User Manual

The content of Alarm Report
Alarm report command:[Command Class Alarm, Alarm Report, Alarm Type
= 0x08, Alarm Level = 0xFF]
3. Z-Wave’s Configuration
Configuration
Parameter
Function Size
(Byte)
Value Unit Default Description
1 Edge or
Pulse
mode or
Edge-Tog
gle mode
1 1-3 1
1Edge mode
2Pulse mode
3Edge-Toggle
mode
5 Restore
switch
state
mode
1 0-2 1
0 : Switch Off
1 : Last Switch
State
2 : Switch On
6 Manual
On/Off
mode
1 0-1 1
0Disable
manual On/Off
1Enable
manual On/Off
7 LED
indication
mode
1 1-2 1
1Show switch
state
2Show night
mode
8 Auto off
timer
1 0-
0x7FFF
Second
0
0Disable auto
off function
1-0x7FFF1 ~
32767seconds
9 RF Off
command
mode
1 0-3 0
0Switch off
1Ignore
2Switch toggle
3Switch on
3-1 Edge / Pulse / Edge-Toggle mode
Manual switch S1 and S2 can set to Edge mode or Pulse mode or Edge-Toggle
mode , default value is Edge mode.
Edge mode: this mode is suitable for the bi stable wall switch that has indicator point
on the switch, and the same position correspond to same state of relay1. if the
PAN05 relay change the state because of receiving Z-Wave RF command, it may
need two times of change (switch on to off or switch off to on) to let relay back to the
correspond state. Manual switch S2 is disabled in this mode.
Pulse mode: this mode is suitable for the toggle type wall switch to swap the state of
Relay1.
Edge-Toggle mode: this mode is suitable for the normal bi-stable switch, every time
when change the state of the wall switch will also swap the state of Relay1.
3-2 Restore Switch State Mode
Whenever the AC power reconnected to PAN05, it will set the switch to Off
On or
Last switch state, default value is Last switch state.
3-3 Manual On/Off Mode
The On/Off function of S1
S2 and learn switch can be disabled or enabled by this
parameter, default value is Enable.
5