User's Manual

(Bit Address+Destination End Point =
0x05)
(Bit Address =0
Destination End Point =
command owner Endpoint value)
Command Class = 0x32 (Command_Class_Meter_V3 = 0x32)
Command =0x02 (Meter_Report = 0x02)
Parameter 1 = 0xA1 (Scale Bit2 = 1
Rate Type = 0x01
Meter Type=0x01)
Parameter 2 = 0x51 (Precision = 2
Scale Bit1Bit0 = 0x10
Size
= 1)
Parameter 3 = 0x63 Power Factor = 0x63 = 0.99
Note : If the Destination End Point is 1, it will report the power factor of CT1, but not
the sum of PF of CT1 and CT2.
3.Z-Wave’s Configuration
Configuration
Parameter
Function Size
(Byte)
Value Unit Default Description
1 Watt
Meter
Report
Period
2 0x01-
0x7FFF
5s 720 5*720s=3600s=1
hour
2 KWH 2 0x01- 5s 720 5*720s=3600s=1
Meter
Report
Period
0x7FFF hour
3 Slected
End Point
1 1-3 1 1
CT1 and CT2
2
CT1
3
CT2
4 Threshold
of Current
for Load
Caution
2 10-750
0.01A
750
750*0.01A=7.5A
5 Threshold
of KWH
for Load
Caution
2 1-10000 1KWh 10000
3-1 Watt Meter Report Period:
If the setting is configured for 1hour (set value =720), the PAB01 will report its
instant power consumption every 1 hour to the node of correspond Group. The
maximum interval to report its instant power consumption is 45 hours
(5s*32767/3600=45hr).