User Manual

off.
No node ID Under normal operation, when the Switch has not been allocated a
node ID, the LED flashes on and off alternately at 2-second
intervals. By pressing S1 S2 or On/Off button, it will stop flashing
temporarily. However, after disconnect and reconnect the Switch,
the LED will flash on and off alternately at 2-second intervals.
Learning When PAB01 is in learning mode, LED flashes on and off
alternately and repeatedly at 0.5 second intervals.
Choosing a Suitable Location
1. Do not locate the Switch facing direct sunlight, humid or dusty place.
2. The suitable ambient temperature for the Switch is 0°C~40°C.
3. Do not locate the Switch where exists combustible substances or any source of
heat, e.g. fires, radiators, boiler etc.
4. After putting it into use, the body of Switch will become a little bit hot of which
phenomenon is normal.
Installation
1. Put the in wall switch into a wall box and connect the AC power wire L,N to
PAN05 connector L, N.
2. Connect the wall switch to the PAN05 as Fig1 .
3. There are 3 mode PAN05 can be configured to match different kind of wall
switch, please refer to 3-1 Edge / Pulse / Edge-Toggle mode which described
in next section of this user manual.
4. If Edge-Toggle mode has been set, and the S1 S2 is connect to normal bi-stable
switch, every time when change the state of the wall switch will also swap the
state of Relay1.
Programming
1. Basic Command Class / Binary Switch Command Class
The Switch will respond to BASIC and BINARY commands that are part of the Z-
3