper vent con guration
has been selected.
Use only Town and Country Termination kits #:
TCVT.WTA - Wall Termination Kit
TCVT.RTA - Roof Termination Kit
Vent system components approved for use with the Town and
Country Fireplace are shown in Figure #13.
Various combinations of vertical and horizontal runs may be
used. Refer to #
17 and 18 for details. For optimum performance
and  ame appearance, keep the vent length to a minimum and
limit the number of elbows. Connections between each vent
system component must be tightly joined, secured with sheet
metal screws and sealed. A horizontal run of vent should have
a 1/4" rise for every 1 ft. of run towards the termination.
CAUTION: UNDER NO CONDITION SHOULD COMBUSTI-
BLE MATERIAL BE CLOSER THAN 1 3/4 INCHES FROM
THE TOP AND 1 3/4 INCHES FROM THE SIDES OF A
HORIZONTAL SECTION AND 1 3/4 INCHES FROM THE
VERTICAL SECTIONS OF THE VENT PIPE.
Vent System Town &
Components Country
12" Pipe Length ........................... TCVT.811X12
18" Pipe Length ........................... TCVT.811X18
24" Pipe Length ........................... TCVT.811X24
48" Pipe Length ........................... TCVT.811X48
18" Adjustable Pipe Length ......... TCVT.811X12ADJ
45° Elbow .................................... TCVT.811XLB45
90° Elbow .................................... TCVT.811XLB90
Wall/Offset Support ..................... TCVT.811XOS
Wall Termination Kit .................... TCVT.WTA
Roof Termination Kit .................... TCVT.RTA
Wall Shield/Ceiling Firestop ......... TCVT.THIMA
Roof Flashing, Adjustable ............ TCVT.811FLADJ
Roof Flashing, Flat ...................... TCVT.811FLFLT
Roof Flashing, Steep ................... TCVT.811FLSTP
or any that  ts 11" pipe
Fig. # 13
WALL TERMINATION VENTING
Exterior wall opening:
Determine the exact position of the  replace so that the vent
pipe is centred (if possible) between two building framing
members. Consult your local building codes prior to proceed-
ing. The vent kit will accommodate up to a maximum wall
thickness of 12 inches.
1) Having determined the position of the  replace, cut and
frame a 14 1/2 inch opening centred at a minimum height
of
68 1/2 inches above the  oor. The opening may be
round or square. Height of the opening will vary with each
installation. As the horizontal vent run increases, so does
the minimum vertical rise (see Fig. #17).
IMPORTANT: When locating the opening, it should be
noted that vent terminal clearances must be maintained.
See "Vent Terminal Clearances" section for proper clear-
ances.
A minimum 2 foot length of pipe is required for any wall termi-
nation. With this minimum vertical rise in combination with a
90° elbow, a maximum horizontal run of 18 inches is permitted
(see Fig. #17 and 18). For longer horizontal runs greater than
18 inches, increase vertical rise appropriately.
The rise and run must be constrained to the boundaries of the
chart shown in  gure #17. The horizontal run of vent must have
a 1/4" rise for every 1 ft. of run towards the termination.